![Daikin SkyAir GQI-Eco FCQG100EVEB Скачать руководство пользователя страница 6](http://html1.mh-extra.com/html/daikin/skyair-gqi-eco-fcqg100eveb/skyair-gqi-eco-fcqg100eveb_installation-manual_2460091006.webp)
4
English
2. OPTIONAL ACCESSORIES
•
The optional decoration panel and remote controller are required for this indoor unit. (Refer to Table 1, 2)
•
Check that the decoration panel is prepared.
(For the installation of the decoration panel, refer to the installation manual attached to the decoration
panel.)
Table 1
•
Remote controllers: Select a remote controller from Table 2 according to customer request and install in an
appropriate place.
Table 2
FOR THE FOLLOWING ITEMS, TAKE SPECIAL CARE DURING CONSTRUCTION AND
CHECK AFTER INSTALLATION IS FINISHED.
1. Items to be checked after completion of work
2. Items to be checked at time of delivery
* Also review the ‘‘1. SAFETY PRECAUTIONS’’
Unit model
Optional decoration panel
FCQG71·100·125·140EVEB
BYCP125B-W1
Color : White
Remote controller
Wired type
BRC1E51A7/BRC1D528
Items to be checked
If not properly done, what is likely to occur
Check
Are the indoor unit and outdoor unit fixed firmly?
The unit may drop, vibrate or make noise.
Is the installation of the indoor unit and the
outdoor unit completed?
The unit may malfunction or the components
burn out.
Is the gas leak test finished?
It may result in insufficient cooling.
Is the unit fully insulated?
Condensate water may drip.
Does drainage flow smoothly?
Condensate water may drip.
Does the power supply voltage correspond
to that shown on the name plate?
The unit may malfunction or the components
burn out.
Are wiring and piping correct?
The unit may malfunction or the components burn out.
Is the unit safely grounded?
It may result in electric shock.
Is wiring size according to specifications?
The unit may malfunction or the components burn out.
Is something blocking the air outlet or inlet
of either the indoor or outdoor units?
It may result in insufficient cooling.
Are refrigerant piping length and additional
refrigerant charge noted down?
The refrigerant charge in the system is not clear.
Items to be checked
Check
Has the field setting done (as necessary)?
Did you attach the control box lid, the air filter, and suction grille?
Does the cold air (warm air) blow properly during the cooling (heating) operation?
Did you explain about operations while showing the instruction manual to your customer?
Did you hand the instruction manual over to your customer?
Содержание SkyAir GQI-Eco FCQG100EVEB