English

4

2 Operation lamp (red)

The lamp lights up during operation or blinks if a malfunc-
tion occurs.

3 Display “

” (changeover under control)

May be displayed when combined with a VRV-system air 
conditioner.
It is impossible to changeover heat/cool with the remote 
controller when this icon is displayed.

4 Display “

” (air flow flap)

This displays the direction and mode of the air flow flap of 
the combined air conditioner.

5 Display “

” (ventilation/air cleaning)

This display shows that the total heat exchange and the air 
cleaning unit are in operation. (these are optional accessories)

6 Display “

” (set temperature)

This displays the set temperature of the combined air con-
ditioner.
It is not displayed when the unit is used as an independent 
system.

7 Display “

” “

” “

” “

” “

” (operation 

mode: “FAN, DRY, AUTOMATIC, COOLING, HEATING”)

This displays the operating status of the combined air con-
ditioner.
• There is no “heating” for the VRV

II

 system (Cooling only 

type).

• “

” is only available for systems operating in cooling 

and heating at the same time.

8 Display “

” (programmed time)

This display shows the programmed time of the system 
start or stop.

9 Display “

” (inspection/test operation)

When the inspection/test operation button is pressed, the 
display shows the mode in which the system actually is.

• Do not use under usual use (service person/installer only).

10 Display “

” (under centralized control)

When this display shows, the system is under centralized 
control. (This is not a standard specification.)

11 Display “

” (fan speed)

This display shows the fan speed you have selected.

This is only displayed when the fan speed selection but-
ton is pressed. It normally displays the set fan strength of 
the combined air conditioner.

12 Display “

” (time to clean air filter)

Refer to “4.1 HOW TO CLEAN THE AIR FILTER”.

13 Display “

” (defrost/hot start)

It may be displayed when freezing of outdoor unit’s coil 
increases in heating mode.

14 Timer mode start/stop button

Refer to the chapter “Operation procedure - 
Programming start and stop of the system with timer.”
(Refer to page 9 (3.3))

15 Timer on/off button

Refer to the chapter “Operation procedure - 
Programming start and stop of the system with timer.”
(Refer to page 9 (3.3))

16 Inspection/test operation button

Pressed during inspection or “test run.”

• Do not use under usual use. (service person/installer only)

17 Programming time button

Use this button for programming start and/or stop time.

18 Temperature setting button

Use this button for setting the desired temperature of air 
conditioner combined with this unit.
This button can’t use for this unit.
This unit can’t change temperature setting.

19 Filter sign reset button

Refer to “4.1 HOW TO CLEAN THE AIR FILTER”.

20 Fan speed control button

Press this button to select the fan speed of air conditioner 
combined with this unit.

21 Operation mode selector button

Press this button to select the operation mode of air condi-
tioner combined with this unit.

22 Air flow direction adjust button

Press this button to select the air flow direction of air con-
ditioner combined with this unit.

23 Fan only/air conditioning selector switch

Set the switch to “

” for fan only operation or to “

” 

for heating or cooling operation.

24 Cool/heat changeover switch

Set the switch to “

” for cooling or to “

” for heating 

operation.

25 Remote controller thermo

This detects the temperature around the remote controller. 
This is not the same as the temperature of return air from 
room (RA) by heat exchanger unit.

26 Display “NOT AVAILABLE”

• “NOT AVAILABLE” may be displayed for a few seconds if 

the function for the button pressed is not available for the 
unit or the air conditioner.

• “NOT AVAILABLE” is only displayed when none of the 

indoor units is equipped with the function in question when 
running several units simultaneously. It is not displayed if 
the function is available on even one of the units.

27 Display “

” “

” “

This displays the ventilation mode. (BRC1D527 and so 
on.) (This is not displayed on the controller BRC1A62)

28 Ventilation mode selector button (available only con-

necting the HRV unit)

This is pressed to switch the ventilation mode of the HRV unit.

29 Ventilation fan speed control button (available only 

connecting the HRV unit)

This is pressed to control the fan speed of the HRV unit.

(Refer to item 11)

30 LEAVE HOME ICON “

The leave home icon shows the status of the leave home 
function.

31 DAY OF THE WEEK INDICATOR “

The day of the week indicator shows the current week day 
(or the set day when reading or programming the schedule 
timer).

32 CLOCK DISPLAY “

The clock display indicates the current time (or the action 
time when reading or programming the schedule timer).

33 MAXIMUM SET TEMPERATURE “

The maximum set temperature indicates the maximum set 
temperature when in limit operation.

C

TEST

ON

Leave home is enabled

FLASHING

Leave home is active

OFF

Leave home is disabled

01_EN_3P130767-3G.fm  Page 4  Monday, March 5, 2007  10:05 AM

Содержание VKM100GAMV1

Страница 1: ...ий OPERATION MANUAL Total Heat Exchanger HRV Heat Reclaim Ventilation with DX Coil MODELS Ceiling mounted duct type With DX coil Humidifier VKM50GAMV1 VKM80GAMV1 VKM100GAMV1 With DX coil VKM50GAV1 VKM80GAV1 VKM100GAV1 00_CV_3P130767 3G_01 fm Page 1 Wednesday March 7 2007 3 18 PM ...

Страница 2: ...e al condizionatore d aria per interni sistema VRVII di tipo M RXYQ REYQ RXQ È anche possibile utilizzare questa unità come sistema indipendente L unità non può controllare la temperatura del locale Se ciò è necessario non installare l unità HRV da sola ma invece installare un altra unità interna Per controllare l unità utilizzare il telecomando del condizionatore d aria interno a sistema VRVII HR...

Страница 3: ...e cover 6 Electric parts box 8 Heat exchanger elements 12 Gas pipe 13 Liquid pipe 16 Strainer included VKM GAMV1 series only VKM GAMV1 series only 14 Drain outlet 15 Humidifier Natural evaporating type 19 Remote controller Optional accessory 11 Direct expansion coil 9 Name plate 10 Air supply fan 4 Air filter Long life filter 5 Damper 21 EA Exhaust air to outdoors 22 OA Fresh air from outdoors out...

Страница 4: ...dent system HRV With DX Coil Remote controller for indoor unit Outdoor unit Remote controller for VRV BRC1A62 3 2 Remote controller for VRV BRC1A62 4 1 5 3 Remote controller for VKM BRC1D527 EU only 4 5 UNIT No GROUP Remote controller for VKM BRC1D527 EU only 4 1 2 3 2 00_CV_3P130767 3G_02 fm Page 2 Friday March 2 2007 6 37 PM ...

Страница 5: ... BRC1D527 EU only 1 2 3 6 1 Heat exchanger element 2 2 Handle 3 Rail 9 1 Air filter 8 2 8 1 3 10 11 12 1 3 2 Remote controller for VRV BRC1A62 7 6 7 UNIT No GROUP Remote controller for VKM BRC1D527 EU only 1 2 4 7 8 3 5 6 00_CV_3P130767 3G_02 fm Page 3 Friday March 2 2007 6 37 PM ...

Страница 6: ...ot including air filters etc Be sure to stop the unit and turn off the power when cleaning or inspecting it As the fan is rotating at high speed it will cause injury Never inspect or service the unit by yourself Ask a qualified service person to perform this work The qualified service person Keep all flames away if the refrigerant leaks The refrigerant in the air conditioner is safe and normally d...

Страница 7: ... When the HRV unit is to be installed in a small room it is necessary to take proper measures so that the amount of any leaked refrigerant does not exceed the limiting concen tration even when it leaks If the refrigerant leaks exceeding the level of limiting concentration an oxygen deficiency acci dent may happen Do not install the HRV unit at any place where flamma ble gas may leak out If the gas...

Страница 8: ...ditioner CHECK LIST CORRESPONDING TO OPERATING NOISE Is the unit installed at the following locations a Location strong enough to support the weight of the unit and which will not amplify noise or vibration b Location where the warm air and the noise from the outlet vent of the outdoor unit will not bother neighbors Are any obstructions near the outlet vent of the outdoor unit They may reduce the ...

Страница 9: ...tton for programming start and or stop time 18 Temperature setting button Use this button for setting the desired temperature of air conditioner combined with this unit This button can t use for this unit This unit can t change temperature setting 19 Filter sign reset button Refer to 4 1 HOW TO CLEAN THE AIR FILTER 20 Fan speed control button Press this button to select the fan speed of air condit...

Страница 10: ...sing the unit as an independent system Ask your dealer what kind of system your system is set up for before operation For the operation of the remote controller for indoor unit and centralized controller refer to the instruction manual provided with each unit See the included operating manuals for details on how to operate each remote control OPERATION for EACH SYSTEM Sample system Refer to figure...

Страница 11: ...t exchange mode VRV Fan mode HRV Heat exchange mode VRV Stopping HRV Heat exchange mode When air conditioner and HRV unit are not connected via duct Operation mode VRV Cooling mode HRV Heat exchange mode VRV Fan mode HRV Heat exchange mode When air conditioner and HRV unit are connected via duct Operation mode VRV Cooling mode HRV Heat exchange mode VRV Fan mode HRV Heat exchange mode VRV Stopping...

Страница 12: ...set for systems operating in cooling and heating at the same time is displayed on all remote controllers when using the VRVΙΙ system cooling only type but only and can be set Select the operating mode on a remote controller on which is not displayed and only for simultaneous cooling heat ing systems cannot be selected on remote controllers on which it is displayed See 3 2 if is displayed Press ven...

Страница 13: ...ues driv ing factory setting The purpose of this is to maintain the amount of ventilation and humidifying The change of the layout in the room should be examined when the cold draft from air supplying opening is feared Though the fan can be stopped by the setting of remote con troller Do not stop the fan in the place where no ventilation by stop ping the fan may cause the influence of diffusion of...

Страница 14: ...D SET THE TIMER WITH THE REMOTE CONTROLLER BRC1A62 Refer to figure 7 The timer is operated in the following two ways Programming the stop time The system stops operating after the set time has elapsed Programming the start time The system starts operating after the set time has elapsed The start and the stop time can be simultaneously pro grammed Press the timer mode start stop button several time...

Страница 15: ...ered you must confirm the programmed actions Make sure the last schedule timer action you want to keep is selected schedule timer actions with a higher number will be deleted Now you must choose between 2 options 1 CONFIRM AND COPY TO NEXT DAY The schedule timer action programmed for the current day are also valid for the next day use the confirm last action and copy actions to next day function b...

Страница 16: ...CESSARY Increase the frequency of cleaning if the unit is installed in a room where the air is etermely contaminated If the dirt becomes impossible to clean change the air filter Air filter for exchange is optional 1 Detach the maintenance cover Go into ceiling through the inspection hatch remove binding metal of maintenance cover and take it off Refer to figure 8 1 2 Detach the air filter Take ou...

Страница 17: ...oller does not display any error code Usage under that status will lead to insufficient humidification and increased tap water consumption The solenoid valve should be checked at the beginning of the heating season For dealers 4 5 INSPECTION OF THE FAN MOTER NOTE When the fan motor fails the remote controller does not dis play any error code Usage under that status will lead to insufficient ventil...

Страница 18: ...the power on The remote control buttons do not work well Measure Turn off the main power switch If the display INSPECTION UNIT No and the OPERATION lamp flash and the MALFUNCTION CODE appears Measure Notify and inform the model name and what the malfunction code indicates to your Daikin dealer There are other malfunctions Measure Stop the unit List of malfunction codes of Remote controller of the ...

Страница 19: ...board and other electric parts h Is the float switch broken Replace the float switch i Is the water supply pressure sufficient Re set it so that there is sufficient pressure j Is there foreign matter in the feed water tank Clean the feed water tank After sales service and warranty After sales service WARNING Do not modify the unit This may cause electric shock or fire Do not disassemble or repair ...

Страница 20: ... wear out parts The cycle is not the same as the warranty period Table 2 Replacement Cycle Lists Note 1 This table indicates main parts See the maintenance and inspection contract for details Note 2 This maintenance cycle indicates recommended lengths of time until the need arises for maintenance work in order to ensure the product is operational as long as possible Use for appropriate maintenance...

Страница 21: ...3P130767 3G EM05A069A 0704 HT 00_CV_3P130767 3G_01 fm Page 2 Wednesday March 7 2007 3 18 PM ...

Отзывы: