Field Setting on Outdoor Unit
Si30-408
58
Field Settings from Remote Controller
2.1.2
Setting Mode 2
↑
The numbers in the "No." column show the number of times to press the
.
No.
Setting item
Set Content
0
Emergency operation
(INV compressor
operation inhibit)
In defect of the INV compressor, operation is made only using the
STD compressor.
The operation is for temporary use until replacing of the
compressor. The comfort declines excessively. Therefore,
replace the compressor without delay.
(However, for RX(Y)(Q)5M, this setting is not available.)
1
Address in batch cooling/
heating
Sets the address in unified cooling/heating operation.
2
Low noise · Demand
address
Address in low noise and demand operation
5
Indoor unit forcedly fan H
The indoor fan in the stop condition is forcedly to operate. (H tap)
6
Indoor unit forcedly
operation
Indoor unit is forcedly to operate.
8
Te setting
Target evaporation temperature in cooling
9
Tc setting
Target condensing temperature in heating
10
Setting of defrost
selection
Changes temperature conditions for defrosting. Setting is
available to defrost quick or slow.
11
Starting in sequence
setting
Sets when starting in sequence.
(ON is factory setting.)
12
External low noise ·
Demand setting
Receives the low noise or the demand signal from outside.
13
AirNet address
Sets the AirNet address.
18
High static pressure
setting
Set when mounting air discharge duct and operating in high static
pressure
19
Emergency operation
(STD compressor
operation inhibit)
In defect of the STD compressor, operation is made only using
the INV compressor. The operation is for temporary use until
replacing of the compressor. The comfort declines excessively.
Therefore, replace the compressor without delay.
(However, for RX(Y)(Q)5M, this setting is not available.)
20
Setting of refrigerant re-
filling operation
Makes refrigerant re-filling operation.
21
Setting of refrigerant
recovery vacuuming
mode
Sets to refrigerant collection mode.
22
Setting of nighttime low
noise level
Enables to set the simplified operation of automatic night low
noise.
Time is subject to "starting set" and "ending set".
25
Setting of external low
noise level
Sets the low noise level when the low noise signal is input from
outside.
26
Starting time of nighttime
low noise operation
Sets the starting time of the nighttime low noise.
("Setting of the nighttime low noise" is required.)
27
Closing time of the night
low noise operation
Sets the closing time of the nighttime low noise.
("Setting of the nighttime low noise" is required.)
28
Setting of power
transistor checks mode
Uses for the troubleshooting of the DC compressor. The inverter
waveform is output without wiring to the compressor. Therefore,
the mode is convenient to identify if the defect part is the
compressor or the PC board.
29
Setting of capacity
priority
When the low noise operation or the nighttime low noise
operation was performed, this setting enables to release the low
noise operation automatically if the capacity is required.
30
Setting of demand 1 level
Change the target value of power consumption when the demand
1 is input.
32
Setting of constant
demand
The demand 1 is always performed by making this setting without
input from outside.
(It is effective against such a problem that the capacity in the
breaker is small and the breaker trips when the load is growing.)
38
Emergency operation
(Master unit with multi-
outdoor-unit system is
inhibited to operate.)
Prohibits operating the corresponding outdoor unit tentatively for
the parts of outdoor-multi malfunction. The comfort declines
excessively. Therefore, replace the parts without delay.
39
Emergency operation
(Slave unit 1 with multi-
outdoor-unit system is
inhibited to operate.)
40
Emergency operation
(Slave unit 2 with multi-
outdoor-unit system is
inhibited to operate.)
Press and hold the MODE button
(BS1) for a period of five seconds or
more to put the system into "Setting
mode 2".
<Selection of Setting Items>
Press the SET button (BS2) and set
the LED display to setting items
shown on the right.
Press the RETURN button (BS3) to
finalize the setting items. (The current
setting conditions are displayed while
blinking.)
<Selection of setting conditions>
Press the SET button (BS2) and set
the LED display to conditions to be
set.
Press the RETURN button (BS3) to
finalize the check items.
Press the RETURN button (BS3) and
put the system into the initial state of
"Setting mode 2".
* If you become confused about the
setting halfway through it, press the
MODE button (BS1) . Thus, the
system will return to Setting mode 1.
SET button (BS2)
Содержание VRV
Страница 1: ...Si30 408 Basic Training Manual...
Страница 4: ...Si30 408 ii General Contents...
Страница 24: ...REFNET Piping Si30 408 20 Introduction...
Страница 159: ...Si30 408 Collection and Playback of Data on Checker Service Checker Type3 Application Edition 155 Pane fixing...
Страница 166: ...Collection and Playback of Data on Checker Si30 408 162 Service Checker Type3 Application Edition...
Страница 171: ...Si30 408 Collection and Playback of Data on Checker Service Checker Type3 Application Edition 167...
Страница 172: ...Collection and Playback of Data on Checker Si30 408 168 Service Checker Type3 Application Edition 4 4 Organizing Graph...
Страница 179: ...Si30 408 Collection and Playback of Data on Checker Service Checker Type3 Application Edition 175...
Страница 180: ...Collection and Playback of Data on Checker Si30 408 176 Service Checker Type3 Application Edition...
Страница 185: ...Si30 408 Points of Analysis Service Checker Type3 Application Edition 181 5 4 Example of Checker Connection...
Страница 194: ...Points of Analysis Si30 408 190 Service Checker Type3 Application Edition...
Страница 255: ...Printed in Japan 12 2004 AK...