background image

9

English

HOW TO DESIGNATE THE MASTER REMOTE CONTROLLER

Press the operation mode selector button of the current 
master remote controller for 4 seconds.
The display showing“

” (changeover under 

controll) of all slave remote controllers connected to the 
same outdoor unit or BS unit flashes on.

• “

” flashes when the power is first turned on.

• The ventilation mode can be changed regardless of the set-

ting (main or slave).

NOTE

• This unit cannot control room temperature. If the unit is con-

nected to the same system with other indoor units, set the 
master remote controller on the other indoor units.

Press the operation mode selector button of the controller that 
you wish to designate as the master remote controller. Then 
designation is completed. This remote controller is designated 
as the master remote controller and the display showing 

” (changeover under control) vanishes.

The displays of other remote controller show 

” (changeover under control).

Press the operation mode selector button on the master 
remote controller (i.e. a remote controller which does not 
display “

”) to scroll through the modes.The 

display will scroll through “

” – “

” (only for simulta-

neous cooling/heating systems) – “

” – “

”.

The display on slave remote controllers will also change 
automatically.

„

Details and activity of operation

• Setting the master remote controller (without the 

” display) to cooling/heating mode will make 

slave remote controllers (with the “

” display) to 

follow to the mode of the master remote controller.
Selection of fan mode is possible, however.

• Setting the master remote controller (without the 

” display) to fan mode will make slave remote 

controllers (with the “

” display) any setting other 

than fan mode impossible.

3.3 PROGRAMMING START AND STOP OF THE 

SYSTEM WITH TIMER

3.3.1

HOW TO PROGRAM AND SET THE TIMER WITH THE 
REMOTE CONTROLLER “BRC1A62” (Refer to figure 7)

• The timer is operated in the following two ways. 

Programming the stop time “

”. The system stops 

operating after the set time has elapsed.

Programming the start time “

”. The system starts 

operating after the set time has elapsed.

• The start and the stop time can be simultaneously pro-

grammed.

Press the timer mode start/stop button “

” several 

times and select the mode on the display.

• For setting the timer stop “

• For setting the timer start “

Each time the button is pushed, the indication changes 
as shown below.

Press the programming time button and set the time for 
stopping or starting the system.

Each time this button is pressed, the time 
advances or goes backward by 1 hour.

• The timer can be programmed for a maximum of 72 hours.

• Each time when “

” is pushed, the time advances one hour.

Each time when “

” is pushed, the time goes back one hour.

Press the timer on/off button.
The timer setting procedure ends. The display 

” or “

” changes from flashing light to 

constant light.

• After the timer is programmed, the display shows the 

remaining time.

For cancelling the timer operation, push the timer on/off 
button “

” once again.

The indication disappears.

NOTE

• When setting the timer off and on at the same time, 

repeat the above procedure (from “

” to “

”) 

once again.

„

DETAIL EXPLANATION

When you want to stop operation after a desired time,
Example:

Set the time to “8”.

” will display.

Stops operation 8 hours after the reservation is complete.
The program will be cleared after the operation stops.

• Set the stop time during operation.

(Simultaneous cooling/heating systems)

If multiple indoor units or many 
of this unit are connected to 
outdoor unit via BS unit.

BS unit

HRV
-with DX coil-

One of these remote controllers can be 
designated as the master remote 
controller.

Indoor unit

BS unit:
This is the unit which 
selects cooling and 
heating.

1

2

3

1

“No indication”

2

3

1

3

8hr

01_EN_3P130767-3G.fm  Page 9  Monday, March 5, 2007  10:05 AM

Содержание VKM100GAMV1

Страница 1: ...ий OPERATION MANUAL Total Heat Exchanger HRV Heat Reclaim Ventilation with DX Coil MODELS Ceiling mounted duct type With DX coil Humidifier VKM50GAMV1 VKM80GAMV1 VKM100GAMV1 With DX coil VKM50GAV1 VKM80GAV1 VKM100GAV1 00_CV_3P130767 3G_01 fm Page 1 Wednesday March 7 2007 3 18 PM ...

Страница 2: ...e al condizionatore d aria per interni sistema VRVII di tipo M RXYQ REYQ RXQ È anche possibile utilizzare questa unità come sistema indipendente L unità non può controllare la temperatura del locale Se ciò è necessario non installare l unità HRV da sola ma invece installare un altra unità interna Per controllare l unità utilizzare il telecomando del condizionatore d aria interno a sistema VRVII HR...

Страница 3: ...e cover 6 Electric parts box 8 Heat exchanger elements 12 Gas pipe 13 Liquid pipe 16 Strainer included VKM GAMV1 series only VKM GAMV1 series only 14 Drain outlet 15 Humidifier Natural evaporating type 19 Remote controller Optional accessory 11 Direct expansion coil 9 Name plate 10 Air supply fan 4 Air filter Long life filter 5 Damper 21 EA Exhaust air to outdoors 22 OA Fresh air from outdoors out...

Страница 4: ...dent system HRV With DX Coil Remote controller for indoor unit Outdoor unit Remote controller for VRV BRC1A62 3 2 Remote controller for VRV BRC1A62 4 1 5 3 Remote controller for VKM BRC1D527 EU only 4 5 UNIT No GROUP Remote controller for VKM BRC1D527 EU only 4 1 2 3 2 00_CV_3P130767 3G_02 fm Page 2 Friday March 2 2007 6 37 PM ...

Страница 5: ... BRC1D527 EU only 1 2 3 6 1 Heat exchanger element 2 2 Handle 3 Rail 9 1 Air filter 8 2 8 1 3 10 11 12 1 3 2 Remote controller for VRV BRC1A62 7 6 7 UNIT No GROUP Remote controller for VKM BRC1D527 EU only 1 2 4 7 8 3 5 6 00_CV_3P130767 3G_02 fm Page 3 Friday March 2 2007 6 37 PM ...

Страница 6: ...ot including air filters etc Be sure to stop the unit and turn off the power when cleaning or inspecting it As the fan is rotating at high speed it will cause injury Never inspect or service the unit by yourself Ask a qualified service person to perform this work The qualified service person Keep all flames away if the refrigerant leaks The refrigerant in the air conditioner is safe and normally d...

Страница 7: ... When the HRV unit is to be installed in a small room it is necessary to take proper measures so that the amount of any leaked refrigerant does not exceed the limiting concen tration even when it leaks If the refrigerant leaks exceeding the level of limiting concentration an oxygen deficiency acci dent may happen Do not install the HRV unit at any place where flamma ble gas may leak out If the gas...

Страница 8: ...ditioner CHECK LIST CORRESPONDING TO OPERATING NOISE Is the unit installed at the following locations a Location strong enough to support the weight of the unit and which will not amplify noise or vibration b Location where the warm air and the noise from the outlet vent of the outdoor unit will not bother neighbors Are any obstructions near the outlet vent of the outdoor unit They may reduce the ...

Страница 9: ...tton for programming start and or stop time 18 Temperature setting button Use this button for setting the desired temperature of air conditioner combined with this unit This button can t use for this unit This unit can t change temperature setting 19 Filter sign reset button Refer to 4 1 HOW TO CLEAN THE AIR FILTER 20 Fan speed control button Press this button to select the fan speed of air condit...

Страница 10: ...sing the unit as an independent system Ask your dealer what kind of system your system is set up for before operation For the operation of the remote controller for indoor unit and centralized controller refer to the instruction manual provided with each unit See the included operating manuals for details on how to operate each remote control OPERATION for EACH SYSTEM Sample system Refer to figure...

Страница 11: ...t exchange mode VRV Fan mode HRV Heat exchange mode VRV Stopping HRV Heat exchange mode When air conditioner and HRV unit are not connected via duct Operation mode VRV Cooling mode HRV Heat exchange mode VRV Fan mode HRV Heat exchange mode When air conditioner and HRV unit are connected via duct Operation mode VRV Cooling mode HRV Heat exchange mode VRV Fan mode HRV Heat exchange mode VRV Stopping...

Страница 12: ...set for systems operating in cooling and heating at the same time is displayed on all remote controllers when using the VRVΙΙ system cooling only type but only and can be set Select the operating mode on a remote controller on which is not displayed and only for simultaneous cooling heat ing systems cannot be selected on remote controllers on which it is displayed See 3 2 if is displayed Press ven...

Страница 13: ...ues driv ing factory setting The purpose of this is to maintain the amount of ventilation and humidifying The change of the layout in the room should be examined when the cold draft from air supplying opening is feared Though the fan can be stopped by the setting of remote con troller Do not stop the fan in the place where no ventilation by stop ping the fan may cause the influence of diffusion of...

Страница 14: ...D SET THE TIMER WITH THE REMOTE CONTROLLER BRC1A62 Refer to figure 7 The timer is operated in the following two ways Programming the stop time The system stops operating after the set time has elapsed Programming the start time The system starts operating after the set time has elapsed The start and the stop time can be simultaneously pro grammed Press the timer mode start stop button several time...

Страница 15: ...ered you must confirm the programmed actions Make sure the last schedule timer action you want to keep is selected schedule timer actions with a higher number will be deleted Now you must choose between 2 options 1 CONFIRM AND COPY TO NEXT DAY The schedule timer action programmed for the current day are also valid for the next day use the confirm last action and copy actions to next day function b...

Страница 16: ...CESSARY Increase the frequency of cleaning if the unit is installed in a room where the air is etermely contaminated If the dirt becomes impossible to clean change the air filter Air filter for exchange is optional 1 Detach the maintenance cover Go into ceiling through the inspection hatch remove binding metal of maintenance cover and take it off Refer to figure 8 1 2 Detach the air filter Take ou...

Страница 17: ...oller does not display any error code Usage under that status will lead to insufficient humidification and increased tap water consumption The solenoid valve should be checked at the beginning of the heating season For dealers 4 5 INSPECTION OF THE FAN MOTER NOTE When the fan motor fails the remote controller does not dis play any error code Usage under that status will lead to insufficient ventil...

Страница 18: ...the power on The remote control buttons do not work well Measure Turn off the main power switch If the display INSPECTION UNIT No and the OPERATION lamp flash and the MALFUNCTION CODE appears Measure Notify and inform the model name and what the malfunction code indicates to your Daikin dealer There are other malfunctions Measure Stop the unit List of malfunction codes of Remote controller of the ...

Страница 19: ...board and other electric parts h Is the float switch broken Replace the float switch i Is the water supply pressure sufficient Re set it so that there is sufficient pressure j Is there foreign matter in the feed water tank Clean the feed water tank After sales service and warranty After sales service WARNING Do not modify the unit This may cause electric shock or fire Do not disassemble or repair ...

Страница 20: ... wear out parts The cycle is not the same as the warranty period Table 2 Replacement Cycle Lists Note 1 This table indicates main parts See the maintenance and inspection contract for details Note 2 This maintenance cycle indicates recommended lengths of time until the need arises for maintenance work in order to ensure the product is operational as long as possible Use for appropriate maintenance...

Страница 21: ...3P130767 3G EM05A069A 0704 HT 00_CV_3P130767 3G_01 fm Page 2 Wednesday March 7 2007 3 18 PM ...

Отзывы: