Installation
EDUS39-605
57
Installation of Outdoor Units
Cautions for normal operation check:
•
Once stopped, the compressor cannot restart in about 5
minutes even if the
On/Off
button of an indoor unit in the
same system is pressed.
•
When the system operation is stopped by the remote con-
trol, the outdoor units may continue to operate for a further
5 minutes.
•
If the system has not undergone any check operation by
the test operation button since it was first installed, an error
code “U3” is displayed. In this case, perform check opera-
tion referring to
8-2 Test Operation
.
•
After the test operation, when handing the unit over to the
customer, make sure the electric box lid, the service lid,
and the unit casing are all attached.
10.4 CAUTION FOR REFRIGERANT LEAKS
DANGER
•
Refrigerant gas is heavier than air and replaces oxygen. A
massive leak could lead to oxygen depletion, especially in
basements, and an asphyxiation hazard could occur lead-
ing to serious injury or death.
CHECKING FOR REFRIGERANT LEAKS IS MANDATORY
The installer must be properly trained in safety requirements
and procedures for handling and working with R-410A. The
installer must prevent leakage according to local regulations
or standards.
The VRV System uses R-410A as refrigerant. R-410A itself is
an entirely safe, non-toxic, non-combustible refrigerant
Compliance with local regulations and standards must be fol-
lowed in order to ensure that the maximum concentration level
of refrigerant gas is not exceeded, and care must be taken to
ensure that equipment is installed in a large enough room.
Maximum concentration level
The maximum concentration and charge of refrigerant is
directly related to the occupied space in which it could leak.
The unit of measurement of the concentration is lb./ft
3
and the
weight in lbs of the refrigerant gas is 1ft
3
volume of the occu-
pied space.
1.
direction of the refrigerant flow
2.
room where refrigerant leak has occurred depicting
outflow of all the refrigerant from the system.
Pay special attention to the types of places, such basements
or other areas with limited ventilation, where refrigerant can
be trapped. Refrigerant is heavier than air and replaces oxy-
gen. See Danger caption on Page 19.
Procedure for checking maximum concentration
Check the maximum concentration level in accordance with
steps 1 to 4 below and take whatever action is necessary to
comply.
1.
Calculate the amount of refrigerant (Ib.) charged to each
system separately.
NOTE
•
Where a single refrigerant facility is divided into 2 entirely
independent refrigerant systems, use the amount of refrig-
erant with which each separate system is charged.
amount of refriger-
ant in a single unit
system (amount of
refrigerant with
which the system
is charged before
leaving the factory)
+
additional charging
amount (amount of
refrigerant added
locally in accordance
with the length or
diameter of the refrig-
erant piping)
=
total amount
of refriger-
ant (Ib.) in
the system