Method of Troubleshooting
Si30-408
76
Troubleshooting
3.2.1 Thermistor
1. Symptoms with Thermistor Resistance Deviation
In Cooling with
Superheat
Degree Control
Code of Thermistors Detecting Various Temperatures
Units using R22, R407C
Units using R410A
Tl (indoor liquid pipe temperature)
Th2
R2T
Tg (indoor gas pipe temperature)
Th3
R3T
•
Indoor unit liquid pipe thermistor
· When the resistance deviates to smaller value.
(Higher temperature detected)
Superheat degree (SH) = Tg-Tl
Tg-Tl decreases.
Indoor electronic EV closes.
· When the resistance deviates to larger value.
(Lower temperature detected)
Superheated degree (SH) = Tg-Tl
Tg-Tl increases.
Indoor electronic EV opens.
Superheat operation, cooling
capacity lowering (Freeze-up
protection cannot be detected.)
Wet operation (Freeze-up
protection can be applied
easily.)
•
Indoor gas pipe thermistor
· When the resistance deviates to smaller value.
(Higher temperature detected)
Superheated degree (SH) = Tg-Tl
Tg-Tl increases.
Indoor electronic EV opens.
Wet operation
· When the resistance deviates to larger value.
(Lower temperature detected)
Superheat degree (SH) = Tg-Tl
Tg-Tl decreases.
Indoor electronic EV closes.
Superheat operation,
cooling capacity lowering
Содержание VRV
Страница 1: ...Si30 408 Basic Training Manual...
Страница 4: ...Si30 408 ii General Contents...
Страница 24: ...REFNET Piping Si30 408 20 Introduction...
Страница 159: ...Si30 408 Collection and Playback of Data on Checker Service Checker Type3 Application Edition 155 Pane fixing...
Страница 166: ...Collection and Playback of Data on Checker Si30 408 162 Service Checker Type3 Application Edition...
Страница 171: ...Si30 408 Collection and Playback of Data on Checker Service Checker Type3 Application Edition 167...
Страница 172: ...Collection and Playback of Data on Checker Si30 408 168 Service Checker Type3 Application Edition 4 4 Organizing Graph...
Страница 179: ...Si30 408 Collection and Playback of Data on Checker Service Checker Type3 Application Edition 175...
Страница 180: ...Collection and Playback of Data on Checker Si30 408 176 Service Checker Type3 Application Edition...
Страница 185: ...Si30 408 Points of Analysis Service Checker Type3 Application Edition 181 5 4 Example of Checker Connection...
Страница 194: ...Points of Analysis Si30 408 190 Service Checker Type3 Application Edition...
Страница 255: ...Printed in Japan 12 2004 AK...