Field Settings for Indoor Unit
SiUS342303E
165
Part 5 Field Settings and Test Operation
There is a limitation of combination between Ton and Toff as below due to 2°C (3.6°F) hysteresis
required for reliability.
1 The second code No. 07 is used for disabling the starting of gas furnace interlocking with room
temperature.
1.4.7 Setting of Airflow Rate when Heating
The fan revolution is changed to maintain the sufficient distance for warm air to reach during the
heating operation. The setting should be changed depending on the installation condition of the
unit.
: Factory setting
Note that this setting is effective only during the heating operation.
Second Code No.
Ton
01
02
03
04
05
06
–4°C
(–7.2°F)
–3.5°C
(–6.3°F)
–3°C
(–5.4°F)
–2.5°C
(–4.5°F)
–2°C
(–3.6°F)
–1.5°C
(–2.7°F)
To
ff
06
0.5°C (0.9°F)
h
h
h
h
h
h
05
0°C (0°F)
h
h
h
h
h
—
04
–0.5°C (–0.9°F)
h
h
h
h
—
—
03
–1°C (–1.8°F)
h
h
h
—
—
—
02
–1.5°C (–2.7°F)
h
h
—
—
—
—
01
–2°C (–3.6°F)
h
—
—
—
—
—
h
—
: Available
: Not available
CXTQ-TA
: Factory setting
Mode
No.
First Code
No.
Symbol
Second Code No.
01
02
03
04
05
06
07 (
1)
11 (21)
1
Ton
–4°C
(–7.2°F)
–3.5°C
(–6.3°F)
–3°C
(–5.4°F)
–2.5°C
(–4.5°F)
–2°C
(–3.6°F)
–1.5°C
(–2.7°F)
–100°C
(–148°F)
2
Toff
–2°C
(–3.6°F)
–1.5°C
(–2.7°F)
–1°C
(–1.8°F)
–0.5°C
(–0.9°F)
0°C
(0°F)
0.5°C
(0.9°F)
–98°C
(–144.4°F)
Second Code No.
Ton
01
02
03
04
05
06
07
–4°C
(–7.2°F)
–3.5°C
(–6.3°F)
–3°C
(–5.4°F)
–2.5°C
(–4.5°F)
–2°C
(–3.6°F)
–1.5°C
(–2.7°F)
–100°C
(–148°F)
Toff
07
–98°C (–144.4°F)
—
—
—
—
—
—
h
06
0.5°C (0.9°F)
h
h
h
h
h
h
h
05
0°C (0°F)
h
h
h
h
h
—
h
04
–0.5°C (–0.9°F)
h
h
h
h
—
—
h
03
–1°C (–1.8°F)
h
h
h
—
—
—
h
02
–1.5°C (–2.7°F)
h
h
—
—
—
—
h
01
–2°C (–3.6°F)
h
—
—
—
—
—
h
h
—
: Available
: Not available
Mode
No.
First Code
No.
Second Code
No.
Contents
11 (21)
3
01
Standard
02
Slightly increased
03
Increased
Содержание VRV EMERION RXYQ-AATJA
Страница 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Страница 380: ...Check SiUS342303E 373 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 379 CHECK 8 Refer to page 380...
Страница 405: ...SiUS342303E Wiring Diagrams Part 7 Appendix 398 RXYQ72 96 120 144 168 192 216 240AAYDA C 2D140769B...
Страница 406: ...Wiring Diagrams SiUS342303E 399 Part 7 Appendix 1 2 Indoor Unit FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 407: ...SiUS342303E Wiring Diagrams Part 7 Appendix 400 BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ TVJU 3D076375A...
Страница 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 413: ...SiUS342303E Wiring Diagrams Part 7 Appendix 406 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Страница 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 423: ...SiUS342303E Wiring Diagrams Part 7 Appendix 416 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269D...
Страница 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...