Note for Multi System

〈〈 

What is a “Multi System”? 

〉〉

This system has one outdoor unit connected to multiple indoor units.

„

Selecting the Operation Mode

1. With the Priority Room Setting 

present but inactive or not present.

When more than one indoor unit is operating, priority is 
given to the first unit that was turned on. 
In this case, set the units that are turned on later to the 
same operation mode (*1) as the first unit.
Otherwise, they will enter the Standby Mode, and the operation lamp will flash; this does not indicate malfunction.

(*1)

• COOL, DRY and FAN mode may be used at the same time.
• AUTO mode automatically selects COOL mode or HEAT mode based on the room temperature.

Therefore, AUTO mode is available when selecting the same operation mode as that of the room 
with the first unit to be turned on.

CAUTION

Normally, the operation mode in the room where the unit is first run is given priority, but the following situations are 
exceptions, so please keep this in mind.
If the operation mode of the first room is 

FAN Mode

, then using 

Heating Mode

 in any room after this will give priority to 

heating.

 In this situation, the air conditioner running in FAN Mode will go on standby, and the operation lamp will flash.

2. With the Priority Room Setting active.

See “Priority Room Setting” on the next page.

„

NIGHT QUIET Mode (Available only for cooling operation)

NIGHT QUIET Mode requires initial programming during installation. Please consult your retailer or dealer for assistance.
NIGHT QUIET Mode reduces the operation noise of the outdoor unit during the night time hours to prevent 
annoyance to neighbors.

• The NIGHT QUIET Mode is activated when the temperature drops 5

°

C or more below the highest temperature 

recorded that day. Therefore, when the temperature difference is less than 5

°

C, this function will not be activated.

• NIGHT QUIET Mode reduces slightly the cooling efficiency of the unit.

„

OUTDOOR UNIT QUIET Operation 

(page 18.)

1. With the Priority Room Setting present but inactive or not present.

When using the OUTDOOR UNIT QUIET operation feature with the Multi system, set all indoor units to 
OUTDOOR UNIT QUIET operation using their remote controllers.
When clearing OUTDOOR UNIT QUIET operation, clear one of the operating indoor units using their remote controller.
However OUTDOOR UNIT QUIET operation display remains on the remote controller for other rooms.
We recommend you release all rooms using their remote controllers.

2. With the Priority Room Setting active.

See “Priority Room Setting” on the next page.

„

Cooling / Heating Mode Lock (Available only for heat pump models)

The Cooling / Heating Mode Lock requires initial programming during installation.Please consult your retailer or dealer 
for assistance. The Cooling / Heating Mode Lock sets the unit forcibly to either Cooling or Heating Mode. This function 
is convenient when you wish to set all indoor units connected to the Multi system to the same operation mode.

C

room

B

room

A

room

Living

room

Outdoor
unit

01_EN_3P207037-2D.fm  Page 22  Friday, March 13, 2009  9:39 AM

Содержание Super Multi NX ATXS20G2V1B

Страница 1: ...ran ais Nederlands Espa ol Italiano Portugues MODELS DAIKIN ROOM AIR CONDITIONER Operation Manual ATXS20G2V1B ATXS25G2V1B ATXS35G2V1B ATXS42G2V1B ATXS50G2V1B 00_CV_3P207037 2D fm Page 1 Wednesday Marc...

Страница 2: ...ation 10 Adjusting the Airflow Direction 12 COMFORT AIRFLOW Operation 14 INTELLIGENT EYE Operation 15 POWERFUL Operation 17 OUTDOOR UNIT QUIET Operation 18 ECONO Operation 19 TIMER Operation 20 Note f...

Страница 3: ...tempt to install the air conditioner by your self Incorrect work will result in water leakage electric shocks or fire For installation consult the dealer or a qualified technician In order to avoid el...

Страница 4: ...for small animals which can enter the unit Once in the unit such animals can cause malfunc tions smoke or fire when making contact with electrical parts Do not operate the air conditioner with wet ha...

Страница 5: ...4 Names of parts Indoor Unit 16 14 13 15 12 1 3 4 5 7 9 11 10 8 6 2 01_EN_3P207037 2D fm Page 4 Friday March 13 2009 9 39 AM...

Страница 6: ...ush this switch once to start operation Push once again to stop it The operation mode refers to the following table This switch is useful when the remote controller is missing 13 Operation lamp green...

Страница 7: ...QUIET button OUTDOOR UNIT QUIET operation page 18 9 FAN setting button It selects the airflow rate setting 10 SWING button Ajusting the Airflow Direction page 12 11 SWING button Louvers vertical blade...

Страница 8: ...long time take the batteries out The batteries will last for approximately one year If the remote controller display begins to fade and the degradation of reception performance occurs within a year h...

Страница 9: ...location with the screws procured locally 3 Place the remote controller in the remote controller holder ATTENTION About remote controller Never expose the remote controller to direct sunlight Dust on...

Страница 10: ...for a long period for example in spring or autumn turn the breaker OFF Use the air conditioner in the following conditions The operation of the system outside the above humidity or temperature range m...

Страница 11: ...COOL HEAT FAN 2 Press ON OFF button The OPERATION lamp lights up To stop operation 3 Press ON OFF button again Then OPERATION lamp goes off To change the temperature setting 4 Press TEMPERATURE adjus...

Страница 12: ...eration to take away the frost During defrosting operation hot air does not flow out of indoor unit A pinging sound may be heard during defrosting operation which however does not mean that the air co...

Страница 13: ...ition press SWING button once more The flaps will stop moving disappears from the LCD To adjust the vertical blades louvers 3 Press SWING button is displayed on the LCD 4 When the louvers have reached...

Страница 14: ...r which tends to collect near the ceiling throughout the room preventing areas of cold and hot developing ATTENTION Always use a remote controller to adjust the angles of the flaps and louvers If you...

Страница 15: ...Notes on COMFORT AIRFLOW Operation The flap position will change preventing air from blowing directly on the occupants of the room POWERFUL operation and COMFORT AIRFLOW operation cannot be used at th...

Страница 16: ...LLIGENT EYE operation 2 Press COMFORT SENSOR button Press the button to select Blank EX TEMP ON OFF POWERFUL MODE FAN QUIET SWING SENSOR COMFORT ECONO TIMER ON CANCEL OFF R 1 2 Blank Somebody back in...

Страница 17: ...assersby temperature range etc The sensor also mistakenly detects pets sunlight fluttering curtains and light reflected off of mirrors as passersby INTELLIGENT EYE operatipon will not go on during pow...

Страница 18: ...t POWERFUL Operation can only be set when the unit is running Pressing the operation stop button causes the settings to be canceled and the disappears from the LCD POWERFUL operation will not increase...

Страница 19: ...e OUTDOOR UNIT QUIET operation is set on all operated indoor units However if using priority room setting see Note for multi system page 22 This function is available in COOL HEAT and AUTO modes This...

Страница 20: ...the disappears from the LCD ECONO operation is a function which enables efficient operation by limiting the power consumption of the outdoor unit operating frequency ECONO operation functions in AUTO...

Страница 21: ...ton again The TIMER lamp lights up To cancel the OFF TIMER operation 4 Press CANCEL button The TIMER lamp goes off NOTE When TIMER is set the present time is not displayed Once you set ON OFF TIMER th...

Страница 22: ...IMER lamp lights up To cancel ON TIMER operation 4 Press CANCEL button The TIMER lamp goes off To combine ON TIMER and OFF TIMER A sample setting for combining the two timers is shown below ATTENTION...

Страница 23: ...n Please consult your retailer or dealer for assistance NIGHT QUIET Mode reduces the operation noise of the outdoor unit during the night time hours to prevent annoyance to neighbors The NIGHT QUIET M...

Страница 24: ...s POWERFUL operation operation capacity will be concentrated in Room A In such a case the cooling heating efficiency of the units in Rooms B C and D may be slightly reduced 3 Priority when using OUTDO...

Страница 25: ...and push them in all the way Close the front panel slowly and push the panel at the 3 points 1 on each side and 1 in the middle CAUTION Units Don t touch the metal parts of the indoor unit If you touc...

Страница 26: ...hinned with lukewarm water then dry them up in the shade It is recommended to clean the air filters every two weeks Titanium Apatite Photocatalytic Air Purifying Filter The Titanium Apatite Photocatal...

Страница 27: ...shop there you bought the air conditioner Dispose of the old filter as non flammable waste Check that the base stand and other fittings of the outdoor unit are not decayed or corroded Check that noth...

Страница 28: ...airflow during cooling operation The indoor unit gives out odour This happens when smells of the room furniture or cigarettes are absorbed into the unit and discharged with the airflow If this happen...

Страница 29: ...the outdoor units Clean the air filters or take all obstacles away and turn the breaker OFF Then turn it ON again and try operating the air conditioner with the remote controller If the lamp still fla...

Страница 30: ...quences for the environment and human health Please contact the installer or local authority for more information In certain operating conditions the inside of the air conditioner may get foul after s...

Страница 31: ...UNIT EA COOLING HEATING SWITCHING ERROR E1 CIRCUIT BOARD FAULT E5 OL STARTED E6 FAULTY COMPRESSOR START UP E7 DC FAN MOTOR FAULT E8 OVERCURRENT INPUT F3 HIGH TEMPERATURE DISCHARGE PIPE CONTROL F6 HIG...

Страница 32: ...AND BY UNIT OVERLOAD RELAY WORKED OR HIGH DISCHARGE PIPE TEMPERATURE FAULTY COMPRESSOR START INPUT OVERCURRENT THERMISTOR OR CT ABNORMALITY HIGH TEMPERATURE SWITCHBOX HIGH TEMPERATURE AT INVERTER CIRC...

Страница 33: ...32 MEMO 01_EN_3P207037 2D fm Page 32 Friday March 13 2009 9 39 AM...

Страница 34: ...0903 HT M07B015B Two dimensional bar code is a code for manufacturing 3P207037 2D 00_CV_3P207037 2D fm Page 2 Wednesday March 11 2009 9 15 AM...

Отзывы: