Daikin VRV III RXYQ-PY1K Скачать руководство пользователя страница 23

RXYQ8~1 RXYQ8~12P7YLK
VRVIII System air conditioner
4PW41760-1

Installation manual

20

Continue with the automatic charging in cooling
mode OR in heating mode.

Charging in heating mode

 

6.

Start up
Wait while the unit is preparing for charging in heating mode.

7.

Ready

Press the 

 button once within 5 minutes.

If the 

 button is not pushed within 5 minutes, 

P2

 will be

displayed on the remote controller. Refer to 

"4 Remote controller

malfunction code display" on page 22

.

8.

Operation
When the following LED display is shown, open valve A and
close the frontpanel. If the frontpanel is left open, the system
can not operate properly during the refrigerant charging.

*

 = The state of this LED is not important.

9.

Complete
If the calculated amount of refrigerant minus 10 kg is reached,
close valve A and press the 

 button once.

As long as the 

 button is not pressed, the system

will remain in heating mode. This can be required to increase the
indoor temperature.

10. Press the 

 button to perform the temperature range

check
Out of range:

In these cases, press the 

 button once and follow the

procedure as 

"5 Final adjustment of the amount of refrigerant"

on page 23

.

In range:
The unit will restart from the charging mode judgement onwards
and the cooling mode will be selected. However, if in the mean
time the temperature has become out of range, heating mode
will be selected again, this is required to increase the indoor
temperature.

Charging in cooling mode

6.

Start up
Wait while the unit is preparing for charging in cooling mode.

7.

Ready

Press the 

 button once within 5 minutes.

If the 

 button is not pushed within 5 minutes, 

P2

 will be

displayed on the remote controller. Refer to 

"4 Remote controller

malfunction code display" on page 22

.

8.

Operation
When the following LED display is shown, open valve A and
close the frontpanel. If the frontpanel is left open, the system
can not operate properly during the refrigerant charging.

*

 = The state of this LED is not important.

9.

Complete
If the display on the remote controller shows a flashing

 PE

 code,

charging is almost finished.
When the unit stops operating, close valve A immediately and
check the LEDs and check if the 

P9

  code is displayed on the

remote controller. When the charging amount is little, the 

PE

code may not be displayed, but instead the 

P9

  code will be

displayed immediately.

If it is not as shown above, correct the malfunction (as indicated
in the display of the remote controller) and restart the complete
charging procedure.

10. Press the 

 button to perform the temperature range

check
Out of range:

In these cases, press the 

 button once and follow the

procedure as described in 

"5 Final adjustment of the amount of

refrigerant" on page 23

.

In range:
The state of the LEDs will show:

Press the 

 button once. The procedure is completed.

Record the amount that was added on the "Request for indication
of additional refrigerant charging and leak detection amount" label
provided with the unit and attach it on the switch box cover.
Perform the procedure as described in 

"Inputting of additional

refrigerant charge" on page 23

.

H1P

H2P

H3P

H4P

H5P

H6P

H7P

Pressure control 
(for the first minute)

x c x

x

x

x w

Start up control 
(for the next 2 minutes)

c c x

x

x w x

Waiting for stable 
heating conditions 
(for the next ±15 
minutes (according to 
the system))

c c x

x

x w w

H1P

H2P

H3P

H4P

H5P

H6P

H7P

c c x

x w x w

H1P

H2P

H3P

H4P

H5P

H6P

H7P

w c

*

*

*

*

*

When a malfunction occurs, check the display of the
remote controller and refer to 

"4 Remote  controller

malfunction code display" on page 22

.

H1P

H2P

H3P

H4P

H5P

H6P

H7P

c c c w w w w

H1P

H2P

H3P

H4P

H5P

H6P

H7P

Out of outdoor 
temperture range

w c c c w x

x

Out of indoor 
temperture range

w c c c x w x

BS4  TEST

BS4  TEST

BS3  RETURN

BS3  RETURN

BS4  TEST

BS1  MODE

H1P

H2P

H3P

H4P

H5P

H6P

H7P

Pressure control 
(for the first minute)

x c x

x

x

x w

Start up control 
(for the next 2 minutes)

x c x

x

x w x

Waiting for stable 
heating conditions 
(for the next ±15 
minutes (according to 
the system))

x c x

x

x w w

H1P

H2P

H3P

H4P

H5P

H6P

H7P

c c c x w x w

H1P

H2P

H3P

H4P

H5P

H6P

H7P

w c

*

*

*

*

*

When a malfunction occurs, check the display of the
remote controller and refer to 

"4 Remote  controller

malfunction code display" on page 22

.

H1P

H2P

H3P

H4P

H5P

H6P

H7P

w c c w w w w

H1P

H2P

H3P

H4P

H5P

H6P

H7P

Out of outdoor 
temperture range

w c c c w x

x

Out of indoor 
temperture range

w c c c x w x

H1P

H2P

H3P

H4P

H5P

H6P

H7P

w c c w w w w

BS4  TEST

BS4  TEST

BS4  TEST

BS1  MODE

BS1  MODE

Содержание VRV III RXYQ-PY1K

Страница 1: ...INSTALLATION MANUAL RXYQ8P7Y1K RXYQ10P7Y1K RXYQ12P7Y1K RXYQ8P7YLK RXYQ10P7YLK RXYQ12P7YLK System air conditioner...

Страница 2: ...XYQ16 32 2 1 h1 h2 a 10 mm b 300 mm c 10 mm d 500 mm a 50 mm b 100 mm c 50 mm d 500 mm a 200 mm b 300 mm a 10 mm b 300 mm c 10 mm d 500 mm e 20 mm a 50 mm b 100 mm c 50 mm d 500 mm e 100 mm a 200 mm b...

Страница 3: ...OUT D UNIT TO MULTI UNIT A1P 3 A B C F1 F2 F1 F2 Q1 Q2 Q1 Q2 A1P 4 4 5 6 2 1 3 Q1 Q2 7 5 3 4 1 6 6 2 2 TO IN D UNIT F1 F2 DS1 1 2 3 4 OFF ON O U T I N F1 F2 P1 P2 P1 P2 1 A B C A B C 1 DS1 1 2 3 4 OF...

Страница 4: ...for their installation 1 1 Combination The indoor units can be installed in the following range Always use appropriate indoor units compatible with R410A To learn which models of indoor units are com...

Страница 5: ...5 35 RXYQ24 RXYQ12 RXYQ12 300 780 39 RXYQ26 RXYQ8 RXYQ8 RXYQ10 325 845 42 RXYQ28 RXYQ8 RXYQ10 RXYQ10 350 910 45 RXYQ30 RXYQ8 RXYQ10 RXYQ12 375 975 48 RXYQ32 RXYQ10 RXYQ10 RXYQ12 400 1040 52 RXYQ34 RXY...

Страница 6: ...easures in order to prevent that the outdoor unit be used as a shelter by small animals Small animals making contact with electrical parts can cause malfunctions smoke or fire Please instruct the cust...

Страница 7: ...G 1 Packaging material 2 Opening large 3 Belt sling 4 Opening small 40x45 5 Protector NOTE Use a belt sling of 20 mm wide that adequately bears the weight of the unit NOTE Use filler cloth on the fork...

Страница 8: ...size is not available stick to the original pipe diameter which may result in a small capacity decrease 6 3 Pipe connection Be sure to perform a nitrogen blow when brazing and to read the paragraph C...

Страница 9: ...on into the piping side Pattern 1 Pattern 2 Prohibited patterns change to pattern 1 or 2 1 Pinched piping 2 Stop valve 3 Service port 4 Point of melting the brazing metal Precautions when connecting f...

Страница 10: ...e than 500 mm of straight section can be ensured Improper installation may lead to malfunction of the outdoor unit 6 Piping length restrictions Make sure to perform the piping installation within the...

Страница 11: ...be used with R410A How to select the refnet joint When using refnet joints at the first branch counted from the outdoor unit side Choose from the following table in accordance with the capacity of the...

Страница 12: ...es must be doubled except main pipe and the pipes that not increase the pipe size a b 2 c 2 d 2 e 2 f 2 g 2 h i j k l m n p 1000 m Indoor unit to the nearest branch kit 40 m h i j p 40 m The differenc...

Страница 13: ...side stop valve Gas side stop valve Performing the airtightness test and vacuum drying Valve A must always be shut Otherwise the refrigerant in the unit will pour out Close Open Open Close Close NOTE...

Страница 14: ...stor current limiting S1NPH Pressure sensor high S1NPL Pressure sensor low S1PH S2PH Pressure switch high T1A Current sensor A6P A7P SD1 Safety devices input V1R Power module A3P A4P A8P V2R Diode bri...

Страница 15: ...prevent malfunctioning of the earth leakage breaker itself Earth leakage breakers that are especially designed for protecting ground faults must be used in conjunction with main switch and fuse for us...

Страница 16: ...akage breaker 4 Outdoor unit 5 Indoor unit 6 Remote controller Power supply wiring sheathed cable outdoor 3 phase 380 415 V indoor 1 phase 230 V Transmission wiring sheathed cable 16 V 1 Electric wiri...

Страница 17: ...16 branches are possible for unit to unit cabling No branching is allowed after branching See figure 16 Never connect the power supply to transmission wiring terminal block Otherwise the entire system...

Страница 18: ...ying power wiring Do not connect wiring of different thicknesses to the power terminal block Slack in the power wiring may cause abnormal heat When connecting wiring which is the same thickness do as...

Страница 19: ...ansmission wiring between outdoor and indoor unit outdoor and COOL HEAT selector etc 11 CHARGING REFRIGERANT The outdoor unit is factory charged but depending on the length of the piping when installe...

Страница 20: ...d line stop valve 9 5 a a The model RXYQ12 supports field piping of 12 7 on the accessory pipe supplied with the unit Gas line stop valve 19 1 25 4 b b The model RXYQ10 supports field piping of 22 2 o...

Страница 21: ...r the power is on via the service lid which is in the lid of the electric box Operate switches with an insulated stick such as a ball point pen to avoid touching the life parts Make sure to re attach...

Страница 22: ...tton once if the LEDs combination is not as in the figure below 3 Press the button once 4 Hold the button down for 5 seconds or more 5 Charging mode judgement For automatic charging the charging must...

Страница 23: ...d check the LEDs and check if the P9 code is displayed on the remote controller When the charging amount is little the PE code may not be displayed but instead the P9 code will be displayed immediatel...

Страница 24: ...mode is not possible in some cases The unit will automatically select the cooling mode or heating mode for charging Continue with the manually charging in cooling mode OR in heating mode Charging in...

Страница 25: ...e controller malfunction code display on page 22 H1P H2P H3P H4P H5P H6P H7P w c c w w w w BS4 TEST BS4 TEST BS1 MODE LED display Default status before delivery Micro computer operation monitor Mode R...

Страница 26: ...form the overcharge judgement procedure again When there is no more overcharging of refrigerant detected restart the automatic refrigerant charging from 1 Start of automatic charging refrigerant as ex...

Страница 27: ...uch as a ball point pen to avoid touching live parts Make sure to re attach the inspection cover 1 into the switch box cover 2 after the job is finished WARNING ELECTRIC SHOCK Caution when performing...

Страница 28: ...selection on page 13 not installed factory setting 2 4 NOT USED DO NOT CHANGE THE FACTORY SETTING What to set with dip switch DS2 1 4 NOT USED DO NOT CHANGE THE FACTORY SETTING What to set with dip s...

Страница 29: ...he external control adapter F power consumption limitation setting via the external control adapter G enabling function of the low noise operation level setting and or power consumption limitation set...

Страница 30: ...pleted Normal operation will be possible after 5 minutes If a malfunction code is displayed on the remote controller correct the malfunction and perform the check operation again as decribed in Correc...

Страница 31: ...tion will be prohibited 2 Cut off the power supply to the indoor units and the outdoor unit with the circuit breaker After the power supply to one side is cut off cut off the power supply to the other...

Страница 32: ...such as the following calculate the volume of A B as a single room or as the smallest room 3 Calculating the refrigerant density using the results of the calculations in steps 1 and 2 above If the re...

Страница 33: ...5 1 7 10 3 2 9 6 6 6 6 7 4 11 8 6 6 6 6 6 6 7 7 9 8 4 11 6 6 1 10 3 2 6 6 6 6 28 13 6 9 8 1 2 4 3 5 14 15 16 12 11 10 10 7 29 13 14 3 5 4 2 1 7 8 9 6 10 10 11 10 2 2 12 9 9 30 13 14 3 5 4 2 1 7 8 9 6...

Страница 34: ...4PW41760 1 Copyright Daikin...