background image

30

FA ROTEX Solaris RPS4 - 

04/2016

x

 FlowSensor

The following instructions help with determining the setting 
values and guarantee optimum thermal yield with low power con-
sumption:

Ɣ

Adjust the switch-on temperature difference [Delta T on] so
that the system remains in operation under constant solar
radiation conditions, and does not switch off immediately
when the collector temperature drops due to heat removal.
The lower this value can be adjusted, the longer will be the
operating periods with a correspondingly higher heat yield.
If the adjusted switch-on temperature difference is too low,
the collector will already cool down so far during filling, that
the switch-off temperature difference is reached.

Î

The pumps are switched off immediately, with resulting
lower heat yield and higher power consumption.

Ɣ

Adjust the switch-off temperature difference [Delta T off] so
that the heat yield obtainable at the switch-off point is higher
than the electrical power required to drive the pump.

Î

Since the power consumption of the solar operating pump 
P

S

 is virtually independent of the size of the connected 

solar panel array, but the thermal power that can be 
exploited is directly dependent on the number of solar 
panels, the parameter value on a few solar panels is set 
higher, but with multiple solar panels it is set lower.

Ɣ

The run time [time P2] for maximum output of the solar
operating pump P

S

 to be set so that, in all cases, the total

cross-section of the flow line is filled with water. Determine
the time from the detection of air noises from switching on the 
solar operating pump P

S

 to entry into the storage tank and

add a safety factor of 20 secs. The filling period depends on
the adjusted flow rate, the number of collectors, system
height, and the length of the connecting pipe

Ɣ

The maximum storage temperature [TS max] is set according
to the individual conditions. The higher the value of the
parameter, the higher will be the available heat storage
capacity, and thus the output potential of the ROTEX solar
system.

System switch-on involving steam generation can often be 
disconcerting for the operator. In order to reduce boiling noises 
and steam emission, the restart temperature [TK permitted] is set 
in the factory. The Solaris R4 regulator only switches the solar 
operation pump P

S

 on again when the collector temperature has 

fallen 2 Kelvin below the adjusted parameter value. Conse-
quently, the system runs without evaporation in the collector. 
However, on a cloudless day, this can lead to a situation where 
the system only switches on again in the late afternoon, although 

the storage cylinder temperature permits additional heating.

Ɣ

In order to maximise energy input, set the [TK permitted] to a
value greater than 100°C and thus deactivate the restart
protection function.
In this case the system operator should be advised of audible
bubbling noises and steam knocking during filling.

6.4.2 Additional settings for your solar system

The following setting instructions apply only to basic setting with 
fitted FlowGuard:

Ɣ

Activate manual mode.

Ɣ

After filling the system completely, set the water flow rate so
that each solar panel is transited at 90 to 120 l/h. Influence the 
flow rate either by setting the speed stage at the solar
operating pump PS or/and by setting the FlowGuard
(regulating valve with flow indication). Reference values for
correct valve and pump stage settings are listed in tab. 6-6.

Ɣ

Switch the Solaris R4 regulator after completing the setting.

Tab. 6-6 Setting the flow rate on the FlowGuard (FLG)

During commissioning, the system parameters must be 
adjusted individually to suit the installed system, and 
might need fine tuning during subsequent operation. 
Usually, the system will operate with the default set-
tings.

WARNING!

Temperatures in excess of 60°C can arise in the 
solar storage tank.

Ɣ

Install scalding protection.
– Scalding protection VTA32 (

 15 60 15

)

– Screw connection set 1" (

15 60 16

)

Number of

solar panels

Nominal flow 

in l/min

Desired flow in l/hour

2

3.0 to 4.0

180 to 240

3

4.5 to 6.0

270 to 360

4

6.0 to 8.0

360 to 480

5

7.5 to 10.0

450 to 600

For rapid and safe filling of the system, always set the 
solar operating pump P

S

 to a high speed stage, if the 

installation height H, as a height difference between the 
installation surface of the solar storage tank and the top 

of the solar panel does not exceed 10 m and an adequate flow 
rate still sets itself.

Even if the flow volume is set correctly, the cut-in tem-
perature difference [Delta T on] and good weather con-
ditions will occasionally shut down the solar system. 
With a rising or setting sun, and an increasing storage 

cylinder temperature, the collector temperature gradually falls 
after the pumps have been switched on, i.e. the switch-off con-
ditions are met. The continuing solar radiation will increase the 
temperature of the solar panels, the pumps will operate and the 
system will cycle because the solar radiation is no longer suffi-
cient for continuous operation. The FlowSensor reduces this 
effect by pump speed regulation.

