Gas Heating Capacity Data
Table 14: DPS 003-015 Gas Heating Capacities
Data
Unit Size
003 - 006
007 - 015
Low Heat
Med Heat
High Heat
Low Heat
Med Heat
High Heat
Heating Input (MBh)
80
120
160
200
300
400
Heating Output (MBh)
64
96
128
160
240
320
Steady State Efficiency
80%
Number of Stages
2
Turndown
1
5:1
10:1
Maximum Temperature Rise
3
60/100
Gas Connection Size
1/2"
3/4"
Min/Max External Static Pressure
0.5"/2.5"
Gas Main Pressure
Natural Gas (in. wc)
7-14
7-14
7-14
7-14
7-14
7-14
Propane (in. wc)
12-14
12-14
12-14
12-14
12-14
12-14
Manifold Pressure Natural Gas (per gas valve)
Stage 1 (in. wc)
1 .2
1 .2
1 .2
1 .2
1 .2
1 .2
Stage 2 (in. wc)
3 .2
3 .2
3 .2
3 .2
3 .2
3 .2
Low fire
2
0 .4
0 .4
0 .4
0 .4
0 .4
0 .4
Manifold Pressure Propane Gas (per gas valve)
Stage 1 (in. wc)
2 .3
2 .3
2 .3
2 .3
2 .3
2 .3
Stage 2 (in. wc)
10 .0
10 .0
10 .0
10 .0
10 .0
10 .0
Low fire
2
N/A
N/A
N/A
N/A
N/A
N/A
NOTE:
1. Modulating heat only.
2. Modulating heat not available with propane.
3. Aluminized steel 60°, Stainless steel 100°
Table 15: DPS 016–028 Gas Heating Capacities
Data
Unit Size
016 - 028
Low Heat
Medium Heat
High Heat
Heating Input (MBh)
300
300
450
450
450
600
600
600
Heating Output (MBh)
240
240
360
360
360
480
480
480
Steady State Efficiency
80%
Control (stage/modulating)
2
Mod
2
4
Mod
2
4
Mod
Turndown
2:1
5:1
2:1
4:1
10:1
2:1
4:1
10:1
Maximum Temperature Rise
100
Gas Connection Size
¾"Ø
Min/Max External Static Pressure
0.5"/2.5" wc
Gas Main Pressure
Natural Gas (in wc)
7-14
7-14
7-14
7-14
7-14
7-14
7-14
7-14
Propane Gas (in wc)
12-14
12-14
12-14
12-14
12-14
12-14
12-14
12-14
Manifold Pressure Natural Gas (per gas valve)
Stage 1 (in wc)
0 .88
0 .88
0 .88
0 .88
0 .88
0 .88
0 .88
0 .88
Stage 2 (in wc)
3 .5
3 .5
3 .5
3 .5
3 .5
3 .5
3 .5
3 .5
Low Fire
0 .88
0 .26
0 .88
0 .88
0 .26
0 .88
0 .88
0 .26
Manifold Pressure Propane Gas (per gas valve)
Stage 1 (in wc)
2 .5
2 .5
2 .5
2 .5
2 .5
2 .5
2 .5
2 .5
Stage 2 (in wc)
10 .0
10 .0
10 .0
10 .0
10 .0
10 .0
10 .0
10 .0
Low Fire
2 .5
0 .74
2 .5
2 .5
0 .74
2 .5
2 .5
0 .74
o
pTIonal
g
as
h
eaT
www.DaikinApplied.com
41
IM 1125-7 • REBEL ROOFTOPS
Содержание Rebel DPS003A