3
|
Specific installer safety instructions
Installer and user reference guide
14
BS4~12A14AJV1B
VRV 5 branch selector unit
4P695527-1 – 2022.02
WARNING
The appliance shall be stored as follows:
▪
in such a way as to prevent mechanical damage.
▪
in a well-ventilated room without continuously operating ignition sources
(example: open flames, an operating gas appliance or an operating electric
heater).
▪
in a room with dimensions as specified in
"13 Special requirements for R32
40].
WARNING
Make sure installation, servicing, maintenance and repair comply with instructions
from Daikin and with applicable legislation and are executed ONLY by authorised
persons.
CAUTION
Do NOT use potential sources of ignition in searching for or detection of refrigerant
leaks.
NOTICE
▪
Take precautions to avoid excessive vibration or pulsation to refrigeration piping.
▪
Protect the protection devices, piping and fittings as much as possible against
adverse environmental effects.
▪
Provide space for expansion and contraction of long runs of piping.
▪
Design and install piping in refrigerating systems such as to minimise the
likelihood of hydraulic shock damaging the system.
▪
Mount the indoor equipment and pipes securely and protect them to avoid
accidental rupture of equipment or pipes in case of events such as moving
furniture or reconstruction activities.
NOTICE
▪
Do NOT re-use joints and copper gaskets which have been used already.
▪
Joints made in installation between parts of refrigerant system shall be accessible
for maintenance purposes.
See
"13.3 To determine the required safety measures"
41] to check if your
system meets the R32 safety requirements.