Содержание Rotex RPS4

Страница 1: ...ller ROTEX RPS4 Operating and installation instructions Regulation and pump unit for Solaris Solar Systems Valid for the following components ROTEX Solaris RPS4 Solaris R4 Differential temperature con...

Страница 2: ...aris RPS4 04 2016 1 x Guarantee 1 Guarantee 1 1 Warranty conditions The legal guarantee conditions fundamentally apply Our war ranty conditions beyond that can be found online on your sales representa...

Страница 3: ...Manual operation 21 6 2 7 FlowSensor 21 6 2 8 Output calculation maximum values and yield count 22 6 2 9 Speed regulation of the solar operating pump PS 22 6 2 10 Total Reset Function 23 6 2 11 Frost...

Страница 4: ...documentation of the ROTEX solar system and therefore must be observed The documents are included in the scope of supply of the individual components ROTEX high performance flat solar panels Solaris...

Страница 5: ...trained persons heating technicians roofers etc under observance of the relevant Accident Prevention Regulations Material and tools must be secured against falling Barriers must be erected to prevent...

Страница 6: ...panel 10 Solar panel array 11 Solar flow line at the top on the solar panel 12 Thermal mixing valve scalding protection provided by customer 13 Convection brake accessory 14 Solar flow layering pipe 1...

Страница 7: ...er heat pump Electronic control The fully electronic ROTEX Solaris R4 regulator ensures op timum utilisation of the solar heat hot water generation heating support and that all safety relevant aspects...

Страница 8: ...adequate you can interconnect several Sanicube HybridCube as modules The following components are offered Solar storage tank extension kit CON SX 16 01 20 Solar storage tank kit 2 CON SXE 16 01 21 Flo...

Страница 9: ...els can be mounted one above the other Solar panels or solar panel fields mounted one above the other must be connected in series fig 4 3 Fig 4 1 Solar panel field with a connection at each end recomm...

Страница 10: ...regulations DANGER Leaking gas in the immediate proximity of electrical components can cause an explosion The RPS4 regulating and pump unit and electrical components should not be installed in locatio...

Страница 11: ...of the FlowSensors c 4 Cut the flow pipe g 15 mm to the required length and insert it in the push in fitting f 5 Route the FlowSensor cable between the FlowSensor c and the Solaris R4 regulator 6 Plu...

Страница 12: ...sensor and insert into the sensor tube 2 Position the return flow temperature sensor in the sensor tube at approx 130 cm insertion depth cable tie 3 Position the storage cylinder temperature sensor in...

Страница 13: ...lti core with wire end sleeves with insulating collar 1 5 mm2 Multi core with wire end sleeves without insulating collar 2 5 mm2 Electrical connection 1 Plug in the supplied cables using the PCB edge...

Страница 14: ...as shown in fig 4 28 and fig 4 29 point downwards 6 Cabling of the solar operating pump PS Connect the pump cable to the solar operating pump PS 7 Run the control cables along the return pipe and fix...

Страница 15: ...control unit 2 Fix the cover to the control unit on both sides with countersunk screws 3 Fasten the cover to the cylinder connecting bracket underneath To do this carefully screw in the self tapping...

Страница 16: ...distributed evenly to all the con nected solar storage tanks We recommend using a FlowGuard FLG at each storage tank for regulation pur poses 10 Instruct the user fill out the acceptance report and se...

Страница 17: ...frost and may suffer damage Drain the heating system that is shut down if there is danger of frost CAUTION CAUTION Pumps that are switched off for a long time can seize With temporarily shut down sol...

Страница 18: ...5 3 Fig 5 3 Assembling the KFE fill ing connection in the connecting angle Thanks to the environmentally friendly design of the solar system ROTEX has complied with requirements for environmentally so...

Страница 19: ...r moving the temperature or pa rameter display up by one setting increas ing parameter settings 9 Down arrow for moving the temperature or parameter display down by one setting de creasing parameter s...

Страница 20: ...ly switched off TS light flashes pump operation with activated intensified frost protection function star symbol flashes in the display see section 6 2 11 pump operation if the solar panel temperature...

Страница 21: ...TV TR If the system has detected the FlowSensor once the display shows an error message if a sensor is faulty or is disconnected see section 7 1 Display of events The system then works in the emergen...

Страница 22: ...ing pump PS then takes place between the determined minimum and maximum outputs The spread of TV and TR TV TR is measured continuously and compared with the target spread DT If the temperature spread...

