background image

x

 FlowSensor

FA ROTEX Solaris RPS4 - 

04/2016

31

6.4.3 Setting recommendation for the post-heating 

via external heat sources or by the electrical 
immersion heater, burner blocking contact

For the highest performance potential:

Ɣ

Heat the solar storage tank only infrequently and then only to
a just adequate temperature via the external heat source or
electrical immersion heater.

Ɣ

Restrict the recharging times by means of timer programmes:
a) Determine the optimum times for "normal use" by regular

consumption habits.

b) Enable supplementary heating for 1/2 to 2 hours before

usual usage time depending on the external source.

Ɣ

The charging time should be limited so that the cylinder does
not need to be directly heated after a normal consumption
cycle.

Ɣ

If greater volumes of hot water are used and to maintain
comfortable temperatures during periods of unusual use, set
the temperature in the hot water zone to a sufficiently high
level or enable the heat generator for supplementary heating, 
e.g. by switching to a different timer programme.

Setting the storage tank charging temperature

Ɣ

Set the hot water target temperature so that there is adequate 
hot water for drawing off (e.g. for one shower) at the lowest
possible setting value. This setting will guarantee the
maximum heating of the hot water by the solar installation for
a certain withdrawal quantity.

Heating by means of an external heat generator

Depending heating requirements (related to the building's insu-
lation standard, outdoor temperature, and desired room temper-
atures) and the installed collector surface, it might be expedient 
to disable the external heat generator by fitting a burner inhibit 
contact. For this purpose, also if the heater control demands ad-
ditional heat:

Ɣ

Set the operating parameters [P min], [TS min] and [time
VBSK] in such a way that the external heat generator does
not heat (see section 6.3.10),
– if a a minimum heating output is provided by the solar pan-

els or

– the storage cylinder has reached a sufficiently high tem-

perature.

6.4.4 Tips for optimised user behaviour

Hot water needs and user behaviour are highly individual. 
The higher the desired storage cylinder temperature is, and the 
longer the periods for non-solar charging heating have been ad-
justed, the more will the storage potential for solar heat gener-
ation be limited. Careful consumption behaviour, adapted to the 
particular strengths of the solar system minimises the energy 
consumption for non-solar charging processes.

Ɣ

Use modern and convenient shower heads with flow rates of
5 - 7 l/min.

Î

The lower flow rate (hot water consumption per minute)
results in a reduced need for supplementary heating, and 
there-fore a larger amount of hot water at a higher temper-
ature.

Ɣ

Reduce the consumption times.

Î

Lower energy consumption.

Ɣ

Start filling the bathtub only with hot water.

Î

After the domestic water stored in the solar storage tank
has been drawn off, the hot water outlet temperature 
drops slightly and the water is mixed in the bath. In this 
way, the storage capacity is used in an optimal manner 
with a minimum charging temperature; an adequate 
amount of hot water is available.

6.4.5 Domestic water hygiene

If no hot water is used for several days and the storage temper-
ature of the Solaris system does not reach at least 60°C, for hy-
giene reasons (Legionella protection) it is periodically heated up 
to above 60°C once or draw-off of the stored hot water (25 l) is 
recommended.

The optimum charging temperature depends on per-
sonal needs; frequently a storage cylinder temperature 
of 50°C is adequate. An average shower requires about 
30 to 50 l of hot water with an outlet temperature of 

40°C. The cold water that flows into the storage tank when tak-
ing a shower must be heated in the solar storage tank in a 
through-flow heating manner.

Содержание Rotex RPS4

Страница 1: ...ller ROTEX RPS4 Operating and installation instructions Regulation and pump unit for Solaris Solar Systems Valid for the following components ROTEX Solaris RPS4 Solaris R4 Differential temperature con...

Страница 2: ...aris RPS4 04 2016 1 x Guarantee 1 Guarantee 1 1 Warranty conditions The legal guarantee conditions fundamentally apply Our war ranty conditions beyond that can be found online on your sales representa...

Страница 3: ...Manual operation 21 6 2 7 FlowSensor 21 6 2 8 Output calculation maximum values and yield count 22 6 2 9 Speed regulation of the solar operating pump PS 22 6 2 10 Total Reset Function 23 6 2 11 Frost...

