Outline of Control (Indoor Unit)
SiENBE34-703
64
Function
6.6 Electronic Expansion Valve Control
• Electronic expansion Valve Control
In cooling, to maximize the capacity of indoor unit heat exchanger (evaporator), operate the
electronic expansion valve under PI control so that the evaporator outlet superheated degree
(SH) will become constant.
In heating, to maximize the capacity of indoor unit heat exchanger (condenser), operate the
electronic expansion valve under PI control so that the evaporator outlet superheated degree
(Condenser outlet subcooled degree) will become constant.
Furthermore, the default value of the optimal evaporator outlet superheated degree (condenser
outlet subcooled degree) is 5 deg. However, this default value varies with the operating
performance.
6.7 Hot Start Control (In Heating Operation Only)
At startup with thermostat ON or after the completion of defrosting in heating operation, the
indoor unit fan is controlled to prevent cold air from blasting out and ensure startup capacity.
[Detail of operation]
When either the
start
condition 1
or the
start
condition 2
is established, the operations shown
below will be conducted.
Cooling SH=TH
2
-TH
1
SH
: Evaporator outlet superheated degree
(Heating SC=TC-TH
1
)
TH
1
: Temperature (°C) detected with the liquid thermistor
TH
2
: Temperature (°C) detected with the gas thermistor
SC
: Condenser outlet subcooled degree
TC
: High pressure equivalent saturated temperature
TH
2
: Temperature (°C) detected with the gas thermistor
TC
: High pressure equivalent saturated temperature
Defrost ending or oil return ending
or Thermostat ON
The fan is not OFF before initiating the hot start: LL
The fan is OFF before initiating the hot start: OFF
Hot start control
Hot start in progress
Normal control
Normal control
H/L remote
control setting
LL
OFF
Remote control
setting
Po (Horizontal)
Fa
n
Louv
er
Hot start ending conditions
·
lapse of 3 minutes
·
[TH2]>34°C
·
"Tc">52°C
OR
Содержание VRVIII-S
Страница 1: ...SiENBE34 703 Basic Training Manual R 410A Heat Pump 50Hz Service Manual...
Страница 11: ...Introduction SiENBE34 703 x...
Страница 16: ...SiENBE34 703 Specifications 5 Part 2 Specifications 1 Specifications 6 1 1 Outdoor Units 6 1 2 Indoor Units 8...
Страница 113: ...Field Setting SiENBE34 703 102 Test Operation...
Страница 207: ...Troubleshooting by Indication on the Unified ON OFF Control SiENBE34 703 196 Troubleshooting...
Страница 215: ...Wiring Diagrams SiENBE34 703 204 Appendix 2 3 Indoor Unit FXCQ20 25 32 63M8...
Страница 216: ...SiENBE34 703 Wiring Diagrams Appendix 205 FXCQ40 50 80 125M8V3...
Страница 217: ...Wiring Diagrams SiENBE34 703 206 Appendix FXFQ25 32 40 50 63 80 100 125P7VE...
Страница 218: ...SiENBE34 703 Wiring Diagrams Appendix 207 FXZQ20 25 32 40 50M8V1...
Страница 221: ...Wiring Diagrams SiENBE34 703 210 Appendix FXDQ20 25M8V3...
Страница 222: ...SiENBE34 703 Wiring Diagrams Appendix 211 FXSQ20 25 32 40 50 63 80 100 125M8V3...
Страница 232: ...SiENBE34 703 Option List Appendix 221...
Страница 235: ...Example of Connection SiENBE34 703 224 Appendix...
Страница 241: ...Method of Replacing the Inverter s Power Transistors Modules SiBE34 703 230 Appendix...
Страница 261: ...RXYSQ4 5 6 P7Y1B SiENBE34 703 250 Removal Procedure...