EDUS39-605
Installation
Installation of Outdoor Units 23
•
Secure the unit to its base using foundation bolts. Use four
commercially available M12-type foundation bolts, nuts,
and washers.
•
The foundation bolts should be inserted
13/16”.
•
Make sure the base under the unit sup-
ports the unit over an area of at least the
base leg widths of 2-5/8”.
•
The height of the base should be at least 5-7/8” from the
floor.
•
The unit must be installed on a solid longitudinal foundation
(steelbeam frame or concrete) as indicated in figure 4.
Refer to Figure 4.
1.
Foundation bolt point (
φ
9/16” dia. : 4 positions)
2.
Depth of product
3.
Shape of outdoor unit’s support leg and foundation
bolt positions
4.
Base leg width
DO NOT USE STANDS TO SUPPORT THE CORNERS
Refer to Figure 5.
1.
Do not use stands to support four corners.
2.
Center position of unitPrepare a channel around
the foundation to drain condensate waste water
from the unit.
2.
If the unit is to be installed on a roof, check the strength
of the roof and its drainage facilities before beginning
installation.
3.
If the unit is to be installed on a frame, install the water-
proofing board at least 5-14/16” under the unit to pre-
vent water from infiltrating the unit.
NOTE
•
When installing on a roof, make sure the roof floor is strong
enough and be sure to waterproof all work.
•
Make sure the area around the machine drains properly by
setting up drainage grooves around the foundation.
Condensate water is sometimes discharged from the out-
door unit when it is running.
•
Block all gaps in the holes for piping and wiring using
locally procured sealing material
to prevent small animals or debris from entering the
machine.
Ex: passing piping out through the front
1.
Plug the areas marked with
.
when the piping is routed from the front panel.
2.
Gas side piping
3.
Liquid side piping
• Use a nut with a resin clip plate to protect the nut tightening
part from rusting.
Model
A (in.)
B (in.)
Q96 type
48-13/16
43-3/8
13/16”
!
Resin clip plate