Страница 4: ...documentation of the ROTEX solar system and therefore must be observed The documents are included in the scope of supply of the individual components ROTEX high performance flat solar panels Solaris...

Страница 5: ...trained persons heating technicians roofers etc under observance of the relevant Accident Prevention Regulations Material and tools must be secured against falling Barriers must be erected to prevent...

Страница 6: ...panel 10 Solar panel array 11 Solar flow line at the top on the solar panel 12 Thermal mixing valve scalding protection provided by customer 13 Convection brake accessory 14 Solar flow layering pipe 1...

Страница 7: ...er heat pump Electronic control The fully electronic ROTEX Solaris R4 regulator ensures op timum utilisation of the solar heat hot water generation heating support and that all safety relevant aspects...

Страница 8: ...adequate you can interconnect several Sanicube HybridCube as modules The following components are offered Solar storage tank extension kit CON SX 16 01 20 Solar storage tank kit 2 CON SXE 16 01 21 Flo...

Страница 9: ...els can be mounted one above the other Solar panels or solar panel fields mounted one above the other must be connected in series fig 4 3 Fig 4 1 Solar panel field with a connection at each end recomm...

Страница 10: ...regulations DANGER Leaking gas in the immediate proximity of electrical components can cause an explosion The RPS4 regulating and pump unit and electrical components should not be installed in locatio...

Страница 11: ...of the FlowSensors c 4 Cut the flow pipe g 15 mm to the required length and insert it in the push in fitting f 5 Route the FlowSensor cable between the FlowSensor c and the Solaris R4 regulator 6 Plu...

Страница 12: ...sensor and insert into the sensor tube 2 Position the return flow temperature sensor in the sensor tube at approx 130 cm insertion depth cable tie 3 Position the storage cylinder temperature sensor in...

Страница 13: ...lti core with wire end sleeves with insulating collar 1 5 mm2 Multi core with wire end sleeves without insulating collar 2 5 mm2 Electrical connection 1 Plug in the supplied cables using the PCB edge...

Страница 14: ...as shown in fig 4 28 and fig 4 29 point downwards 6 Cabling of the solar operating pump PS Connect the pump cable to the solar operating pump PS 7 Run the control cables along the return pipe and fix...

Страница 15: ...control unit 2 Fix the cover to the control unit on both sides with countersunk screws 3 Fasten the cover to the cylinder connecting bracket underneath To do this carefully screw in the self tapping...

Страница 16: ...distributed evenly to all the con nected solar storage tanks We recommend using a FlowGuard FLG at each storage tank for regulation pur poses 10 Instruct the user fill out the acceptance report and se...

Страница 17: ...frost and may suffer damage Drain the heating system that is shut down if there is danger of frost CAUTION CAUTION Pumps that are switched off for a long time can seize With temporarily shut down sol...

Страница 18: ...5 3 Fig 5 3 Assembling the KFE fill ing connection in the connecting angle Thanks to the environmentally friendly design of the solar system ROTEX has complied with requirements for environmentally so...

Страница 19: ...r moving the temperature or pa rameter display up by one setting increas ing parameter settings 9 Down arrow for moving the temperature or parameter display down by one setting de creasing parameter s...

Страница 20: ...ly switched off TS light flashes pump operation with activated intensified frost protection function star symbol flashes in the display see section 6 2 11 pump operation if the solar panel temperature...

Страница 21: ...TV TR If the system has detected the FlowSensor once the display shows an error message if a sensor is faulty or is disconnected see section 7 1 Display of events The system then works in the emergen...

Страница 22: ...ing pump PS then takes place between the determined minimum and maximum outputs The spread of TV and TR TV TR is measured continuously and compared with the target spread DT If the temperature spread...

Страница 23: ...unction As soon as the Solaris R4 regulator detects a solar panel temper ature TK below 5 C non adjustable parameter T frost off the enhanced frost protection function becomes active This com pletely...

Страница 24: ...tem perature 30 to 250 C 1 K TK min Min measured collector tem perature 30 to 250 C 1 K V max Maximum flow rate 0 0 to 12 0 l min 0 1 l min Maximum flow measured during filling 0 0 to 20 0 l min 0 0...

