15
English
• Table 1 “Inspection Cycle” and “Maintenance Cycle” Lists
*1:
• When the fan motor fails, the remote controller does not dis-
play any error code.
Usage under that status will lead to insufficient ventilation.
The air supply and exhaust fans should be checked once
every one or two months.
• You can make a simple check such as below way.
To check the wind flow, hold a bar of which the end has a
string or other similar lightweight item over the supply grille
and exhaust grille.
*2:
• When the solenoid valve fails, the remote controller does not
display any error code.
Usage under that status will lead to insufficient humidification
and increased tap water consumption.
The solenoid valve should be checked at the biginning of the
heating season.
Note 1
This table indicates main parts.
See the maintenance and inspection contract for details.
Note 2
This maintenance cycle indicates recommended lengths of
time until the need arises for maintenance work, in order to
ensure the product is operational as long as possible.
Use for appropriate maintenance design (budgeting mainte-
nance and inspection fees, etc.).
Depending on the content of the maintenance and inspection
contract, the inspection and maintenance cycles may in reality
be shorter than those listed here.
Shortening of “maintenance cycle” and “replacement
cycle” needs to be considered in the following cases.
• When used in hot, humid locations or locations where tem-
perature and humidity fluctuate greatly.
• When used in locations where power fluctuation (voltage, fre-
quency, wave distortion, etc.) is high.
(Cannot be used if it is outside the allowable range.)
• When installed and used in locations where bumps and
vibrations are frequent.
• When used in bad locations where dust, salt, harmful gas or
oil mist such as sulfurous acid and hydrogen sulfide may be
present in the air.
• When used in locations where the machine is started and
stopped frequently or operation time is long. (Example:
24 hour air-conditioning)
• When the supply water is hard water the humidifier’s life
become shorter.
Recommended replacement cycle of wear-out parts
[The cycle is not the same as the warranty period.]
• Table 2 “Replacement Cycle” Lists
Note 1
This table indicates main parts.
See the maintenance and inspection contract for details.
Note 2
This maintenance cycle indicates recommended lengths of
time until the need arises for maintenance work, in order to
ensure the product is operational as long as possible.
Use for appropriate maintenance design (budgeting mainte-
nance and inspection fees, etc.).
Note 3
Life of humidifying element is about 3 years (4,000 hours),
under the supply water conditions of hardness: 150mg/l.
(Life of humidifying element is about 1 year (1,500 hours),
under the supply water conditions of hardness: 400mg/l.)
Annual operating hours: 10 hours/day × 26 days/
month × 5 month = 1,300 hours.
Contact your dealer for details.
Note: Breakage due to taking apart or cleaning inside by any-
one other than our authorized dealers may not be included in
the warranty.
Moving and discarding the unit
• Contact your dealer for removing and reinstalling the total
enthalpy heat exchanger when moving house since they
require technical expertise.
• This unit contains chlorofluorocarbon in the refrigent.
When discarding, removing linstalling and maintaining the
unit, collect the refrigent in accordance with the local law for
the global environmental destruction prevention.
In detail contact your dealer.
Where to call
For after-sales service, etc., consult with your dealer.
Warranty period:
Warranty period:
Within one year after
installation.
• If it is necessary to repair the air conditioner within the war-
ranty period, contact your dealer.
Name of Main Part
Inspection
Cycle
Maintenance Cycle
[replacements and/
or repairs]
Electric motor (fan,
damper, etc.)
1~2 months
recom-
mended *1
20,000 hours
PC boards
1 year
25,000 hours
Heat exchanger
element
10 years
Heat exchanger
5 years
Sensor (thermistor)
5 years
Remote controller and
switches
25,000 hours
Drain pan
8 years
Expansion valve
1 year *2
20,000 hours
Electromagnetic valve
1 year
20,000 hours
Name of Main Part
Inspection
Cycle
Replacement Cycle
Air filter
1 year
3 years
High efficiency filter
(Optional accessory)
1 year
Heat exchanger ele-
ment
2 years
10 years
Humidifier element
1 year
3 years (Note 3)
01_EN_3P130767-3G.fm Page 15 Monday, March 5, 2007 10:05 AM