Field Setting
SiENBE34-703
76
Test Operation
3.1.6 Detailed Explanation of Setting Modes
Filter Sign Setting
If switching the filter sign ON time, set as given in the table below.
Set Time
Ultra-Long-Life Filter Sign Setting
When a Ultra-long-life filter is installed, the filter sign timer setting must be changed.
Setting Table
External ON/OFF input
This input is used for "ON / OFF operation" and "Protection device input" from the outside. The
input is performed from the T1-T1 terminal of the operation terminal block (X1A) in the electric
component box.
Setting Table
Fan Speed Changeover When Thermostat is OFF
By setting to “Set Fan Speed,” you can switch the fan speed to the set fan speed when the
heating thermostat is OFF.
∗
Since there is concern about draft if using “fan speed up when thermostat is OFF,” you should
take the setup location into consideration.
Setting Table
Filter Specs.
Setting
Standard
Long Life
Ultra Long Life Filter
Contamination Light
200 hrs.
2,500 hrs.
10,000 hrs.
Contamination Heavy
100 hrs.
1,250 hrs.
5,000 hrs.
Mode No.
Setting Switch No.
Setting Position No.
Setting
10 (20)
1
01
Long-Life Filter
02
Ultra-Long-Life Filter (1)
03
—
F2 T1 T2
Forced stop
Input A
Mode No.
Setting
Switch No.
Setting
Position No.
Operation by input of the signal A
12 (22)
1
01
ON: Forced stop (prohibition of using the remote control)
OFF: Permission of using the remote control
02
OFF
→
ON: Permission of operation
ON
→
OFF: Stop
03
ON: Operation
OFF: The system stops, then the applicable unit
indicates "A0". The other indoor units indicate "U9".
Mode No.
First Code No.
Second Code No.
Setting
12(22)
3
01
LL Fan Speed
02
Set Fan Speed
Содержание VRVIII-S
Страница 1: ...SiENBE34 703 Basic Training Manual R 410A Heat Pump 50Hz Service Manual...
Страница 11: ...Introduction SiENBE34 703 x...
Страница 16: ...SiENBE34 703 Specifications 5 Part 2 Specifications 1 Specifications 6 1 1 Outdoor Units 6 1 2 Indoor Units 8...
Страница 113: ...Field Setting SiENBE34 703 102 Test Operation...
Страница 207: ...Troubleshooting by Indication on the Unified ON OFF Control SiENBE34 703 196 Troubleshooting...
Страница 215: ...Wiring Diagrams SiENBE34 703 204 Appendix 2 3 Indoor Unit FXCQ20 25 32 63M8...
Страница 216: ...SiENBE34 703 Wiring Diagrams Appendix 205 FXCQ40 50 80 125M8V3...
Страница 217: ...Wiring Diagrams SiENBE34 703 206 Appendix FXFQ25 32 40 50 63 80 100 125P7VE...
Страница 218: ...SiENBE34 703 Wiring Diagrams Appendix 207 FXZQ20 25 32 40 50M8V1...
Страница 221: ...Wiring Diagrams SiENBE34 703 210 Appendix FXDQ20 25M8V3...
Страница 222: ...SiENBE34 703 Wiring Diagrams Appendix 211 FXSQ20 25 32 40 50 63 80 100 125M8V3...
Страница 232: ...SiENBE34 703 Option List Appendix 221...
Страница 235: ...Example of Connection SiENBE34 703 224 Appendix...
Страница 241: ...Method of Replacing the Inverter s Power Transistors Modules SiBE34 703 230 Appendix...
Страница 261: ...RXYSQ4 5 6 P7Y1B SiENBE34 703 250 Removal Procedure...