Field Setting on Outdoor Unit
Si30-408
66
Field Settings from Remote Controller
2.2.4 Working in the Check Operation
Provide the test operation mode and study the following items in order to prevent the
malfunction in the field installation: the check for erroneous wiring, the check the stop valve,
judging the piping length, judging the refrigerant over-charging, the check for missing thermistor
(or reverse connection) in discharging pipe and the minimum opening degree at start of the
motorized valve.
Stopping
Pressure equalizing
Cooling start control
Cooling stability waiting
Various judgment functions
Pump down residual operation
Standby for restarting
Completion
7787777
7977778
7977787
7977788
7977888
7978777
7977877
↓
7977878
↓
7977887
Step1
Press and hold BS4
for a period of 5 seconds or more
Step2
10 seconds to 10 minutes
Step3
20 seconds to 2 minutes
Step4~6
10 minutes
· Stop valve close check
· Erroneous wiring check
· Refrigerant over charge check
· Piping length check
3 minutes
Step7
Step8
Less than 5 minutes
5 minutes
LED display (H1P~H7P
8
ON
9
BLINKING
7
OFF)
Check operation function
Содержание VRV
Страница 1: ...Si30 408 Basic Training Manual...
Страница 4: ...Si30 408 ii General Contents...
Страница 24: ...REFNET Piping Si30 408 20 Introduction...
Страница 159: ...Si30 408 Collection and Playback of Data on Checker Service Checker Type3 Application Edition 155 Pane fixing...
Страница 166: ...Collection and Playback of Data on Checker Si30 408 162 Service Checker Type3 Application Edition...
Страница 171: ...Si30 408 Collection and Playback of Data on Checker Service Checker Type3 Application Edition 167...
Страница 172: ...Collection and Playback of Data on Checker Si30 408 168 Service Checker Type3 Application Edition 4 4 Organizing Graph...
Страница 179: ...Si30 408 Collection and Playback of Data on Checker Service Checker Type3 Application Edition 175...
Страница 180: ...Collection and Playback of Data on Checker Si30 408 176 Service Checker Type3 Application Edition...
Страница 185: ...Si30 408 Points of Analysis Service Checker Type3 Application Edition 181 5 4 Example of Checker Connection...
Страница 194: ...Points of Analysis Si30 408 190 Service Checker Type3 Application Edition...
Страница 255: ...Printed in Japan 12 2004 AK...