Troubleshooting by Remote Controller
SiBE341027
132
Service Diagnosis
2.19 Low Pressure Sensor Abnormality
Remote
Controller
Display
JC
Applicable
Models
RQYQ-PY1B
Method of Error
Detection
Error is detected from the pressure detected by the low pressure sensor.
Error Decision
Conditions
When the low pressure sensor is short circuit or open circuit.
(Not less than 1.77MPa, or -0.01MPa and below)
Supposed
Causes
Defect of low pressure sensor
Connection of high pressure sensor with wrong connection.
Defect of outdoor unit PCB
Defective connection of low pressure sensor
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Are the characteristics of the low
pressure sensor normal? (Make
a comparison between the
voltage characteristics (*1) and
the gauge pressure.)
NO
Replace the low pressure sensor.
1. Mount the low pressure
gauge.
2. Connect the checker for
VRV.
If the PCB pressure
detection normal? (Make a
comparison between the
checker pressure data and
the voltage characteristics
(*1).)
Reset the operation, and then
restart the outdoor unit.
Are the
characteristics of
the low pressure
sensor normal?
Replace the outdoor unit PCB.
Replace the low pressure sensor.
Replace the outdoor unit PCB.
NO
NO
YES
YES
YES