Troubleshooting by Indication on the remote control
SiENBE34-703
132
Troubleshooting
3.8
“
AJ
”
Indoor Unit: Malfunction of Capacity Determination
Device
remote control
display
AJ
Applicable
Models
All indoor unit models
Method of
Malfunction
Detection
Capacity is determined according to resistance of the capacity setting adapter and the memory
inside the IC memory on the indoor unit PC board, and whether the value is normal or abnormal
is determined.
Malfunction
Decision
Conditions
Operation and:
1. When the capacity code is not contained in the PC board’s memory, and the capacity setting
adapter is not connected.
2. When a capacity that doesn’t exist for that unit is set.
Supposed
Causes
!
You have forgotten to install the capacity setting adapter.
!
Defect of indoor unit PC board
Troubleshooting
(V2783)
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Caution
Install a capacity setting adaptor.
Replace the indoor unit PC board.
Replace the indoor unit PC board.
The indoor unit is a
model that requires
installation of a capacity
setting adaptor when
replacing the PC board.
The indoor unit PC
board was
replaced with a
replacement PC
board.
NO
NO
YES
YES
Содержание VRVIII-S
Страница 1: ...SiENBE34 703 Basic Training Manual R 410A Heat Pump 50Hz Service Manual...
Страница 11: ...Introduction SiENBE34 703 x...
Страница 16: ...SiENBE34 703 Specifications 5 Part 2 Specifications 1 Specifications 6 1 1 Outdoor Units 6 1 2 Indoor Units 8...
Страница 113: ...Field Setting SiENBE34 703 102 Test Operation...
Страница 207: ...Troubleshooting by Indication on the Unified ON OFF Control SiENBE34 703 196 Troubleshooting...
Страница 215: ...Wiring Diagrams SiENBE34 703 204 Appendix 2 3 Indoor Unit FXCQ20 25 32 63M8...
Страница 216: ...SiENBE34 703 Wiring Diagrams Appendix 205 FXCQ40 50 80 125M8V3...
Страница 217: ...Wiring Diagrams SiENBE34 703 206 Appendix FXFQ25 32 40 50 63 80 100 125P7VE...
Страница 218: ...SiENBE34 703 Wiring Diagrams Appendix 207 FXZQ20 25 32 40 50M8V1...
Страница 221: ...Wiring Diagrams SiENBE34 703 210 Appendix FXDQ20 25M8V3...
Страница 222: ...SiENBE34 703 Wiring Diagrams Appendix 211 FXSQ20 25 32 40 50 63 80 100 125M8V3...
Страница 232: ...SiENBE34 703 Option List Appendix 221...
Страница 235: ...Example of Connection SiENBE34 703 224 Appendix...
Страница 241: ...Method of Replacing the Inverter s Power Transistors Modules SiBE34 703 230 Appendix...
Страница 261: ...RXYSQ4 5 6 P7Y1B SiENBE34 703 250 Removal Procedure...