1-3 Combination

• This Branch Selector unit is only for systems for models REYQ-T and PC series.

 

It cannot be connected to systems for models REYQ-M, P, PA and PB series.

• 

For series of applicable indoor units, refer to the catalog or other literature.

• Select the Branch Selector unit to fit the total capacity (sum of unit’s capacity) of the indoor units 

to be connected downstream, refer to the Table 1. About indoor unit’s capacity, refer to the Table 2.

Table 1 

Model

Total capacity of all downstream indoor units

BS4Q54TVJ

 

A ≤ 144 

(*)

BS6Q54TVJ

 

A ≤ 216 

(*)

BS8Q54TVJ 
BS10Q54TVJ 
BS12Q54TVJ

 

A ≤ 290 

(*)

The total capacity and number of indoor units connectable to each branch connector are up to 
54 and 5, respectively. When the total capacity of indoor units to be connected downstream is 

larger than 54 (MAX. 96), use a junction pipe kit (KHRP26A250T, sold separately) to join two 

connections downstream from the Branch Selector unit.

Table 2 

Capacity expressed as indoor unit’s model No.

07

09

12

18

24

30

36

42

48

54

72

96

Indoor unit’s capacity (for use in computation)

7.5

9.5

12

18

24

30

36

42

48

54

72

96

<Example selection>

 

In case of the Branch Selector unit with connect a FXFQ

12P and a FXMQ18P. 

  Total capacity = 

12+18 = 30

1-4 Checklist

Exercise particular care concerning the following items during installation work and check again 

after installation is complete:

Post-installation checklist

Checklist

If defective

Check here.

Has the Branch Selector unit been installed securely?

The unit may fall, vibrate, or operate noisily. 

Did you conduct a gas leak inspection?

The unit may fail to heat or cool as designed.

Was the unit fully insulated? (Refrigerant pipes)

The unit may leak water.

Is the supply voltage the same as the voltage indicated on the 
label?

The unit may fail to operate or burn up.

Are there any wiring mistakes or erroneous wiring or erroneous 
pipe connections?

The unit may fail to operate, burn up, or produce 
abnormal noise.

Has the unit been grounded?

The unit may pose a hazard in the event of a 
short-circuit.

Is the thickness of the electrical wiring the same as described in 

the specifications?

The unit may fail to operate or burn up.

Delivery checklist

Checklist

Check here.

Has a cover been installed on the control box?

Did you give the customer the installation manual?

3

3P405106-9 English

01_EN_3P405106-9.indb   3

3/27/2015   1:53:08 PM

Содержание VRV IV Series

Страница 1: ...HIS MANUAL IN A HANDY PLACE FOR FUTURE REFERENCE LIRE SOIGNEUSEMENT CES INSTRUCTIONS AVANT L INSTALLATION CONSERVER CE MANUEL A PORTEE DE MAIN POUR REFERENCE ULTERIEURE LEA CUIDADOSAMENTE ESTAS INSTRU...

Страница 2: ...onnel must carry out the installation work Installation must be done in accordance with this installation manual Improper installation could result in water leakage electric shock or fire When install...

Страница 3: ...stallation only Outdoor units can be installed either outdoors or indoors This unit is for indoor use Do not install the air conditioner or heat pump in the fol lowing locations a Where a mineral oil...

Страница 4: ...NSTALLATION SITE 4 3 PREPARATIONS BEFORE INSTALLATION 5 4 BRANCH SELECTOR UNIT INSTALLATION 5 5 REFRIGERANT PIPING WORK 6 6 ELECTRIC WIRING WORK 11 7 INITIAL SETTING 17 8 ADDING AN ADDITIONAL CHARGE O...

Страница 5: ...Insulation tube 2 Vinyl tube 3 Quantity BS4Q54TVJ 23 pcs 4 pcs 4 pcs 1 pc BS6Q54TVJ 32 pcs 6 pcs 6 pcs BS8Q54TVJ 40 pcs 8 pcs 8 pcs BS10Q54TVJ 49 pcs 10 pcs 10 pcs BS12Q54TVJ 57 pcs 12 pcs 12 pcs Sha...

Страница 6: ...42 48 54 72 96 Example selection In case of the Branch Selector unit with connect a FXFQ12P and a FXMQ18P Total capacity 12 18 30 1 4 Checklist Exercise particular care concerning the following items...

Страница 7: ...0 or more 20 500 or more 1 18 450 2 Control box 4 100 or more 3 4 100 or more Control box and motorized valve coil Maintenance space Indoor unit side pipe 1 Unit in mm Fig 1 1 Leave enough space to co...

Страница 8: ...rts that conform to the designated specifications when installing the unit 1 Position the Branch Selector unit and secure it temporarily in place Attach the hanging brackets to the suspension bolts as...

Страница 9: ...t the size of piping between the outdoor unit refrigerant branch kit and the Branch Selector unit and between the Branch Selector unit and indoor units refrigerant branch kits based on example con nec...

Страница 10: ...6 4 24 30 36 42 48 54 f5 8 f15 9 f3 8 f9 5 72 f3 4 f19 1 96 f7 8 f22 2 Table 5 lists Branch Selector unit connection pipe size Table 5 Branch Selector unit connection pipe size Outdoor unit side 1 Bra...

Страница 11: ...a enough to feel a slight breeze on your cheek 2 Do not use flux when brazing the refrigerant pipe Use phosphor copper B Cu93P 710 795 ISO 3677 which does not require flux as the filler metal for braz...

Страница 12: ...ng joint may be required field supply if the local pipe size does not suit on the pipe size of the Branch Selector unit Table 5 If there are branch ports left unused not connected to an indoor unit If...

Страница 13: ...piping and gas piping so use insulation that can withstand more than 250 F 120 C When reinforcing the insulation material in accordance with the installation environment also reinforce the insulation...

Страница 14: ...wire installation work Follow the WIRING DIAGRAM attached to the unit body to wire the outdoor unit and indoor units Properly connect wire of the specified wire type and copper thickness Also use the...

Страница 15: ...rrent Use copper conductors only Use insulated wire for the power cord Select the power supply cable type and size in accordance with relevant local and national regulations Use vinyl cord with sheath...

Страница 16: ...d unit Note 1 Indoor unit A Indoor unit B 1 Indoor unit B 2 Note 3 Indoor unit C Note 2 Indoor unit Indoor unit TO IN D UNIT Never connect to power supply wiring In case joining branch pipes Note 2 IN...

Страница 17: ...ed screwdriver to tighten the terminal screws Use of a screwdriver that is too small could damage the screw head and prevent proper tightening Overtightening the terminal screws could damage the screw...

Страница 18: ...the included clamps 1 to securely hold the wires For more information about how much insulation to strip off transmission wir ing refer to the following figure Transmission wiring 3 8 in 10 mm 2 in 50...

Страница 19: ...e wire use the included clamp 1 so as not to apply tensile force to the wire connec tion and then securely fasten the wire Also after the wiring is completed organize the wiring so that the control bo...

Страница 20: ...D I J K L Piping branch port number Terminal No to which to connect transmission wiring DIP switch Setting 1 Setting for branch ports to which no indoor unit is connected Setting Setting for branch po...

Страница 21: ...N 1 Verify that the control box cover is closed 2 Refer to the installation manual included with the outdoor unit and conduct a check and a test run after all the work on the Branch Selector unit and...

Страница 22: ...5151 San Felipe Suite 500 Houston TX 77056 3P405106 9 EM14A003A 1506 HT 00_CV_3P405106 9 indd 2 4 20 2015 3 08 14 PM...

Отзывы: