SiUS342303E
Field Settings for Indoor Unit
Part 5 Field Settings and Test Operation
170
1.4.17 Thermostat Switching
Differential value during thermostat ON/OFF control can be changed.
Factory Setting
1.4.18 Airflow Setting when Heating Thermostat is OFF
This setting is used to set airflow when heating thermostat is OFF.
If the airflow setting when thermostat is OFF is set to 03: OFF, the air in the indoor unit will be
stagnant and suction air thermistor may not detect room temperature correctly, resulting in
problems that thermostat will not be ON easily.
Use optional remote sensor in such conditions, or set the field setting 10 (20)-2 to
03
(only remote
controller thermistor).
When thermostat OFF airflow volume up mode is used, careful consideration is required before
deciding installation location.
: Factory setting
1.4.19 Setting of Operation Mode to AUTO
This setting makes it possible to change differential values for mode selection while in automatic
operation mode, only when the wireless remote controller or any central remote controller is
connected.
: Factory setting
The automatic operation mode setting is made by the use of the "Operation Mode Selector" button.
1.4.20 Auto Restart after Power Failure
: Factory setting
When the "Auto Restart after Power Failure" setting is turned OFF, all the units will remain OFF
after power failure, or after the main power supply is restored. When this setting is turned ON
(factory setting), the units that were operating before the power failure will automatically restart
operation after power failure, or after the main power supply is restored.
Mode No.
First Code No.
Second Code No.
Contents
12 (22)
2
01
1°C (1.8°F)
02
0.5°C (0.9°F)
Model
Second Code No.
Contents
FXFQ-T, FXEQ-P, FXHQ-M, FXTQ-TA
01
1°C (1.8°F)
FXZQ-TB, FXUQ-PA, FXDQ-M, FXSQ-TB, FXMQ-PB,
FXMQ-TB, FXMQ-M, FXAQ-P, FXLQ-M, FXNQ-M, FXMQ-MF,
CXTQ-TA
02
0.5°C (0.9°F)
Mode No.
First Code No.
Second Code No.
Contents
12 (22)
3
01
LL tap
02
Set fan speed
03
OFF
Mode No.
First Code
No.
Second Code No.
01
02
03
04
05
06
07
08
12 (22)
4
0°C
(0°F)
1°C
(1.8°F)
2°C
(3.6°F)
3°C
(5.4°F)
4°C
(7.2°F)
5°C
(9.0°F)
6°C
(10.8°F)
7°C
(12.6°F)
Mode
No.
First
Code No.
Second
Code No.
Contents
12 (22)
5
01
OFF
02
ON
Содержание VRV EMERION RXYQ-AATJA
Страница 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Страница 380: ...Check SiUS342303E 373 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 379 CHECK 8 Refer to page 380...
Страница 405: ...SiUS342303E Wiring Diagrams Part 7 Appendix 398 RXYQ72 96 120 144 168 192 216 240AAYDA C 2D140769B...
Страница 406: ...Wiring Diagrams SiUS342303E 399 Part 7 Appendix 1 2 Indoor Unit FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 407: ...SiUS342303E Wiring Diagrams Part 7 Appendix 400 BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ TVJU 3D076375A...
Страница 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 413: ...SiUS342303E Wiring Diagrams Part 7 Appendix 406 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Страница 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 423: ...SiUS342303E Wiring Diagrams Part 7 Appendix 416 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269D...
Страница 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...