1-3 Combination
• This Branch Selector unit is only for systems for models REYQ-T and PC series.
It cannot be connected to systems for models REYQ-M, P, PA and PB series.
•
For series of applicable indoor units, refer to the catalog or other literature.
• Select the Branch Selector unit to fit the total capacity (sum of unit’s capacity) of the indoor units
to be connected downstream, refer to the Table 1. About indoor unit’s capacity, refer to the Table 2.
Table 1
Model
Total capacity of all downstream indoor units
BS4Q54TVJ
A ≤ 144
(*)
BS6Q54TVJ
A ≤ 216
(*)
BS8Q54TVJ
BS10Q54TVJ
BS12Q54TVJ
A ≤ 290
(*)
*
The total capacity and number of indoor units connectable to each branch connector are up to
54 and 5, respectively. When the total capacity of indoor units to be connected downstream is
larger than 54 (MAX. 96), use a junction pipe kit (KHRP26A250T, sold separately) to join two
connections downstream from the Branch Selector unit.
Table 2
Capacity expressed as indoor unit’s model No.
07
09
12
18
24
30
36
42
48
54
72
96
Indoor unit’s capacity (for use in computation)
7.5
9.5
12
18
24
30
36
42
48
54
72
96
<Example selection>
In case of the Branch Selector unit with connect a FXFQ
12P and a FXMQ18P.
Total capacity =
12+18 = 30
1-4 Checklist
Exercise particular care concerning the following items during installation work and check again
after installation is complete:
Post-installation checklist
Checklist
If defective
Check here.
Has the Branch Selector unit been installed securely?
The unit may fall, vibrate, or operate noisily.
Did you conduct a gas leak inspection?
The unit may fail to heat or cool as designed.
Was the unit fully insulated? (Refrigerant pipes)
The unit may leak water.
Is the supply voltage the same as the voltage indicated on the
label?
The unit may fail to operate or burn up.
Are there any wiring mistakes or erroneous wiring or erroneous
pipe connections?
The unit may fail to operate, burn up, or produce
abnormal noise.
Has the unit been grounded?
The unit may pose a hazard in the event of a
short-circuit.
Is the thickness of the electrical wiring the same as described in
the specifications?
The unit may fail to operate or burn up.
Delivery checklist
Checklist
Check here.
Has a cover been installed on the control box?
Did you give the customer the installation manual?