Troubleshooting by Error Code
SiUS372201EA
349
Part 6 Service Diagnosis
3.38 Compressor Damage Alarm
Applicable
Models
All outdoor unit models
Error Code
E6
Method of Error
Detection
Determine the symptom to be error by detecting the revolutions of the compressor and pressure
values detected by the high and low pressure sensors, and further making a comparison between a
theoretical current value of the compressor calculated from parameters detected and an actual
current value detected by the power transistor.
Error Decision
Conditions
When a state in which the actual current value of the compressor is abnormally high (by 130% or
more) compared to the theoretical current value continues for a period of 30 minutes.
In case of a system with multi outdoor units, the system will return an alarm if there is any
operational unit other than that applicable to
E6
or determine to be error if not.
Supposed
Causes
Defective compressor
Defective high pressure sensor
Defective low pressure sensor
Defective outdoor unit main PCB
Defective inverter PCB
Troubleshooting
NO
YES
Are the
characteristics of
the high pressure
sensor normal?
(
1)
(1) Mount a pressure gauge on the high and low pressure
service ports.
(2) Reset the power supply, and then restart the operation.
Replace the high pressure sensor
(S1NPH).
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
NO
YES
Are the
characteristics of
the low pressure
sensor normal?
(
1)
Replace the low pressure sensor
(S1NPL).
Connect the service checker to compare the high
pressure and low pressure checked by the service
checker and the actual measured values of the high and
low pressure sensors. (
1)
Service Checker
A
CHECK 12
Go to the next page.
Содержание REYQ-AATJA
Страница 1: ...Service Manual Heat Recovery 60 Hz REYQ AATJA 208 230 V REYQ AAYDA 460 V SiUS372201EA...
Страница 433: ...SiUS372201EA Check Part 6 Service Diagnosis 426 Reference Reference CHECK 7 Refer to page 432 CHECK 8 Refer to page 433...
Страница 460: ...Wiring Diagrams SiUS372201EA 453 Part 7 Appendix REYQ72 96 120 144 168 192 216 240AAYDA C 2D131905G...
Страница 463: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 456 1 2 2 Multi Branch Selector Unit Standard Series BS4Q54TVJ 3D089123B...
Страница 465: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 458 BS6 8Q54TVJ 2D089122B...
Страница 466: ...Wiring Diagrams SiUS372201EA 459 Part 7 Appendix BS10 12Q54TVJ 2D089121B...
Страница 468: ...Wiring Diagrams SiUS372201EA 461 Part 7 Appendix 1 2 3 Multi Branch Selector Unit Flex Series BSF4Q54TVJ 3D123904A...
Страница 469: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 462 BSF6 8Q54TVJ 2D123905A...
Страница 470: ...Wiring Diagrams SiUS372201EA 463 Part 7 Appendix 1 3 Indoor Unit FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 471: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 464 BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ TVJU 3D076375A...
Страница 472: ...Wiring Diagrams SiUS372201EA 465 Part 7 Appendix FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Страница 476: ...Wiring Diagrams SiUS372201EA 469 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 477: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 470 FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 478: ...Wiring Diagrams SiUS372201EA 471 Part 7 Appendix FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU C 3D110467C...
Страница 480: ...Wiring Diagrams SiUS372201EA 473 Part 7 Appendix FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 483: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 476 FXHQ12 24 36MVJU 3D048116C...
Страница 484: ...Wiring Diagrams SiUS372201EA 477 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 490: ...Wiring Diagrams SiUS372201EA 483 Part 7 Appendix VAM1200GVJU 3D073270D...