• NOTE TO SERVICE PERSONNEL
WARNING
RISK OF ELECTRIC SHOCKS OR A FIRE.
•
When checking the electric components (such as the
inside of the control box, fan motor, drain pump, etc.),
make sure to shut off all power supply for the air condi-
tioner.
•
When cleaning the heat exchanger, make sure to remove
the electronic components above.
(If they get cleaning agent, there is a risk that the compo-
nents will burn out because of insulation degradation).
CAUTION! DANGER OF ELECTRIC SHOCKS
•
Shut off power supply before work.
•
Never open the control box lid for 10 minutes after shutting
off the power supply because there is residual voltage.
•
After opening the control box lid, measure the residual
voltage between the points shown
Fig. 1
on the Printed
Circuit Board by the tester without touching the live part
and confirm that the residual voltage is DC50V or below.
RISK OF ELECTRIC SHOCKS
When removing the metal part shown as below, make sure
to install by screws with spring washer as the way they
were. (to secure earthing route)
•
After power failure, operation will restart automatically.
X27A
A1P
0
+
C+
–
C–
C+
C–
Measuring points for
residual voltage
Printed Circuit Board
Control box
+
–
Measuring points for
residual voltage
Printed Circuit
Board
Control box
(80·125 type only)
Fig.1
0
X10A
X9A
X3A
X8A
C+
C–
screw with spring washer
Correct
Wrong
Metal part
2. NAMES AND FUNCTIONS OF PARTS
1
Air outlet
2
Horizontal blade (inside air outlet)
3
Suction panel
4
Air filter (inside suction panel)
(Refer to “
3. MAINTENANCE
” on page 4)
5
Air outlet identification mark (
,
)
Use this mark as a reference for setting the airflow
direction. (only for BRC1E52)
6
Remote controller (optional accessory)
The remote controller may not be needed depending
on the system configuration.
7
Decoration panel (optional accessory)
8
Drain device (built-in)
It drains moisture in the room removed during the
cooling operation.
9
Refrigerant piping
10
Drain piping
11
Transmission wiring
Earth wiring (Note)
(Note) It is a wiring to let electricity flow from the
indoor unit to the earth for prevention of electric
shocks or a fire in case of emergency.
Power supply wiring
5
3
10
11
7
4
8
9
1
2
6