When you want to start operation after a desired time has 
elapsed
Example:

Set the time to “8”.

” will display.

Starts operation 8 hours after the reservation is complete.
The reservation is cancelled after operation starts.

• Set the start time while the unit is stopped.
• The remaining time will count at the same time after reser-

vation is complete.

See the example below if you want to reserve “off after time” 
and “on after time” at the same time.

For example: (Refer to figure below)

When the timer is programmed to stop the system after 3 hours 
and start the system after 4 hours, the system will stop after 
3 hours and start 1 hour later.

Example:

• Setting “off after 3 hours” and “on after 4 hours” will

• Operation will stop after 3 hours.

Operation will then start in 1 hour from the time it stopped.

3.3.2 HOW TO PROGRAM AND SET THE TIMER WITH THE 

REMOTE CONTROLLER “BRC1D527” (Refer to figure 7)

• The controller is equipped with a schedule timer that 

enables the user to operate the installation automatically; 
setting the clock and day of the week is required to be able 
to use the schedule timer.

• To set up clock, refer to the operation manual of the remote 

controller.

Browse to Monday by pressing the “

” button.

The “

” icon appears,  “

” will blink and one of the  

” icons, one of the “

” 

icons might be displayed but all other fields remain blank, 
indicating that no actions are programmed for Monday.
Enter the program mode by holding down the  “

”  but-

ton for 5 seconds, the “

”  icon will now blink too.

Press the  “

”  button to activate the first programmed 

action. 
A blinking “ ” is displayed indicating that the first pro-
grammed action for Monday is being programmed; The 
set temperature and clock display are blinking.
Enter the time when the action must start using the 

” & “

” buttons (min. step = 10 minutes).

Press the “

”  button to display the next programmed 

action. If a second action is programmed for Monday,  

”  will still be blinking and “ 

” will appear. 

Assuming that 5 actions were programmed for Monday, a 
total of 5 presses will be required to display all pro-
grammed actions.
Enter the time when the action must stop using the 

” & “

” buttons (min. step = 10 minutes).

Press the “

” button. “

” icon displays.

This icon means the unit will stop at the set time.
When all data for the schedule timer actions for Monday 
are entered, you must confirm the programmed actions.
Make sure the last schedule timer action you want to 
keep is selected (schedule timer actions with a higher 
number will be deleted). 

Now you must choose between 2 options:

1. CONFIRM AND COPY TO NEXT DAY

The schedule timer action programmed for the current 
day are also valid for the next day: use the “confirm last 
action and copy actions to next day” function by pressing 
the “

” and “

” buttons simultaneously for 5 sec-

onds. “DAY OF THE WEEK INDICATOR” will change 
blinking from “

” to “

”.

2. CONFIRM ONLY

The schedule timer action programmed for the current 
day are only valid for the selected day: use the “confirm 
last action and go to next day” function by pressing the   

” button for 5 seconds.

Program mode is quit and depending on the choice 
made, the programmed actions are saved for Monday 
(and possibly Tuesday).

PROGRAMMING THE OTHER DAYS OF THE WEEK
Programming the other days of the week is identical to program-

ming the first day of the week. “

” is blinking to indicate the 

selected day, “

” and “ ” are steady if actions were copied 

from Monday to Tuesday, only “

” is displayed if no actions 

were copied from Monday to Tuesday.

NOTE) The schedule timer will not:

• control fan speed,
• control air flow direction,
• control ventilation mode,
• control ventilation amount,
• change the operation mode for a scheduled setpoint.

The parameters listed above can be set manually, without inter-
fering with the schedule timer.

3.4 OPTIMUM OPERATION

Observe the following precautions to ensure the system oper-
ates.

• When the display shows “

 ”, ask a qualified service 

person to clean the filters (Refer to MAINTENANCE).

• Do not operate the HRV unit in Bypass mode when the 

room air is under heating in winter or when the outside 
temperature is 30°C or higher.

This may cause condensation to form on the main unit or on 
discharge grill, or around air supply opening.

Keep the indoor unit and the remote controller at least 
1 m away from televisions, radios, stereos, and other 
similar equipments.

This may cause distorted picture or noise.

