11
■
English
Facility Setting
(cooling at low outdoor temperature)
This function is designed for facilities such as equipment or computer rooms. It is never to be used
in a residence or office where people occupy the space.
Cutting the jumper 6 (J6)
on the circuit board will expand the operation range down to 14°F (–10°C).
Installing an air direction adjustment grille (sold separately) will further extend the operation range to –4°F (–20°C).
In these cases, the unit will stop operating if the outdoor temperature falls below –4°F (–20°C), restarting once the
temperature rises above this level.
1) Remove the top plate of the outdoor unit. (4 screws)
2) Remove the front plate. (5 screws)
3) Cut the jumper (J6) of the PCB inside.
Cut the jumper (J6).
For RX09/12, RXL09
Cut the jumper (J6).
For RXL12
J6
J5
J9
J12
J8
J11
J12
J11
J9
J8
J6
J5
When Attaching the Drain Pan Heater
WARNING
• Make sure to turn the power OFF before performing work.
In high humidity areas or heavy snow areas, it is recommended to attach a drain pan heater to
prevent ice build-up from the bottom frame.
1) Attach the drain pan heater in accordance with the installation manual included with the drain pan heater.
2) Cut the jumper (J9) of the PCB inside.
Cut the jumper (J9).
Cut the jumper (J9).
J6
J5
J9
J12
J8
J11
For RX09/12, RXL09
For RXL12
J12
J11
J9
J8
J6
J5
01_EN_3P686855-1.indd 11
2022/05/16 9:29:38