Model 9016 X-Purge Operator Interface
Daisy Data Displays, Inc.
February 2022
7
D010-000002
11.
Slowly increase air pressure
with the regulator until the purge process stops.
Note Pressure the pressure at which the purge process stops.
The Purge Status LED will flash red and display an error code -
[2 – 2]
(over
pressure) or
[3 –2]
(over-flow).
12.
Remove AC power
from the enclosure for a minimum of 30 seconds. Decrease
the pressure reading on the pressure gauge by 5 PSI.
This change may vary slightly on some units; if in later testing the unit fails with
an
[3 –2]
(over-flow) error code, decrease the inlet pressure by another 2 PSI.
Note Pressure for use during start-up.
13.
Re-apply AC power.
The Purge Status LED will illuminate yellow and should purge
for a minimum of 8 minutes. Time will vary according to the flow rate of the air
into the enclosure.
14.
After the purge is complete
, the Purge Status indicator will illuminate green.
AC power is now applied to the internal electronics to power on the display or PC.
15.
If the purge status light blinks red
, refer to Table 6.1 X-Purge Status Light Key on
page 12 for error code details.
Содержание 9016 X-Purge
Страница 1: ...February 2022 D010 000002 Model 9016 X Purge User Manual...
Страница 19: ...Page 19...
Страница 20: ...Page 20...
Страница 21: ...Page 21...
Страница 22: ...Page 22...
Страница 23: ...Page 23...
Страница 24: ...Page 24...
Страница 25: ...Page 25...
Страница 26: ...Page 26...
Страница 27: ...Page 27...
Страница 28: ...Page 28...
Страница 29: ...Page 29...
Страница 30: ...Page 30...
Страница 32: ......
Страница 33: ......
Страница 34: ...Page 34...
Страница 35: ...Page 35...
Страница 36: ...Page 36...
Страница 37: ...Page 37...
Страница 38: ...Page 38...
Страница 39: ...Page 39...