Turn off the main power supply switch when it is not 
used for long periods of time. When the main power 
switch is turned on, some watts of electricity is being 
used even if the system is not operating.

Turn off the main power supply switch for saving energy. 
When reoperating, turn on the main power supply switch 
6 hours before operation for smooth running.

8hr

1

2

3

3

4

5

6

7

8

01_EN_3P130767-3G.fm  Page 10  Monday, March 5, 2007  10:05 AM

Содержание VKM100GAMV1

Страница 1: ...ий OPERATION MANUAL Total Heat Exchanger HRV Heat Reclaim Ventilation with DX Coil MODELS Ceiling mounted duct type With DX coil Humidifier VKM50GAMV1 VKM80GAMV1 VKM100GAMV1 With DX coil VKM50GAV1 VKM80GAV1 VKM100GAV1 00_CV_3P130767 3G_01 fm Page 1 Wednesday March 7 2007 3 18 PM ...

Страница 2: ...e al condizionatore d aria per interni sistema VRVII di tipo M RXYQ REYQ RXQ È anche possibile utilizzare questa unità come sistema indipendente L unità non può controllare la temperatura del locale Se ciò è necessario non installare l unità HRV da sola ma invece installare un altra unità interna Per controllare l unità utilizzare il telecomando del condizionatore d aria interno a sistema VRVII HR...

Страница 3: ...e cover 6 Electric parts box 8 Heat exchanger elements 12 Gas pipe 13 Liquid pipe 16 Strainer included VKM GAMV1 series only VKM GAMV1 series only 14 Drain outlet 15 Humidifier Natural evaporating type 19 Remote controller Optional accessory 11 Direct expansion coil 9 Name plate 10 Air supply fan 4 Air filter Long life filter 5 Damper 21 EA Exhaust air to outdoors 22 OA Fresh air from outdoors out...

Страница 4: ...dent system HRV With DX Coil Remote controller for indoor unit Outdoor unit Remote controller for VRV BRC1A62 3 2 Remote controller for VRV BRC1A62 4 1 5 3 Remote controller for VKM BRC1D527 EU only 4 5 UNIT No GROUP Remote controller for VKM BRC1D527 EU only 4 1 2 3 2 00_CV_3P130767 3G_02 fm Page 2 Friday March 2 2007 6 37 PM ...

Страница 5: ... BRC1D527 EU only 1 2 3 6 1 Heat exchanger element 2 2 Handle 3 Rail 9 1 Air filter 8 2 8 1 3 10 11 12 1 3 2 Remote controller for VRV BRC1A62 7 6 7 UNIT No GROUP Remote controller for VKM BRC1D527 EU only 1 2 4 7 8 3 5 6 00_CV_3P130767 3G_02 fm Page 3 Friday March 2 2007 6 37 PM ...

Страница 6: ...ot including air filters etc Be sure to stop the unit and turn off the power when cleaning or inspecting it As the fan is rotating at high speed it will cause injury Never inspect or service the unit by yourself Ask a qualified service person to perform this work The qualified service person Keep all flames away if the refrigerant leaks The refrigerant in the air conditioner is safe and normally d...

Страница 7: ... When the HRV unit is to be installed in a small room it is necessary to take proper measures so that the amount of any leaked refrigerant does not exceed the limiting concen tration even when it leaks If the refrigerant leaks exceeding the level of limiting concentration an oxygen deficiency acci dent may happen Do not install the HRV unit at any place where flamma ble gas may leak out If the gas...

Страница 8: ...ditioner CHECK LIST CORRESPONDING TO OPERATING NOISE Is the unit installed at the following locations a Location strong enough to support the weight of the unit and which will not amplify noise or vibration b Location where the warm air and the noise from the outlet vent of the outdoor unit will not bother neighbors Are any obstructions near the outlet vent of the outdoor unit They may reduce the ...

Страница 9: ...tton for programming start and or stop time 18 Temperature setting button Use this button for setting the desired temperature of air conditioner combined with this unit This button can t use for this unit This unit can t change temperature setting 19 Filter sign reset button Refer to 4 1 HOW TO CLEAN THE AIR FILTER 20 Fan speed control button Press this button to select the fan speed of air condit...

