English
5
Points for explanation about operations
3. NOTE TO THE INSTALLER
Be sure to instruct customers how to properly operate the unit (especially cleaning filters, operating different func-
tions, and adjusting the temperature) by having them carry out operations themselves while looking at the manual.
3. SELECTING INSTALLATION SITE
Please attach additional thermal insulation material to the unit body when it is believed that the relative humid-
ity in the ceiling exceeds 80%. Use glass wool, polyethylene foam, or similar with a thickness of 10 mm or
more as thermal insulation material.
The direction of air discharge for this product can be selected. Sealing Member of air discharge outlet is avail-
able option for 4-way with sealed corners, and 3-way.
(1) Select an installation site where the following conditions are fulfilled and that meets your customer’s approval.
•
Where optimum air distribution can be ensured.
•
Where nothing blocks air passage.
•
Where condensate can be properly drained.
•
Where the ceiling is strong enough to bear the indoor unit weight.
•
Where the false ceiling is not noticeably on an incline.
•
Where sufficient clearance for maintenance and service can be ensured.
•
Where there is no risk of flammable gas leakage.
•
Where piping between indoor and outdoor units is possible within the allowable limit.
(Refer to the installation manual for the outdoor unit.)
[Space required for installation]
CAUTION
•
Any vents, light fixtures, or other appliances which may disturb the airflow might cause the top side to
become dirty if located too nearby, so follow Fig. 2 when installing.
•
Keep indoor unit, outdoor unit, power supply wiring and transmission wiring at least 1 meter away from
televisions and radios. This is to prevent image interference and noise in those electrical appliances.
(Noise may be generated depending on the conditions under which the electric wave is generated, even
if 1 meter is kept.)
(2) Ceiling height
•
This indoor unit may be installed on ceilings up to 3.5 m (Type 100·125·140: 4.2 m) in height. However,
it becomes necessary to make field settings by remote controller and close the air outlet when installing
the unit at a height over
2.7 m (Type 100·125·140: 3.2 m).
Refer to the section entitled, ‘‘11. FIELD SETTING’’ and the decoration panel installation manual.
The items with
WARNING and
CAUTION marks in the instruction manual are the items per-
taining to possibilities for bodily injury and material damage in addition to the general usage of
the product. Accordingly, it is necessary that you make a full explanation about the described con-
tents and also ask your customers to read the instruction manual.
Air
inlet
Air
discharge
Air
discharge
Floor surface
At least
1800 mm
from a floor
298 mm
Indoor
u
nit
Indoor
u
nit
*At least
1500 mm
from a
w
all
(
N
OTE)
(
N
OTE)
Lighting
Air fan
At least 1500 mm
from an
y fixt
u
re
At least
1500 mm
At least 2000 mm
At least 4000 mm
Fig. 2
Fig. 1