Field Setting from Outdoor Unit
SiUS372201EA
231
Part 5 Field Settings and Test Operation
2.5.3 Details of Setting Mode 2
Mode 2 is used to change the field settings of the system. Consulting the current field setting value
and changing the current field setting value is possible.
In general, normal operation can be resumed without special intervention after changing field
settings.
Some field settings are used for special operation (e.g. 1 time operation, recovery/vacuuming
setting, adding refrigerant setting, etc.). In such a case, it is required to abort the special operation
before normal operation can restart. It will be displayed in below explanations.
[2-0]:
Cool/Heat selection setting
Cool/Heat selection setting is used in case the optional Cool/Heat selector
(KRC19-26A) is used. Depending on the outdoor unit setup (single outdoor unit setup or
multi outdoor unit setup), the correct setting should be chosen. More details on how to
use the Cool/Heat selector option can be found in the manual of the Cool/Heat selector.
Default value: 0.
0: Each individual outdoor unit can select Cool/Heat operation (by Cool/Heat selector
if installed).
1: Master unit decides Cool/Heat operation when outdoor units are connected in
multiple system combination
2: Sub unit for Cool/Heat operation when outdoor units are connected in multiple
system combination
Change [2-0] to 0, 1 or 2 in function of required functionality.
[2-2]:
Low noise/demand address
Address for low noise/demand operation.
1 or more systems (maximum 10 systems wired by “F1F2 OUT/D”) can operate use
the LNO (Low Noise Operation) or/and the DE (Demand Operation) by instruction of
field supplied input to optional PCB DTA104A61/62.
To link the system to the corresponding DTA104A61/62, set the address same as
the DIP switches position on the related optional PCB DTA104A61/62.
Ensure that also field setting 2-12-1 is set to enable input from optional PCB
DTA104A61/62.
[2-5]:
Cross wiring check
Default value: 0. Not active.
Set 1: force all connected indoor units to operate the indoor fan on high speed. This
setting can be made to check which units are missing in the communication if the
number of indoor units do not correspond to the system lay out. Ensure that after
cross wiring check was confirmed, to return setting to default 2-5-0. Once setting
2-5-1 is active, it is not automatically returning to default when exit mode 2.
[2-6]:
Forced thermostat ON command all connected indoor units
Default value: 0. Not active.
Set 1: force all connected indoor units to operate under “Test” (forced thermostat
ON command to outdoor). Ensure that when the forced thermostat ON needs to be
ended, to return setting to default 2-6-0. Once setting 2-6-1 is active, it is not
automatically returning to default when exit mode 2.
Содержание REYQ-AATJA
Страница 1: ...Service Manual Heat Recovery 60 Hz REYQ AATJA 208 230 V REYQ AAYDA 460 V SiUS372201EA...
Страница 433: ...SiUS372201EA Check Part 6 Service Diagnosis 426 Reference Reference CHECK 7 Refer to page 432 CHECK 8 Refer to page 433...
Страница 460: ...Wiring Diagrams SiUS372201EA 453 Part 7 Appendix REYQ72 96 120 144 168 192 216 240AAYDA C 2D131905G...
Страница 463: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 456 1 2 2 Multi Branch Selector Unit Standard Series BS4Q54TVJ 3D089123B...
Страница 465: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 458 BS6 8Q54TVJ 2D089122B...
Страница 466: ...Wiring Diagrams SiUS372201EA 459 Part 7 Appendix BS10 12Q54TVJ 2D089121B...
Страница 468: ...Wiring Diagrams SiUS372201EA 461 Part 7 Appendix 1 2 3 Multi Branch Selector Unit Flex Series BSF4Q54TVJ 3D123904A...
Страница 469: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 462 BSF6 8Q54TVJ 2D123905A...
Страница 470: ...Wiring Diagrams SiUS372201EA 463 Part 7 Appendix 1 3 Indoor Unit FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 471: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 464 BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ TVJU 3D076375A...
Страница 472: ...Wiring Diagrams SiUS372201EA 465 Part 7 Appendix FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Страница 476: ...Wiring Diagrams SiUS372201EA 469 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 477: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 470 FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 478: ...Wiring Diagrams SiUS372201EA 471 Part 7 Appendix FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU C 3D110467C...
Страница 480: ...Wiring Diagrams SiUS372201EA 473 Part 7 Appendix FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 483: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 476 FXHQ12 24 36MVJU 3D048116C...
Страница 484: ...Wiring Diagrams SiUS372201EA 477 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 490: ...Wiring Diagrams SiUS372201EA 483 Part 7 Appendix VAM1200GVJU 3D073270D...