SiBE341027
Troubleshooting by Remote Controller
Service Diagnosis
139
2.23 Overcurrent Abnormal of Inverter Compressor
Remote
Controller
Display
L8
Applicable
Models
RQYQ-PY1B
Method of Error
Detection
Error is detected from the current flowing in the power transistor.
Error Decision
Conditions
When the inverter secondary current value is below.
(1) 33.5A and over continues for 5 seconds.
(2) 27.6A and over continues for 260 seconds.
Supposed
Causes
Compressor overload
Compressor coil disconnected
Defective wiring to the compressor
Defective inverter PCB