Components
Service manual
64
(A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D +
(A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C +
(A)RXF20~42D + (A)RXF20~42E
Split Sensira R32
ESIE18-12G – 2023.01
a
a
Compressor wire terminals cover
13
If applicable, connect the ground wire to the compressor. Install and tighten
the screw to fix the ground wire.
14
Install the following thermistors in their holder:
▪
Suction thermistor
▪
Discharge pipe thermistor
▪
Compressor body thermistor (if applicable)
15
Install the compressor insulation, see
16
17
Add
refrigerant
to
the
refrigerant
circuit,
see
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
3.3 Compressor thermal protector
3.3.1 Checking procedures
To perform a mechanical check of the compressor thermal protector
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
124].
Prerequisite:
Remove the compressor insulation.
1
Remove the cover of the compressor wire terminals.