Field Settings for Indoor Unit
SiUS342303E
155
Part 5 Field Settings and Test Operation
1.2 List of Field Settings for Indoor Unit
: Factory setting
Mode
No.
(Note 2)
First
Code
No.
Setting Contents
Second Code No.
Reference
Page
01
02
03
04
10 (20)
0
Filter
cleaning
sign
interval
Ultra long life
filter
Light
Approx.
10,000
hrs.
Heavy
Approx.
5,000
hrs.
—
—
Long life filter
Approx.
2,500
hrs.
Approx.
1,250
hrs.
Standard filter
Approx.
200
hrs.
Approx.
100 hrs.
0
Filter sign setting
Light
Heavy
—
—
1
Filter type
Long life filter
Ultra long life filter
—
—
1
Filter cleaning sign interval
Short interval
Long interval
—
—
2
Remote controller thermistor
Refer to page on the right for details.
3
Filter cleaning sign
Displayed
Not displayed
—
—
5
Information for intelligent
Touch Manager / intelligent
Touch Controller
Refer to page on the right for details.
6
Remote controller thermistor
control during group control
Not permitted
Permitted
—
—
7
Time for absence area
detection
30 minutes
60 minutes
—
—
11 (21)
1
Auxiliary electric heater ON
temperature: Ton
Refer to page on the right for details.
1
Auxiliary electric heater
ON/OFF temperature:
Ton/Toff
2
Auxiliary electric heater OFF
temperature: Toff
3
Setting of airflow rate when
heating
Standard
Slightly increased
Increased
—
3
Electric heater setting
Refer to page on the right for details.
5
Electric heater capacity
setting
Refer to page on the right for details.
6
Detection rate setting
High sensitivity
Low sensitivity
Standard
sensitivity
Infrared
presence
sensor
disabled
7
Automatic airflow adjustment
OFF
Completion of
airflow adjustment
Start of airflow
adjustment
—
8
Compensating the
temperature around people
Suction air
temperature only
Priorities given on
the suction air
temperature
Standard
Priorities given
on the floor
temperature
9
Compensating the floor
temperature
–4°C (–7.2°F)
–2°C (–3.6°F)
0°C (0°F)
+2°C (+3.6°F)
12
Dry mode set temperature
Room
temperature
Same as cooling
mode set
temperature
—
—
12 (22)
0
Optional output switching
Refer to page on the right for details.
1
External ON/OFF input
Refer to page on the right for details.
2
Thermostat switching
1°C (1.8°F)
0.5°C (0.9°F)
—
—
3
Airflow setting when heating
thermostat is OFF
LL tap
Set fan speed
OFF
—
4
Setting of operation mode to
AUTO
Refer to page on the right for details.
5
Auto restart after power
failure
OFF
ON
—
—
6
Airflow setting when cooling
thermostat is OFF
LL tap
Set fan speed
OFF
—
Содержание VRV EMERION RXYQ-AATJA
Страница 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Страница 380: ...Check SiUS342303E 373 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 379 CHECK 8 Refer to page 380...
Страница 405: ...SiUS342303E Wiring Diagrams Part 7 Appendix 398 RXYQ72 96 120 144 168 192 216 240AAYDA C 2D140769B...
Страница 406: ...Wiring Diagrams SiUS342303E 399 Part 7 Appendix 1 2 Indoor Unit FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 407: ...SiUS342303E Wiring Diagrams Part 7 Appendix 400 BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ TVJU 3D076375A...
Страница 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 413: ...SiUS342303E Wiring Diagrams Part 7 Appendix 406 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Страница 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 423: ...SiUS342303E Wiring Diagrams Part 7 Appendix 416 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269D...
Страница 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...