12
■
English
Pump Down Operation
In order to protect the environment, be sure to pump down when relocating or disposing of the unit.
1) Remove the valve caps from the liquid stop valve and gas stop valve.
2) Begin forced cooling operation.
3)
After 5 to 10 minutes, close the liquid stop valve with a hexagonal wrench.
4) After 2 to 3 minutes, close the gas stop valve and stop forced cooling operation.
5) Attach the valve caps once procedures are complete.
Forced cooling operation
Using the indoor unit ON/OFF switch
[For FTX, FTXR and FVX models]
Press the indoor unit ON/OFF switch for at least 5 seconds. (The operation will start.)
• Forced cooling operation will stop automatically after about 15 minutes.
To stop the operation, press the indoor unit ON/OFF switch.
Gas
stop valve
Valve cap
Hexagonal
wrench
Close
Liquid
stop valve
Service port
Using the indoor unit’s remote controller
[For FTX models]
1) Press
,
and
at the same time.
2) Press
, then select , press
.
3) Press
to turn on the system.
• Forced cooling operation will stop automatically after about 30 minutes.
To stop the operation, press
.
[For FTXR and FVX models]
1) Press
,
and
at the same time.
2) Press
, select “
”, and press
for confirmation.
3) Press
and select the COOL operation.
4) Press
to turn on the system.
• Forced cooling operation will stop automatically after about 30 minutes. To stop the operation, press
.
[For FFQ and FDMQ models]
[For wired remote controller]
1) Set to COOL operation using the remote controller.
2)
Press and hold the Cancel button for 4 seconds or longer.
Service settings menu is displayed.
3) Select
Test Operation
in the service settings menu, and press
the Menu/OK button. Basic screen returns and “Test Operation” is
displayed at the bottom.
4)
Press the ON/OFF button within 10 seconds, and the forced cooling
operation starts.
• Forced cooling operation will stop automatically after about
15 minutes. To stop the operation, press the ON/OFF button.
Basic screen
1)
2)
Cool
Return
Clean the filter
Set to
Cool
68
F
Press and hold the Cancel
button for 4 seconds or
longer during backlight lit.
Service Settings
menu screen
3)
Setting
1/3
Service Settings
Test Operation
Maintenance Contact
Field Settings
Energy Saving Options
Prohibit Buttons
Min Setpoints Differential
Press the Menu/OK button.
4)
Set temperature
80
°F
Cool
Test Operation
Press the ON/OFF button
(within 10 seconds).
English
01_EN_3P686855-1.indd 12