Electric Heater Design
If the 10th digit in the model number is an “E”, the rooftop
unit was furnished with a factory installed electric furnace
(Example, DPS010AHCE). The Rebel rooftop units are
available with 4-stage heat output (see capacities in
Table 23
.
This packaged electric heat rooftop unit is designed for outdoor
non-residential installations only.
The electric heat design consists of a heating coil, DDC staging
control, and all operational safeties. The safety switches include
high-limit temperature switches and individual coil fusing.
The high limit switch is an automatic reset switch. It opens the
control circuit and shuts the heater down when the temperature
reaches the high limit switch closes again allows the heater
to run when the temperature gets below dead band. There is
a second level of protection with an auxiliary high limit switch.
This switch opens up and shuts the heater down when the
temperature exceeds the set point. This switch requires a
manual reset .
Electric Heating Capacity Data
Table 13: Heating Capacity – Electric Heaters
Unit Stages
Option # 1
Option # 2
Option # 3
Option # 4
Option # 5
Option # 6
KW MBH Delta
T
1
Min
(cfm) KW MBH
Delta
T
1
Min
(cfm) KW MBH
Delta
T
1
Min
(cfm) KW MBH
Delta
T
1
Min
(cfm) KW MBH
Delta
T
1
Min
(cfm) KW MBH
Delta
T
1
Min
(cfm)
003
2,
SCR
6
20 .5
15 .8
316
12
40 .9
31 .6
632
18
61 .4
47 .4
948
30
102 .4
60 .03
1580
—
—
—
—
—
—
—
—
004
11 .9
23 .7
35 .6
59 .3
—
—
—
—
—
—
—
—
005
9 .5
19 .0
28 .4
47 .4
—
—
—
—
—
—
—
—
006
7 .9
15 .8
23 .7
39 .5
—
—
—
—
—
—
—
—
007
4,
SCR
18
61 .4
19 .0
948
36
122 .9
37 .9
1896
54
184 .3
56 .9
2844 72 .02 245 .8
60 .03
3793
—
—
—
—
—
—
—
—
010
14 .2
28 .4
42 .7
56 .9
—
—
—
—
—
—
—
—
012
11 .9
23 .7
35 .6
47 .4
—
—
—
—
—
—
—
—
015
9 .5
19 .0
28 .4
37 .9
—
—
—
—
—
—
—
—
016
30
102
17 .5
1580
45
154
26 .2
2369
60
205
34 .9
3159
90
307
52 .4
4739
—
—
—
—
—
—
—
—
018
020
13 .5
20 .3
27 .1
40 .6
120
409
54 .2
6319
—
—
—
—
025
10 .8
16 .2
21 .7
32 .5
43 .3
150
512
54 .2
7898
028
9 .8
14 .8
19 .7
29 .5
39 .4
49 .2
NOTE:
1. Temperature is calculated at nominal air flow
NOTE:
2. Not available in 208 & 230 Volt
NOTE:
3. 60 degree max rise