1. When using 1 remote controller (Normal operation)
L
1
L
2
IN/D OUT/D
F1 F2 F1 F2
P
1
P
2
P
1
P
2
F
1
F
2
T
1
T
2
Control box
Power Supply
208/230V
1~ 60Hz
Outdoor unit
Indoor unit
Remote
controller
L
1
L
2
Fig. 25
2. When using 2 remote controllers
Fig. 26
P
1
P
2
P
1
P
2
L
1
L
2
IN/D OUT/D
F1 F2 F1 F2
P
1
P
2
F
1
F
2
T
1
T
2
Control box
For use with
2 remote
controllers
Power Supply
208/230V
1~ 60Hz
Outdoor unit
Indoor unit
L
1
L
2
[ PRECAUTIONS ]
1.
Do not ground the equipment on gas pipes, water pipes
or lightning rods, or crossground with telephones.
Improper grounding could result in electric shock.
2.
The remote controller wiring (P¹ and P²) and transmis-
sion wiring (F¹ and F²) have no polarity.
8-3
CONTROL BY 2 REMOTE
CONTROLLERS (Controlling 1 indoor unit by 2
remote controllers)
•
When using 2 remote controllers, one must be set to
“MAIN” and the other to “SUB”.
〈
Main/sub changeover
〉
•
Refer to the installation manual supplied with the remote
controller.
〈
Wiring method
〉
(1)
Remove the control box cover.
(2) Add the remote controller 2 (SUB) to the terminal block
for remote controller (P¹, P²
) in the control box. (There is
no polarity.)
Remote controller wiring
terminal block
Remote
controller 2
(SUB)
Remote
controller 1
(MAIN)
1
P
2
P
1
F
2
F
1
T
2
T
FORCED
OFF
REMOTE
CONTRL
TRANSMISSION
WIRING
Fig. 27
8-4
REMOTE CONTROL (FORCED OFF AND ON/
OFF OPERATION)
•
Connect input lines from the outside to the terminals T¹
and T² on the terminal block (6P) for remote controller to
achieve remote control.
•
See “
9. FIELD SETTING
” for details on operation.
Input A
1
P
2
P
1
F
2
F
1
T
2
T
FORCED
OFF
REMOTE
CONTRL
TRANSMISSION
WIRING
Fig. 28
Wire specification
Sheathed vinyl cord or 2 core cable
Gauge
AWG18 – 16 (0.75-1.25 mm
2
)
Length
Max. 328 ft. (100 m)
External terminal
Contact that can ensure the minimum
applicable load of 15 V DC, 1 mA.
8-5
CENTRALIZED CONTROL
•
For centralized control, it is necessary to designate the
group No. For details, refer to the manual of each optional
controllers for centralized control.