Field Settings for Indoor Unit
SiUS372201EA
203
Part 5 Field Settings and Test Operation
Note(s)
Note(s)
1.4.10 Detection Rate Setting (For units with an infrared presence sensor
only)
Set the sensitivity of the infrared presence sensor.
The infrared presence sensor can be disabled by selecting the Second code No.
04
.
When the infrared presence sensor is disabled, the remote controller menu does not display some
functions such as the automatic draft reduction, energy-saving operation in absence and halt in
absence.
1.4.11 Automatic Airflow Adjustment
Make external static pressure setting automatically using automatic airflow adjustment (11 (21)-7),
or manually using external static pressure settings (13 (23)-6).
The volume of blow-off air is automatically adjusted to the rated quantity.
Make settings before performing the test operation of the outdoor unit.
Setting procedure
1. Make sure that electric wiring and duct construction have been completed.
In particular, if the closing damper is installed on the way of the duct, make sure that it is open.
In addition, make sure that a field-supplied air filter is installed within the air passageway on the
suction port side.
2. If there are multiple blow-off and suction ports, adjust the throttle part so that the airflow volume
ratio of each suction/blow-off port conforms to the designed airflow volume ratio. In that case,
operate the unit with the operation mode "fan". When you want to change the airflow rate, adjust
it by pressing the airflow rate control button to select High, Middle or Low.
3. Make settings to adjust the airflow rate automatically.
After setting the operation mode to "fan", enter the field setting mode while operation is stopped
and then select the Mode No. 11 (21), set the First Code No. to
7
and the Second Code No. to
03
.
4. After setting, return to the basic screen (to the normal mode in the case of a wireless remote
controller) and press the ON/OFF button. Fan operation for automatic airflow adjustment will
start with the operation lamp turned ON. Do not adjust the throttle part of the suction and
blow-off ports during automatic adjustment. After operation for approximately one to fifteen
minutes, airflow adjustment automatically stops with the operation lamp turned OFF.
5. After operation stopped, make sure that the Second Code No. is set to
02
as in the following
table by indoor unit with the Mode No. 11 (21). If operation does not stop automatically or the
Second Code No. is not set to
02
, return to the step 3. above to make settings again.
: Factory setting
1. Make sure that the external static pressure is within the range of specifications before making
settings. If it is outside the range, automatic adjustment fails, which may cause an insufficient
airflow volume or leakage of water.
: Factory setting
Mode
No.
First Code
No.
Second Code
No.
Contents
11 (21)
6
01
High sensitivity
02
Low sensitivity
03
Standard sensitivity
04
Infrared presence sensor disabled
Mode
No.
First Code
No.
Second Code
No.
Contents
11 (21)
7
01
OFF
02
Completion of airflow adjustment
03
Start of airflow adjustment
Содержание REYQ-AATJA
Страница 1: ...Service Manual Heat Recovery 60 Hz REYQ AATJA 208 230 V REYQ AAYDA 460 V SiUS372201EA...
Страница 433: ...SiUS372201EA Check Part 6 Service Diagnosis 426 Reference Reference CHECK 7 Refer to page 432 CHECK 8 Refer to page 433...
Страница 460: ...Wiring Diagrams SiUS372201EA 453 Part 7 Appendix REYQ72 96 120 144 168 192 216 240AAYDA C 2D131905G...
Страница 463: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 456 1 2 2 Multi Branch Selector Unit Standard Series BS4Q54TVJ 3D089123B...
Страница 465: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 458 BS6 8Q54TVJ 2D089122B...
Страница 466: ...Wiring Diagrams SiUS372201EA 459 Part 7 Appendix BS10 12Q54TVJ 2D089121B...
Страница 468: ...Wiring Diagrams SiUS372201EA 461 Part 7 Appendix 1 2 3 Multi Branch Selector Unit Flex Series BSF4Q54TVJ 3D123904A...
Страница 469: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 462 BSF6 8Q54TVJ 2D123905A...
Страница 470: ...Wiring Diagrams SiUS372201EA 463 Part 7 Appendix 1 3 Indoor Unit FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 471: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 464 BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ TVJU 3D076375A...
Страница 472: ...Wiring Diagrams SiUS372201EA 465 Part 7 Appendix FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Страница 476: ...Wiring Diagrams SiUS372201EA 469 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 477: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 470 FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 478: ...Wiring Diagrams SiUS372201EA 471 Part 7 Appendix FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU C 3D110467C...
Страница 480: ...Wiring Diagrams SiUS372201EA 473 Part 7 Appendix FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 483: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 476 FXHQ12 24 36MVJU 3D048116C...
Страница 484: ...Wiring Diagrams SiUS372201EA 477 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 490: ...Wiring Diagrams SiUS372201EA 483 Part 7 Appendix VAM1200GVJU 3D073270D...