• Outdoor Units • R-410A • RXL-G2V1B
• Split Sky Air • Outdoor Units
22
3
Electrical data
2
3
RXL20G
Representative unit combination
Power supply
Comp.
OFM
IFM
Indoor unit
Outdoor unit
Hz-volts
Voltage range
MCA
MFA
RHz
RLA
W
FLA
W
FLA
FTXL20G2V1B
RXL20G2V1B
50 - 220
50 - 230
50 - 240
Max. 50Hz 264V
Min. 50Hz 198V
9.75
10
34
2.4
50
0.23
23
0.15
2.3
2.2
3D055009C
SYMBOLS
MCA
: Min. Circuit Amps (A)
MFA
: Max. Fuse Amps (A)
RHz
: Rated operating frequency (Hz)
RLA
: Rated Load Amps (A)
OFM
: Outdoor Fan Motor
IFM
: Indoor Fan Motor
FLA
: Full Load Amps (A)
W
: Fan Motor Rated Output
NOTES
1. RLA is based on the following conditions:
Indoor temp.: 27°CDB/19.0°CWB
Outdoor temp. : 35°CDB
2. Maximum allowable voltage variation between phases is 2%
3. Select wire size based on the larger value of MCA.
4. Instead of fuse, use Circuit Breaker.
RXL25G
Representative unit combination
Power supply
Comp.
OFM
IFM
Indoor unit
Outdoor unit
Hz-volts
Voltage range
MCA
MFA
RHz
RLA
W
FLA
W
FLA
FTXL25G2V1B
RXL25G2V1B
50 - 220
50 - 230
50 - 240
Max. 50Hz 264V
Min. 50Hz 198V
14.75
20
27.5
3.0
50
0.23
23
0.15
2.9
2.8
3D059709A
SYMBOLS
MCA
: Min. Circuit Amps (A)
MFA
: Max. Fuse Amps (A)
RHz
: Rated operating frequency (Hz)
RLA
: Rated Load Amps (A)
OFM
: Outdoor Fan Motor
IFM
: Indoor Fan Motor
FLA
: Full Load Amps (A)
W
: Fan Motor Rated Output
NOTES
1. RLA is based on the following conditions:
Indoor temp.: 27°CDB/19.0°CWB
Outdoor temp. : 35°CDB
2. Maximum allowable voltage variation between phases is 2%
3. Select wire size based on the larger value of MCA.
4. Instead of fuse, use Circuit Breaker.