REFNET Pipe System
EDUS39-605
6 Installation of Outdoor Units
3.2
Field Refrigerant Piping
3.2.1
Heat Pump Series
1. The following materials should be used for all refrigerant piping:
Materials: Deoxidized phosphorous seamless copper pipe or equivalent
2. The tips for insulation
Both Gas and liquid piping must be insulated.
Materials: Glass fiber or heat resistant polyethylene foam
Thickness: 1/2 inch or more
Heat resistance: Gas pipe : 250°F or more / Liquid pipe : 160°F or more
3.2.2
Heat Recovery Series
Suction, discharge gas piping, and liquid piping must be insulated.
Example of thermal insulation work:
Insulation of single pipe only
Insulation of both liquid and gas pipe
3 piping section (between outdoor unit and BS unit)
2 piping section (between BS unit and indoor unit)