• Outdoor Units • R-410A • RXS-G2V1B
• Split Sky Air • Outdoor Units
12
3
Electrical data
3
24
3
3D059718
Representative Unit Combination
Power Supply
Comp
OFM
IFM
Indoor Unit
Outdoor Unit
Hz-Volts
Voltage Range
MCA
MFA
RHz
RLA
W
FLA
W
FLA
FTXS50G2V1B
RXS50G2V1B
50 - 220
Max. 50Hz 264V
Min. 50Hz 198V
19.75
20
70
6.6
53
0.27
23
0.15
50 - 230
6.2
S
IMBOLS
N
OTES
MCA : Min. circuit amps.
(A)
1
RLA is based on the following conditions.
Indoor temp. 27C°DB/19°CWB
Outdoor Temp. 35°CDB.
2
Maximum allowable voltage variation between phases is 2%.
3
Select wire size based on the lager value of MCA.
4
Instead of fuse, use circuit breaker.
MFA : Max. Fuse Amps.
(A)
RLA
: Rated Load Amps.
(A)
OFM : Outdoor Fan Motor
IFM
: Indoor Fan Motor
FLA
: Full Load Amps
(A)
W
: Fan Motor Rated Output
(W)
RHz
: Rated Operated Frequency
(Hz)