![Daikin VRV IV Series Скачать руководство пользователя страница 14](http://html1.mh-extra.com/html/daikin/vrv-iv-series/vrv-iv-series_installation-manual_2459208014.webp)
Product
2) Attach the insulation tube.
(accessory(2))
(2)-1 Liquid pipe
(2)-2 Gas pipes
1) Attach the
insulation material.
(Field supply)
3) Use the clamps
(accessory(1)) to
hold both ends.
Insulation tube installation instructions
(indoor unit side) (gas and liquid pipes)
Adhere.
Product
2) Attach the insulation tube.
(accessory(2))
(2)-1 Liquid pipe
(2)-2 Gas pipes
3) Use the clamps
(accessory(1)) to hold both
ends.
Insulation tube installation instructions for unused branch ports
(indoor unit side) (gas and liquid pipes)
Adhere.
Stopper pipes (accessory(4))
(4)-1 Liquid pipe
(4)-2 Gas pipes
1) Attach the
insulation tube
for stopper pipes.
(accessory(5))
(5)-1 Liquid pipe
(5)-2 Gas pipes
CAUTION
•
Wrap insulation material with the seam facing up. (
Refer to Fig. 3.)
6. ELECTRIC WIRING WORK
6-1 General instructions
•
All wiring must be performed by an authorized electrician.
• All field supplied parts and materials, electric works must conform to local codes.
•
Always ground wires. (In accordance with national regulations of the pertinent country.)
•
Always turn off the power before performing the electric wire installation work.
•
Follow the “WIRING DIAGRAM” attached to the unit body to wire the outdoor unit and indoor units.
• Properly connect wire of the specified wire type and copper thickness. Also use the included clamp to
avoid applying excessive force to the terminal (field wire, ground wire).
•
Do not let the ground wire should come in contact with gas pipes, water pipes, lighting rods, or tele-
phone ground wires.
• Gas pipes: gas leaks can cause explosions and fire.
•
Water pipes: cannot be grounded if hard vinyl pipes are used.
• Telephone ground and lightning rods: the ground potential when struck by lightning gets extremely
high.
•
A circuit breaker capable of shutting down the power supply to the entire system must be installed.
•
This system consists of multiple Branch Selector units. Mark each Branch Selector unit as unit A, unit
B . . . , and be sure the terminal board wiring to the outdoor unit and indoor unit are properly matched.
If wiring and piping between the outdoor unit, Branch Selector unit and an indoor unit are mismatched,
the system may cause a malfunction.
•
Do not turn on the power supply (branch switches, overload interrupters) until all other work is done.
Seam
Seam facing up
Fig. 3
11
3P405106-9 English