Страница 10: ...sing the unit as an independent system Ask your dealer what kind of system your system is set up for before operation For the operation of the remote controller for indoor unit and centralized controller refer to the instruction manual provided with each unit See the included operating manuals for details on how to operate each remote control OPERATION for EACH SYSTEM Sample system Refer to figure...

Страница 11: ...t exchange mode VRV Fan mode HRV Heat exchange mode VRV Stopping HRV Heat exchange mode When air conditioner and HRV unit are not connected via duct Operation mode VRV Cooling mode HRV Heat exchange mode VRV Fan mode HRV Heat exchange mode When air conditioner and HRV unit are connected via duct Operation mode VRV Cooling mode HRV Heat exchange mode VRV Fan mode HRV Heat exchange mode VRV Stopping...

Страница 12: ...set for systems operating in cooling and heating at the same time is displayed on all remote controllers when using the VRVΙΙ system cooling only type but only and can be set Select the operating mode on a remote controller on which is not displayed and only for simultaneous cooling heat ing systems cannot be selected on remote controllers on which it is displayed See 3 2 if is displayed Press ven...

Страница 13: ...ues driv ing factory setting The purpose of this is to maintain the amount of ventilation and humidifying The change of the layout in the room should be examined when the cold draft from air supplying opening is feared Though the fan can be stopped by the setting of remote con troller Do not stop the fan in the place where no ventilation by stop ping the fan may cause the influence of diffusion of...

Страница 14: ...D SET THE TIMER WITH THE REMOTE CONTROLLER BRC1A62 Refer to figure 7 The timer is operated in the following two ways Programming the stop time The system stops operating after the set time has elapsed Programming the start time The system starts operating after the set time has elapsed The start and the stop time can be simultaneously pro grammed Press the timer mode start stop button several time...

Страница 15: ...ered you must confirm the programmed actions Make sure the last schedule timer action you want to keep is selected schedule timer actions with a higher number will be deleted Now you must choose between 2 options 1 CONFIRM AND COPY TO NEXT DAY The schedule timer action programmed for the current day are also valid for the next day use the confirm last action and copy actions to next day function b...

Страница 16: ...CESSARY Increase the frequency of cleaning if the unit is installed in a room where the air is etermely contaminated If the dirt becomes impossible to clean change the air filter Air filter for exchange is optional 1 Detach the maintenance cover Go into ceiling through the inspection hatch remove binding metal of maintenance cover and take it off Refer to figure 8 1 2 Detach the air filter Take ou...

Страница 17: ...oller does not display any error code Usage under that status will lead to insufficient humidification and increased tap water consumption The solenoid valve should be checked at the beginning of the heating season For dealers 4 5 INSPECTION OF THE FAN MOTER NOTE When the fan motor fails the remote controller does not dis play any error code Usage under that status will lead to insufficient ventil...

Страница 18: ...the power on The remote control buttons do not work well Measure Turn off the main power switch If the display INSPECTION UNIT No and the OPERATION lamp flash and the MALFUNCTION CODE appears Measure Notify and inform the model name and what the malfunction code indicates to your Daikin dealer There are other malfunctions Measure Stop the unit List of malfunction codes of Remote controller of the ...

Страница 19: ...board and other electric parts h Is the float switch broken Replace the float switch i Is the water supply pressure sufficient Re set it so that there is sufficient pressure j Is there foreign matter in the feed water tank Clean the feed water tank After sales service and warranty After sales service WARNING Do not modify the unit This may cause electric shock or fire Do not disassemble or repair ...

Страница 20: ... wear out parts The cycle is not the same as the warranty period Table 2 Replacement Cycle Lists Note 1 This table indicates main parts See the maintenance and inspection contract for details Note 2 This maintenance cycle indicates recommended lengths of time until the need arises for maintenance work in order to ensure the product is operational as long as possible Use for appropriate maintenance...

Страница 21: ...3P130767 3G EM05A069A 0704 HT 00_CV_3P130767 3G_01 fm Page 2 Wednesday March 7 2007 3 18 PM ...

Отзывы: