Components
Service manual
108
(A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D +
(A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C +
(A)RXF20~42D + (A)RXF20~42E
Split Sensira R32
ESIE18-12G – 2023.01
2
Check that all wires are properly connected and that all connectors are fully
plugged‑in.
3
Check that no connectors or wires are damaged.
4
Check that the wiring corresponds with the wiring diagram, see
169].
INFORMATION
Correct the wiring as needed.
Is the problem solved?
Action
Yes
No further actions required.
No
continue with the next procedure.
To check the fuse of the main PCB
Prerequisite:
First perform all earlier main PCB checks, see
1
Measure the continuity of the fuse. If no continuity is measured, the fuse has
blown.
c a
b
a
Fuse F1U
b
Fuse F2U
c
Fuse F3U
Blown fuse on the main PCB?
Action
Yes
No
and continue with the next procedure.
To check the rectifier voltage of the main PCB
Prerequisite:
First perform all earlier main PCB checks, see
1
Turn ON the power of the unit.