3.  PREPARATIONS BEFORE INSTALLATION

Install suspension bolts and hanging brackets as illustrated in the diagram below.

• 

Use a suspension bolt size of 3/8 in.(M8) to 7/16 in.(M10).

• 

Use mold-in inserts and embedded foundation bolts for new installations or hole-in anchor bolts or 

similar hardware for existing installations, taking care to install in a manner that can withstand the unit’s 

weight.

Unit: in. (mm)

Branch Selector unit

A

BS4Q54TVJ

16-5/16 (415)

BS6Q54TVJ

24-5/8 (625)

BS8Q54TVJ

BS10Q54TVJ

34-1/16 (865)

BS12Q54TVJ

A

12-1/8 (308)

<Suspension bolt spacing>

• 

Use the hanging brackets to support the connection  
pipes on both the front and back of the unit within  
40 in. (1 m) of the unit’s side. 

Placing an excessive amount of weight on the 

Branch Selector unit's hanging brackets may cause 
the unit to fall, resulting in bodily injury.

Slab

Anchor bolt

Long nut or 

turnbuckle

Suspension bolt

Within 40 in. (1 m) 

Unit

Connection 
pipe

Note: All the above parts must be supplied in the field

 

<Example installation>

4.  BRANCH SELECTOR UNIT INSTALLATION

Use only accessories and parts that conform to the designated specifications when installing 

the unit.
1.  Position the Branch Selector unit and secure it temporarily in 

place. 
Attach the hanging brackets to the suspension bolts as per the 

instructions in the figure to the right.

 

Be sure to affix nuts (3/8 in.(M8) or 7/16 in.(M10), 3 pieces in 

 

4 locations) and washers (for 3/8 in.(M8), outside diameter of 
15/16 in. (24 mm) to 1-1/8 in. (28 mm) or for 7/16 in.(M10), 
outside diameter of 1-3/16 in. (30 mm) to 1-5/16 in. (34 mm):  

2 pieces in 4 locations) (to be supplied in the field) from both 

the top and bottom of the hanging brackets on both sides of the 
unit to secure it in place.

2.  Adjust the height of the unit as desired.
3.  Using a level, verify that the unit has been installed in a level 

orientation.

Nut (double nut) 
(Field supply)

Suspension bolt 
(Field supply)

3/8-9/16 in. 

(10 - 15 mm)

Hanging bracket

Washer 
(Field supply)

Nut 
(Field supply)

Branch 
Selector 
unit

WARNING

• 

Install the Branch Selector unit in a level orientation.

• 

Attach nuts on both the top and bottom of the hanging brackets.  
Overtightening the lower nut without the upper nut in place may cause the hanging bracket and top 
plate to deform, causing the unit to produce abnormal noise.

5

3P405106-9 English

01_EN_3P405106-9.indb   5

3/27/2015   1:53:09 PM

Содержание VRV IV Series

Страница 1: ...HIS MANUAL IN A HANDY PLACE FOR FUTURE REFERENCE LIRE SOIGNEUSEMENT CES INSTRUCTIONS AVANT L INSTALLATION CONSERVER CE MANUEL A PORTEE DE MAIN POUR REFERENCE ULTERIEURE LEA CUIDADOSAMENTE ESTAS INSTRU...

Страница 2: ...onnel must carry out the installation work Installation must be done in accordance with this installation manual Improper installation could result in water leakage electric shock or fire When install...

Страница 3: ...stallation only Outdoor units can be installed either outdoors or indoors This unit is for indoor use Do not install the air conditioner or heat pump in the fol lowing locations a Where a mineral oil...

Страница 4: ...NSTALLATION SITE 4 3 PREPARATIONS BEFORE INSTALLATION 5 4 BRANCH SELECTOR UNIT INSTALLATION 5 5 REFRIGERANT PIPING WORK 6 6 ELECTRIC WIRING WORK 11 7 INITIAL SETTING 17 8 ADDING AN ADDITIONAL CHARGE O...

Страница 5: ...Insulation tube 2 Vinyl tube 3 Quantity BS4Q54TVJ 23 pcs 4 pcs 4 pcs 1 pc BS6Q54TVJ 32 pcs 6 pcs 6 pcs BS8Q54TVJ 40 pcs 8 pcs 8 pcs BS10Q54TVJ 49 pcs 10 pcs 10 pcs BS12Q54TVJ 57 pcs 12 pcs 12 pcs Sha...

Страница 6: ...42 48 54 72 96 Example selection In case of the Branch Selector unit with connect a FXFQ12P and a FXMQ18P Total capacity 12 18 30 1 4 Checklist Exercise particular care concerning the following items...

Страница 7: ...0 or more 20 500 or more 1 18 450 2 Control box 4 100 or more 3 4 100 or more Control box and motorized valve coil Maintenance space Indoor unit side pipe 1 Unit in mm Fig 1 1 Leave enough space to co...

Страница 8: ...rts that conform to the designated specifications when installing the unit 1 Position the Branch Selector unit and secure it temporarily in place Attach the hanging brackets to the suspension bolts as...

Страница 9: ...t the size of piping between the outdoor unit refrigerant branch kit and the Branch Selector unit and between the Branch Selector unit and indoor units refrigerant branch kits based on example con nec...

Страница 10: ...6 4 24 30 36 42 48 54 f5 8 f15 9 f3 8 f9 5 72 f3 4 f19 1 96 f7 8 f22 2 Table 5 lists Branch Selector unit connection pipe size Table 5 Branch Selector unit connection pipe size Outdoor unit side 1 Bra...

Страница 11: ...a enough to feel a slight breeze on your cheek 2 Do not use flux when brazing the refrigerant pipe Use phosphor copper B Cu93P 710 795 ISO 3677 which does not require flux as the filler metal for braz...

Страница 12: ...ng joint may be required field supply if the local pipe size does not suit on the pipe size of the Branch Selector unit Table 5 If there are branch ports left unused not connected to an indoor unit If...

Страница 13: ...piping and gas piping so use insulation that can withstand more than 250 F 120 C When reinforcing the insulation material in accordance with the installation environment also reinforce the insulation...

Страница 14: ...wire installation work Follow the WIRING DIAGRAM attached to the unit body to wire the outdoor unit and indoor units Properly connect wire of the specified wire type and copper thickness Also use the...

Страница 15: ...rrent Use copper conductors only Use insulated wire for the power cord Select the power supply cable type and size in accordance with relevant local and national regulations Use vinyl cord with sheath...

Страница 16: ...d unit Note 1 Indoor unit A Indoor unit B 1 Indoor unit B 2 Note 3 Indoor unit C Note 2 Indoor unit Indoor unit TO IN D UNIT Never connect to power supply wiring In case joining branch pipes Note 2 IN...

Страница 17: ...ed screwdriver to tighten the terminal screws Use of a screwdriver that is too small could damage the screw head and prevent proper tightening Overtightening the terminal screws could damage the screw...

Страница 18: ...the included clamps 1 to securely hold the wires For more information about how much insulation to strip off transmission wir ing refer to the following figure Transmission wiring 3 8 in 10 mm 2 in 50...

Страница 19: ...e wire use the included clamp 1 so as not to apply tensile force to the wire connec tion and then securely fasten the wire Also after the wiring is completed organize the wiring so that the control bo...

Страница 20: ...D I J K L Piping branch port number Terminal No to which to connect transmission wiring DIP switch Setting 1 Setting for branch ports to which no indoor unit is connected Setting Setting for branch po...

Страница 21: ...N 1 Verify that the control box cover is closed 2 Refer to the installation manual included with the outdoor unit and conduct a check and a test run after all the work on the Branch Selector unit and...

Страница 22: ...5151 San Felipe Suite 500 Houston TX 77056 3P405106 9 EM14A003A 1506 HT 00_CV_3P405106 9 indd 2 4 20 2015 3 08 14 PM...

Отзывы: