Field Setting from Outdoor Unit
SiBE341027
78
Test Operation
Setting item 0 Display contents of “Number of units for various settings”
EMG operation /
backup operation
setting
ON
l h h k h h h
OFF
l h h h h h h
Defrost select setting
Short
l h h h k h h
Medium
l h h h l h h
Long
l h h h h h h
Te setting
L
l h h h h h h
M
l h h h h l h
H
~
l h h h h k h
Tc setting
L
l h h h h h h
M
l h h h h h l
H
l h h h h h k
★
Data such as addresses and number of units is expressed as binary numbers; the two ways of
expressing are as follows:
The No. 1 cool/heat unified address is expressed as a binary number consisting
of the lower 6 digits. (0 - 63)
In
c
the address is 010110 (binary number), which translates to 16 + 4 + 2 = 22
(base 10 number). In other words, the address is 22.
The number of terminal blocks for No. 12 and 13 is expressed as an 8-digit
binary number, which is the combination of four upper, and four lower digits for
No. 12 and 13 respectively. (0 - 128)
In
d
the address for No. 12 is 0101, the address for No. 13 is 0110, and the
combination of the two is 01010110 (binary number), which translates to 64 + 16
+ 4 + 2 = 86 (base 10 number). In other words, the number of terminal block is
86.
l
h l h l l h
16 4 1
32 8 2
l h h
h l h l
64 16
128 32
No.12
l h h
h l l h
4 1
No.13
8
2