26
English
*After turning on the power, the maximum is 90 seconds, although it will only display “88”. This is not a
problem, and it will be set for 90 seconds.
■
Trouble shooting with the display on the liquid crystal display remote controller.
1.
With the wired remote controller. (NOTE 1)
When the operation stops due to trouble, operation lamp flashed, and “
” and the Malfunction code are
indicated on the liquid crystal display. In such a case, diagnose the fault contents by referring to the table
on the Malfunction code list it case of group control, the unit No. is displayed so that the indoor unit no with
the trouble can be recognized. (NOTE 2)
2.
With the wireless remote controller.
(Refer also to the operation manual attached to the wireless remote controller)
When the operation stops due to trouble. the display on the indoor unit flashes. In such a case, diagnose
the fault contents with the table on the Malfunction code list looking for the Malfunction code which can be
found by following procedures. (NOTE 2)
(1)
Press the INSPECTION /TEST OPERATION button, “
” is displayed and “ 0 ” flashes.
(2)
Press the PROGRAMMING TIME button and find the unit No. which stopped due to trouble.
Number of beeps 3 short beeps ............ Perform all the following operations
1 short beep .............. Perform (3) and (6)
1 long beep ............... No trouble
(3)
Press the OPERATION MODE SELECTOR button and upper figure of the Malfunction code flashes.
(4)
Continue pressing the PROGRAMMING TIME button unit it makes 2 short beeps and find the upper code.
(5)
Press the Operation selector button and lower figure of the Malfunction code flashes.
(6)
Continue pressing the PROGRAMMING TIME button unit it makes a long beep and find the lower code.
•
A long beep indicate the Malfunction code.
NOTE
1.
In case wired remote controller. Press the INSPECTION /TEST OPERATION button on remote controller,
“
” starts flashing and changes the inspection mode.
2.
Keep down the ON/OFF button for 5 seconds or longer in the inspection mode and the above trouble his-
tory disappears, after the trouble code goes on and off twice, followed by the code “00”(normal).
The display changes from the inspection mode to the normal mode.