Страница 25: ...he 3rd line burner block contact active see section 6 3 10 or a fault status see section 7 2 Trouble shooting H in the 4th line manual operating mode 6 3 3 Setup menu The Solaris R4 regulator paramete...

Страница 26: ...26 FA ROTEX Solaris RPS4 04 2016 6 x FlowSensor Fig 6 7 Setup menu...

Страница 27: ...h Enter choice 1 2 under Code 0000 It activates all important systems parameters in the settings menu for technicians see fig 6 7 6 3 5 Language selection During initial commissioning or after a total...

Страница 28: ...ce P min or if the storage tank has heated up to the adjustable minimum storage tank temperature set by the heating expert operating pa rameter TS min see tab 6 5 the burner is deactivated via a conta...

Страница 29: ...12 20 100 FLS 20 20 FLS 100 100 FR active Status frost protection function Yes No No H A Automatic return from manual to auto matic operation 1 to 900 min 30 min 1 min P min Min output for burner stop...

Страница 30: ...em runs without evaporation in the collector However on a cloudless day this can lead to a situation where the system only switches on again in the late afternoon although the storage cylinder tempera...

Страница 31: ...VBSK in such a way that the external heat generator does not heat see section 6 3 10 if a a minimum heating output is provided by the solar pan els or the storage cylinder has reached a sufficiently h...

Страница 32: ...equipment fault of the supply voltage G 7 Reference Internal equipment fault of the refer ence voltage G 8 RESET Overall reset was carried out Parameters to factory settings calculated values and eve...

Страница 33: ...ration is enabled automat ically Failures Sensor Cause of the fault Status blinks Display Lamp flashing Light flashes Collector temp Interruption K uuuu TK Long term switch off of PS Short circuit TK...

Страница 34: ...aling cap and loosen it if necessary do not remove 2 Check the installation for leaks Check the installation for leaks and rectify if necessary Follow instructions in section 5 Start up and decommis s...

Страница 35: ...atures up to 95 C If a heat exchanger is oper ated at temperatures greater than 95 C another gravity brake must be installed in the building A selection of diagrams of the most common installed syste...

Страница 36: ...36 FA ROTEX Solaris RPS4 04 2016 8 x Hydraulic system connection Fig 8 2 Standard Solaris incorporation with GCU compact 1 Fig 8 3 Standard Solaris incorporation with Air Water Heat Pump HPSU compact1...

Страница 37: ...laris RPS4 04 2016 37 1 The displayed plant schematics do not claim to be complete and do not replace careful indoor planning Fig 8 4 Standard Solaris incorporation with Air Water Heat Pump HPSU Bi Bl...

Страница 38: ...ain regulator heat pump HPSU com pact HPSU compact series solar storage tank with integrated heat pump unit MAG Diaphragm expansion vessel MIX 3 way mixer with drive motor MK1 Mixer group with high ef...

Страница 39: ...anel and the storage tank you cannot use the depressurised ROTEX solar system DrainBack and thus the regulation and pump unit RPS4 Instead the heating system can be executed with the ROTEX solar press...

Страница 40: ...x D 230 x 815 x142 mm Operating voltage 230 V 50 Hz Solar operating pump Grundfos UPM3 15 145 Maximum electrical power consumptionRPS4 During start 65 W 115 W In normal mode 15 65 W modulated 30 115...

Страница 41: ...characteristic curve RS Sensor resistance PTC Pt 1000 t Temperature Fig 9 1 Resistance characteristic lines of the Solaris sensor L Flow rate U Sensor output voltage t Temperature Fig 9 2 Characterist...

Страница 42: ...42 FA ROTEX Solaris RPS4 04 2016 10 x Notes 10 Notes...

Страница 43: ...n 20 29 34 Instantaneous output 35 M Malfunctions Manual 32 Rectification 33 Manual operation 6 21 22 23 25 27 28 Minimum pump output 22 23 Momentary output 24 Mounting position solar panel temperatur...

Страница 44: ...ROTEX FA ROTEX Solaris RPS4 Subject to change and correction 008 1627444_01 04 2016...

Отзывы: