Adaptors for Connection of Air Conditioners
Si30-408
212
Appendix
Wiring to External
Controller
(e.g. Centralized
Control Monitor)
1. Input for distant control (operation)
Depending on whether the INPUT selector switch is set to the “Voltage” or “No-voltage”,
connect wires according to the procedure shown below.
2. Setting of CONTROL MODE selector switch (RS1)
Use the CONTROL MODE selector switch (RS1) on the adapter PC board to make selection
and setting of control mode through input A or B.
���
���
���
���
To use the system only for display function only in individual display mode:
���
���
���
���
To operate the system using normal input to the input A
Position
Function
0
Individual display (with input disregarded)
12 to 24 VDC
G
BC
B2
B1
BC
B2
B1
Input B
Input A
Input B
Input A
Adapter PC board
KRP2A61, 62, 51, 52
Adapter PC board
KRP2A61, 62, 51, 52
Set the INPUT selector switch
(SS1) to "VOLT".
(Factory set: "VOLT")
For input in "VOLT"
mode:
Connect the control input on
the common side.
(No polarities)
Use 12 to 24 VDC for the external power supply.
An approx. 10-mA input current is required by a
single contact.
Pay attention to the capacity of the power supply.
Use micro-current contacts. (Use contacts
of minimum applicable load of 12 VDC and
1mA or less.)
Set the INPUT selector
switch (SS1) to "NONE
VOLT".
For input in "NONE
VOLT" input
Use micro-current contacts. (Use
contacts of minimum applicable load
of 12 VDC and 1mA or less.)
(Wiring specifications)
Types of wires...Sheathed wire
Size of wire ...0.18 to 1.25 mm
2
Total length of wiring...150 m at maximum
<Caution>
In order to prevent malfunctions, keep this
wiring away from the power lines.
Position
Function
Contents with input A tuned ON
Contents with input A
turned OFF
1
Remote controller
inhibited
Operation (The remote controller is
inhibited at all times.)
Stop + Remote controller
inhibited
2
Centralized priority
Ope Remote controller permitted
3
Remote controller
stop permitted
Ope Only remote controller stop
permitted
(Operation from remote controller is
impossible.)
4
Remote controller
permitted / stop
Only remote controller permitted
(Operation from remote is impossible.)
Содержание VRV
Страница 1: ...Si30 408 Basic Training Manual...
Страница 4: ...Si30 408 ii General Contents...
Страница 24: ...REFNET Piping Si30 408 20 Introduction...
Страница 159: ...Si30 408 Collection and Playback of Data on Checker Service Checker Type3 Application Edition 155 Pane fixing...
Страница 166: ...Collection and Playback of Data on Checker Si30 408 162 Service Checker Type3 Application Edition...
Страница 171: ...Si30 408 Collection and Playback of Data on Checker Service Checker Type3 Application Edition 167...
Страница 172: ...Collection and Playback of Data on Checker Si30 408 168 Service Checker Type3 Application Edition 4 4 Organizing Graph...
Страница 179: ...Si30 408 Collection and Playback of Data on Checker Service Checker Type3 Application Edition 175...
Страница 180: ...Collection and Playback of Data on Checker Si30 408 176 Service Checker Type3 Application Edition...
Страница 185: ...Si30 408 Points of Analysis Service Checker Type3 Application Edition 181 5 4 Example of Checker Connection...
Страница 194: ...Points of Analysis Si30 408 190 Service Checker Type3 Application Edition...
Страница 255: ...Printed in Japan 12 2004 AK...