Страница 23: ...unction As soon as the Solaris R4 regulator detects a solar panel temper ature TK below 5 C non adjustable parameter T frost off the enhanced frost protection function becomes active This com pletely...

Страница 24: ...tem perature 30 to 250 C 1 K TK min Min measured collector tem perature 30 to 250 C 1 K V max Maximum flow rate 0 0 to 12 0 l min 0 1 l min Maximum flow measured during filling 0 0 to 20 0 l min 0 0...

Страница 25: ...he 3rd line burner block contact active see section 6 3 10 or a fault status see section 7 2 Trouble shooting H in the 4th line manual operating mode 6 3 3 Setup menu The Solaris R4 regulator paramete...

Страница 26: ...26 FA ROTEX Solaris RPS4 04 2016 6 x FlowSensor Fig 6 7 Setup menu...

Страница 27: ...h Enter choice 1 2 under Code 0000 It activates all important systems parameters in the settings menu for technicians see fig 6 7 6 3 5 Language selection During initial commissioning or after a total...

Страница 28: ...ce P min or if the storage tank has heated up to the adjustable minimum storage tank temperature set by the heating expert operating pa rameter TS min see tab 6 5 the burner is deactivated via a conta...

Страница 29: ...12 20 100 FLS 20 20 FLS 100 100 FR active Status frost protection function Yes No No H A Automatic return from manual to auto matic operation 1 to 900 min 30 min 1 min P min Min output for burner stop...

Страница 30: ...em runs without evaporation in the collector However on a cloudless day this can lead to a situation where the system only switches on again in the late afternoon although the storage cylinder tempera...

Страница 31: ...VBSK in such a way that the external heat generator does not heat see section 6 3 10 if a a minimum heating output is provided by the solar pan els or the storage cylinder has reached a sufficiently h...

Страница 32: ...equipment fault of the supply voltage G 7 Reference Internal equipment fault of the refer ence voltage G 8 RESET Overall reset was carried out Parameters to factory settings calculated values and eve...

Страница 33: ...ration is enabled automat ically Failures Sensor Cause of the fault Status blinks Display Lamp flashing Light flashes Collector temp Interruption K uuuu TK Long term switch off of PS Short circuit TK...

Страница 34: ...aling cap and loosen it if necessary do not remove 2 Check the installation for leaks Check the installation for leaks and rectify if necessary Follow instructions in section 5 Start up and decommis s...

Страница 35: ...atures up to 95 C If a heat exchanger is oper ated at temperatures greater than 95 C another gravity brake must be installed in the building A selection of diagrams of the most common installed syste...

Страница 36: ...36 FA ROTEX Solaris RPS4 04 2016 8 x Hydraulic system connection Fig 8 2 Standard Solaris incorporation with GCU compact 1 Fig 8 3 Standard Solaris incorporation with Air Water Heat Pump HPSU compact1...

Страница 37: ...laris RPS4 04 2016 37 1 The displayed plant schematics do not claim to be complete and do not replace careful indoor planning Fig 8 4 Standard Solaris incorporation with Air Water Heat Pump HPSU Bi Bl...

Страница 38: ...ain regulator heat pump HPSU com pact HPSU compact series solar storage tank with integrated heat pump unit MAG Diaphragm expansion vessel MIX 3 way mixer with drive motor MK1 Mixer group with high ef...

Страница 39: ...anel and the storage tank you cannot use the depressurised ROTEX solar system DrainBack and thus the regulation and pump unit RPS4 Instead the heating system can be executed with the ROTEX solar press...

Страница 40: ...x D 230 x 815 x142 mm Operating voltage 230 V 50 Hz Solar operating pump Grundfos UPM3 15 145 Maximum electrical power consumptionRPS4 During start 65 W 115 W In normal mode 15 65 W modulated 30 115...

Страница 41: ...characteristic curve RS Sensor resistance PTC Pt 1000 t Temperature Fig 9 1 Resistance characteristic lines of the Solaris sensor L Flow rate U Sensor output voltage t Temperature Fig 9 2 Characterist...

Страница 42: ...42 FA ROTEX Solaris RPS4 04 2016 10 x Notes 10 Notes...

Страница 43: ...n 20 29 34 Instantaneous output 35 M Malfunctions Manual 32 Rectification 33 Manual operation 6 21 22 23 25 27 28 Minimum pump output 22 23 Momentary output 24 Mounting position solar panel temperatur...

Страница 44: ...ROTEX FA ROTEX Solaris RPS4 Subject to change and correction 008 1627444_01 04 2016...

Отзывы: