Installation of indoor unit
RZR-P, RZQ-P(9)
193
3PN14093-12A
English
7
CAUTION
• Use the level and check that the unit is installed horizontally.
(4-directions)
• In the case of using a vinyl tube (filled with water) in place of
the level, align the bottom of the unit to the water surface at
both edges of the vinyl tube to make levelness adjustment.
If the unit is installed at a slant with the drain pipe side set
high, in particular, the float switch will not operate normally
and water leakage may result.
6.
REFRIGERANT PIPING WORK
〈
As for the refrigerant piping of the outdoor unit, refer to the
installation manual provided to the outdoor unit.
〉
〈
Perform heat insulation work on both gas piping and liquid
piping, or otherwise water leakage may result.
〉
〈
Use the insulation material that withstands a temperature
of 250°F.
〉
〈
Reinforce the insulation material for the refrigerant piping if
the ambient temperature is high, or otherwise dew conden-
sation may result on the surface of the insulation material.
〉
〈
Make sure that the refrigerant is R410A before refrigerant
piping work. If the refrigerant is different, the air condi-
tioner will not operate normally.
〉
CAUTION
This product uses new refrigerant (R410A) only. Be sure to
keep the following items and conduct the installation work.
• Use a dedicated pipe cutter and flare tool for R410A.
• When connecting the flare, apply ether oil or ester oil
only to inner side of the flare.
• Be sure to use the flare nut provided with the unit. (Do
not use a different flare nut (such as a type-1 flare nut),
or otherwise refrigerant leakage may result.)
• Perform the curing of the piping with pinching or taping
of the piping in order to prevent the intrusion of dirt, dust,
and moisture into the piping.
CAUTION
• Be sure to use the specified type of refrigerant for the
refrigeration cycle and do not contaminate the refrigerant
with air.
• Ventilate the room in case of refrigerant leakage during
installation work.
(1) Connect the piping.
• The outdoor unit is filled with refrigerant.
•
W
hen connecting or disconnecting piping to or from the
unit,
be sure to use a spanner and a torque wrench.
(Refer to Fig. 4)
• Refer to Table 1 for the processing dimensions of the
flare.
• Use the flare nut provided with the unit.
•
Apply ether oil or ester oil only to inner side of the
flare
and screw in the flare nut three to four turns first by
hand at the time of connecting the flare nut.
(Refer to Fig. 5)
• Refer to Table 1 for the corresponding tightening torque.
Table 1
CAUTION
• Do not excessively tighten the flare nut.
Doing so will break the flare nut and refrigerant leakage may
result.
• Make sure that all parts around the flare are free of oil.
The drain pan and the resin part may be deteriorated if oil is
attached.
• If no torque wrenches are available, refer to Table 2 as a
standard.
W
hen the flare nut is tightened with the spanner, the
tightening torque should increase suddenly. Tighten the
flare nut further for the corresponding angle shown in
Table 2.
Pipe
size
Tightening torque
Flare
dimensions
A (in.)
Flare shape
φ
1/4
10.4 – 12.7 lbf·ft
0.342 – 0.358
φ
3/8
24.1 – 29.4 lbf·ft
0.504 – 0.520
φ
1/2
36.5 – 44.5 lbf·ft
0.638 – 0.654
φ
5/8
45.6 – 55.6 lbf·ft
0.760 – 0.776
Torque wrench
Spanner
Piping union
Flare nut
Fig. 4
Fig. 5
Apply ester oil or ether oil
only to inner side of flare.
A
45
0
±2
0
R0.016-0.031
90
0
± 2
0
Содержание SkyAir RZQ-P Series
Страница 1: ...Cooling Only 60Hz Heat Pump 60Hz RZR P RZQ P 9 series EDUS281120_a AMERICAS ...
Страница 31: ...Dimensions and service space EDUS281120_a 30 RZR P RZQ P 9 BRC2A71 Unit in 3D047341 ...
Страница 33: ...Dimensions and service space EDUS281120_a 32 RZR P RZQ P 9 BRC7E818 for FAQ 3D049736 Unit in ...
Страница 34: ...EDUS281120_a Dimensions and service space RZR P RZQ P 9 33 BRC4C82 for FBQ 3D049611 Unit in ...
Страница 38: ...EDUS281120_a Dimensions and service space RZR P RZQ P 9 37 3D064213A ...
Страница 39: ...Dimensions and service space EDUS281120_a 38 RZR P RZQ P 9 3D064213A ...
Страница 40: ...EDUS281120_a Dimensions and service space RZR P RZQ P 9 39 RZR36PVJU RZR42PVJU RZQ36PVJU9 RZQ42PVJU9 3D047381B ...
Страница 41: ...Dimensions and service space EDUS281120_a 40 RZR P RZQ P 9 3D047381B ...
Страница 46: ...EDUS281120_a Wiring diagrams RZR P RZQ P 9 45 FHQ18PVJU FHQ24PVJU FHQ30PVJU FHQ36MVJU FHQ42MVJU 3D048116A ...
Страница 47: ...Wiring diagrams EDUS281120_a 46 RZR P RZQ P 9 FAQ18PVJU FAQ24PVJU 3D046039D ...
Страница 50: ...EDUS281120_a Wiring diagrams RZR P RZQ P 9 49 RZR36PVJU RZR42PVJU RZQ36PVJU9 RZQ42PVJU9 C 3D071178 ...
Страница 61: ...Safety devices list EDUS281120_a 60 RZR P RZQ P 9 8 3 FAQ FAQ18PVJU FAQ24PVJU 4D047085B ...
Страница 91: ...Capacity tables EDUS281120_a 90 RZR P RZQ P 9 RZR36PVJU RZR42PVJU 3D071685 ...
Страница 92: ...EDUS281120_a Capacity tables RZR P RZQ P 9 91 RZQ36PVJU9 RZQ42PVJU9 C 3D047383B ...
Страница 100: ...EDUS281120_a Sound Levels Reference RZR P RZQ P 9 99 FCQ30PAVJU FCQ36PAVJU FCQ42PAVJU L HH H L HH H L HH H ...
Страница 101: ...Sound Levels Reference EDUS281120_a 100 RZR P RZQ P 9 FBQ18PVJU FBQ24PVJU FBQ30PVJU FBQ36PVJU ...
Страница 102: ...EDUS281120_a Sound Levels Reference RZR P RZQ P 9 101 FBQ42PVJU ...
Страница 104: ...EDUS281120_a Sound Levels Reference RZR P RZQ P 9 103 RZQ42PVJU9 RZR42PVJU 4D072769 ...
Страница 111: ...Center of gravity EDUS281120_a 110 RZR P RZQ P 9 FBQ18PVJU FBQ24PVJU FBQ30PVJU FBQ36PVJU FBQ42PVJU C 4D065975A Unit in ...
Страница 113: ...Center of gravity EDUS281120_a 112 RZR P RZQ P 9 RZR36PVJU RZR42PVJU RZQ36PVJU9 RZQ42PVJU9 4D065352A Unit in ...