RXYQ8~1 RXYQ8~12P7YLK
VRVIII System air conditioner
4PW41760-1
Installation manual
2
■
Total capacity/quantity of indoor units
1.2.
Standard supplied accessories
See location 1 in
for reference to where following
accessories are supplied with the unit.
See location 2 in
for reference to where following
accessories are supplied with the unit.
1.3.
Optional accessories
To install the above outdoor units, the following optional parts are
also required.
■
Refrigerant branching kit (for R410A only: Always use an
appropriate kit dedicated for your system.)
■
Outdoor unit multi connection piping kit (For R410A only: Always
use an appropriate kit dedicated for your system.)
■
Pipe size reducer (For R410A only: Always use an appropriate
kit dedicated for your system.)
To select an optimum refrigerant branching kit, refer to
.
1.4.
Technical and Electrical specifications
Refer to the Engineering Data Book for the complete list of
specifications.
2.
M
AIN
COMPONENTS
For main components and function of the main components, refer to
the Engineering Data Book.
Standard combination of outdoor units
Total
capacity of
indoor units
Total
quantity of
indoor units
RXYQ8
(a)
(a) Main unit
100~260
13
RXYQ10
125~325
16
RXYQ12
150~390
19
RXYQ16
=
RXYQ8
+
RXYQ8
200~520
26
RXYQ18
=
RXYQ8
+ RXYQ10
225~585
29
RXYQ20
= RXYQ10
250~650
32
RXYQ22
= RXYQ12
275~715
35
RXYQ24
= RXYQ12
300~780
39
RXYQ26
=
RXYQ8
+
RXYQ8
+ RXYQ10
325~845
42
RXYQ28
=
RXYQ8
+ RXYQ10
350~910
45
RXYQ30
=
RXYQ8
+ RXYQ12
375~975
48
RXYQ32
= RXYQ12
400~1040
52
RXYQ34
= RXYQ12
425~1105
55
RXYQ36
= RXYQ12
450~1170
58
NOTE
■
The table above shows the possible total capacity
and number of possible indoor units when
configured in a standard combination.
■
If the total capacity of the connected indoor units
exceeds the capacity of the outdoor unit, cooling
and heating performance may drop when running
the indoor units.
Refer to the section on performance charac-
teristics in the Engineering Data Book for details.
■
There are restrictions on the refrigerant pipe
connection order between outdoor units during
installation in case of a multiple outdoor unit
system.
Install according to the following restrictions.
The capacities of outdoor units A, B, and C must
fulfill the following restriction conditions:
A
≥
B
≥
C
.
A
B
C
1 2
3
1
To indoor units
2
Outdoor unit multi connection piping kit (first
branch)
3
Outdoor unit multi connection piping kit
(second branch)
Installation manual
1
Operation manual
1
Request for indication of additional
refrigerant charging and leak detection
amount label
1
Gas side accessory pipe
Unit type
Item
Quantity
8~12 Hp
1
8~12 Hp
1
Liquid side accessory pipe
Unit type
Item
Quantity
8~12 Hp
1
8~10 Hp
1
12 Hp
1
Refnet header
Refnet joint
KHRQ22M29H
KHRQ22M20T
KHRQ22M64H
KHRQ22M29T9
KHRQ22M75H
KHRQ22M64T
KHRQ22M75T
Number of outdoor units connected
2
3
BHFQ22P1007
BHFQ22P1517
RXYQ24~36
KHRQ22M75T
KHRQ22M75H