• Split Sky Air • Outdoor Units
23
• Outdoor Units • R-410A • RXL-G2V1B
3
Electrical data
2
3
RXL35G
Representative unit combination
Power supply
Comp.
OFM
IFM
Indoor unit
Outdoor unit
Hz-volts
Voltage range
MCA
MFA
RHz
RLA
W
FLA
W
FLA
FTXL35G2V1B
RXL35G2V1B
50 - 220
50 - 230
50 - 240
Max. 50Hz 264V
Min. 50Hz 198V
19.75
20
44
4.0
53
0.27
23
0.15
3.8
3.6
3D059718A
SYMBOLS
MCA
: Min. Circuit Amps (A)
MFA
: Max. Fuse Amps (A)
RHz
: Rated operating frequency (Hz)
RLA
: Rated Load Amps (A)
OFM
: Outdoor Fan Motor
IFM
: Indoor Fan Motor
FLA
: Full Load Amps (A)
W
: Fan Motor Rated Output
NOTES
1. RLA is based on the following conditions:
Indoor temp.: 27°CDB/19.0°CWB
Outdoor temp. : 35°CDB
2. Maximum allowable voltage variation between phases is 2%
3. Select wire size based on the larger value of MCA.
4. Instead of fuse, use Circuit Breaker.