Daikin SkyAir FAQ18TAVJU Скачать руководство пользователя страница 12

11

English

8. 

WIRING EXAMPLE AND HOW TO SET 
THE REMOTE CONTROLLER

8-1 

HOW TO CONNECT WIRINGS

 

Conduit for power supply wiring 
Unscrew and remove the conduit mounting plate from the 

control box. 

(Refer to Fig. 20)

 

Fix a conduit to the plate with a lock nut and reattach them 

at original position.

Control box

Refrigerant 
piping 

Conduit

Lock nut

Conduit mounting 
plate

Screw 

Fig. 20

<Back side>

<Front side>

 

Power supply wiring and ground wiring 

Unscrew and remove the control box cover.

 

Thread the power supply wiring and ground wiring through 
the included insulating tube (short) (7) and secure them 
with the included clamp (small) (5). 

(Refer to Fig. 21)

 

Connect the power supply wiring and ground wiring to the 
power supply terminal block (3P). 

When doing this, firmly secure using the included clamp 
(small) (5) according to the figure.

 

(Refer to Fig. 22)

 

Transmission wiring and remote controller wiring 

Unscrew and remove the control box cover.

 

Thread the remote controller wiring and transmission 
wiring through the included insulating tube (long) (7) and 
secure them with the included clamp (small) (5).  

(Refer to Fig. 21) 

Connect the remote controller wiring and the transmission 
wiring to the terminal block (6P). 
When doing this, tie the remote controller wiring and the 
transmission wiring using the included clamp (small) (5) 

and then firmly secure using the included clamp (small) 
(5) according to the figure.

 

(Refer to Fig. 22)

Fig. 21

Insulating tube (long)
(accessory) (7)

Clamp (small)
(accessory) (5)

Transmission
wiring

Remote 
controller
wiring

(1 in. (25 mm))

Insulating tube (short)
(accessory) (7)

Clamp (small)
(accessory) (5)

Power
supply
wiring

Ground
wiring

(1 in. (25 mm))

Fig. 22

Ground wiring

Power supply wiring

Transmission 
wiring

< Wiring clamp method >

Clamp (small) 
(accessory) (5)

Clamp (small) 
(accessory) (5)

Remote 
controller 
wiring

Insulating tube

Insulating tube

REMOTE

CNTRL

FORCED

OFF

TRANSMISSION

WIRING

F1 F2 T1 T2

P1 P2

Terminal block (6P)

Ground terminal

Ground wiring

Power supply wiring

Power supply
terminal block (3P)

Remote controller wiring and 

transmission wiring

Clamp (small) (accessory) (5)

(3 places)

Cut off any excess 
material after tightening.

L1

L2

01_EN_3PN07521-5H.indd   11

7/9/2018   14:13:35

Содержание SkyAir FAQ18TAVJU

Страница 1: ...erence This manual should be left with the equipment owner Lire soigneusement ces instructions avant l installation Conserver ce manuel port e de main pour r f rence ult rieure Ce manuel doit tre donn...

Страница 2: ...ant gas leaks during installation ventilate the area immediately Refrigerant gas may produce toxic gas if it comes in contact with fire Exposure to this gas could cause severe injury or death After co...

Страница 3: ...s protection again harmful ultraviolet radiation R410A can contribute to the greenhouse effect if it is released Therefore take proper measures to check for the tightness of the refrigerant piping in...

Страница 4: ...to leaks Where corrosive gas like sulfurous gas exists Copper tubing and brazed spots may corrode which could eventually lead to refrigerant leaks Where exposed to combustible gases and where volatil...

Страница 5: ...our customer Did you give the operation manual over to your cus tomer 2 3 NOTE TO THE INSTALLER Be sure to instruct customers how to properly operate the unit especially cleaning filters operating dif...

Страница 6: ...ght and back right Refer to Fig 3 Using the paper pattern for installation 3 choose where to route the piping out of the unit and drill a through hole f3 1 8 f80 in the wall Open the hole so that ther...

Страница 7: ...direction of the arrows 4 Making sure not to catch the horizontal flaps remove the front grille by pulling in the direction of the arrow Tab position Tab position Front grille Fig 7 Tab 2 2 2 3 3 4 3...

Страница 8: ...ap the insulating tape all the way to the L shaped bend Seal with putty corking material Seal the piping through hole with putty corking mate rial 9 Push on both bottom edges of the indoor unit using...

Страница 9: ...ile working on the unit ventilate the room thoroughly right away The refrigerant is pre charged in the outdoor unit Use copper alloy seamless pipes Be sure to use both a spanner and a torque wrench to...

Страница 10: ...unit piping Indoor unit piping insulating tube Clamp large accessory 5 L shaped bend Start wrapping See 4 INDOOR UNIT INSTALLATION Insulating tape accessory 4 CAUTION Be sure to insulate the field pip...

Страница 11: ...fer to the installation manual attached to the outdoor unit for the size of power supply wiring connected to the outdoor unit the capacity of the circuit breaker and switch and wiring instructions Be...

Страница 12: ...r wiring and transmission wiring through the included insulating tube long 7 and secure them with the included clamp small 5 Refer to Fig 21 Connect the remote controller wiring and the transmission w...

Страница 13: ...NS 1 Use round crimp style terminals for connecting wires to the power supply terminal block Refer to Fig 23 If unavailable observe the following points when wiring Do not connect wires of different g...

Страница 14: ...tallation manual supplied with the remote controller Wiring method 1 Remove the control box cover 2 Add the remote controller 2 SUB to the terminal block for remote controller P P in the control box T...

Страница 15: ...th display air filter signs to display the time to clean air filters Change the SECOND CODE NO according to Table 2 depending on the amount of dirt or dust in the room SECOND CODE NO is factory set to...

Страница 16: ...e indoor unit is off The indoor unit has not been wired for power supply Incorrect wiring for the remote controller wiring the transmission wiring and or the FORCED OFF wiring CAUTION After the test o...

Страница 17: ...5151 San Felipe Suite 500 Houston TX 77056 1809 HT 3PN07521 5H EM17A032...

Отзывы: