Installation
EDUS39-605
43
Installation of Outdoor Units
1-4 Technical specifications (1)
(1) Refer to the engineering data book for the complete list of
specifications.
(2) The nominal cooling capacity is based on:indoor temperature:
80°FDB / 67°FWB
- outdoor temperature: 95°FDB
- pipe length: 25ft.
- level difference: 0ft.
(3) The nominal heating capacity is based on:indoor temperature:
70°FDB
- outdoor temperature: 47°FDB / 43°FWB
- pipe length: 25ft.
- level difference: 0ft.
(4) The nominal input includes total input of the unit: com
pressor, fan motor and control circuit.
General
REYQ72MTJU
REYQ96MTJU
REYQ144MTJU
Nominal cool-
ing capacity (2)
MBh
72
96
144
Nominal heat-
ing capacity (3)
MBh
81
108
162
Nominal input
cooling / heat-
ing (4)
kW
8.67 / 9.19
8.67 / 9.19
17.34 / 18.38
Dimensions
H×W×D
inch
64 × 48-7/8
× 30-1/8
64 × 48-7/8 ×
30-1/8
(64 × 48-7/8 ×
30-1/8) + (64 ×
48-7/8 × 30-1/8)
Mass
Ib.
666
666
666+666
Refrigerant
suction gas
pipe
inch
3/4
7/8
1-1/8
Refrigerant
discharge gas
pipe
inch
5/8
3/4
7/8
Refrigerant liq-
uid pipe
inch
3/8
3/8
5/8
General
REYQ168MTJU
REYQ192MTJU
Nominal cool-
ing capacity
(2)
MBh
168
192
Nominal heat-
ing capacity
(3)
MBh
189
216
Nominal input
cooling / heat-
ing (4)
kW
14.37 / 15.79
17.34 / 18.38
Dimensions
H×W×D
inch
64 × 48-7/8 ×
30-1/8
(64 × 48-7/8 × 30-1/
8) + (64 ×
48-7/8 × 30-1/8)
Mass
Ib.
666+666
666+666
Refrigerant
suction gas
pipe
inch
1-1/8
1-1/8
Refrigerant
discharge gas
pipe
inch
7/8
7/8
Refrigerant
liquid pipe
inch
5/8
5/8
Compressor
REYQ72/96MTJU
REYQ144/168/
192MTJU
Oil type
-
Synthetic(ether)oil
Synthetic(ether)oil
Oil charge vol-
ume
l
1.9+1.6
(1.9+1.6)+(1.9+1.6)
Crankcase
heater
W
33+33
(33+33)+(33+33)
Refrigerant type
-
R-410A
R-410A
Refrigerant
charge
Ib.
27.3
27.3+27.3
Condenser
REYQ72/96MTJU
REYQ144/168/
192MTJU
Nominal air flow
CFM
7400
7400+7400
Fan motor out-
put
W
750
750+750